openstudio-standards 0.2.12.rc4 → 0.2.13.rc3
Sign up to get free protection for your applications and to get access to all the features.
- checksums.yaml +4 -4
- data/data/geometry/ASHRAE90120162019HighriseApartment.json +1042 -0
- data/data/geometry/ASHRAE90120162019Hospital.json +199 -0
- data/data/geometry/ASHRAE90120162019LargeHotel.json +73 -0
- data/data/geometry/ASHRAE90120162019LargeOffice.json +109 -0
- data/data/geometry/ASHRAE90120162019SecondarySchool.json +205 -0
- data/data/geometry/ASHRAECourthouse.json +112 -0
- data/data/geometry/ASHRAECourthouse.osm +26470 -0
- data/data/geometry/ASHRAELargeHotel.osm +11 -1
- data/data/geometry/ASHRAELargeOffice.json +4 -0
- data/data/geometry/ASHRAESmallDataCenter.json +1 -1
- data/data/standards/OpenStudio_Standards-ashrae_90_1(space_types).xlsx +0 -0
- data/data/standards/OpenStudio_Standards-ashrae_90_1-ALL-comstock(space_types).xlsx +0 -0
- data/data/standards/OpenStudio_Standards-ashrae_90_1.xlsx +0 -0
- data/data/standards/exclude_list.csv +19 -0
- data/data/standards/export/ashrae_90_1/ashrae_90_1_2004/data/ashrae_90_1_2004.boilers.json +49 -0
- data/data/standards/export/ashrae_90_1/ashrae_90_1_2004/data/ashrae_90_1_2004.chillers.json +293 -0
- data/data/standards/export/ashrae_90_1/ashrae_90_1_2004/data/ashrae_90_1_2004.construction_properties.json +25426 -0
- data/data/standards/export/ashrae_90_1/ashrae_90_1_2004/data/ashrae_90_1_2004.construction_sets.json +1600 -0
- data/data/standards/export/ashrae_90_1/ashrae_90_1_2004/data/ashrae_90_1_2004.economizers.json +564 -0
- data/data/standards/export/ashrae_90_1/ashrae_90_1_2004/data/ashrae_90_1_2004.elevators.json +349 -0
- data/data/standards/export/ashrae_90_1/ashrae_90_1_2004/data/ashrae_90_1_2004.ext_ltg.json +164 -0
- data/data/standards/export/ashrae_90_1/ashrae_90_1_2004/data/ashrae_90_1_2004.ground_temperatures.json +10663 -0
- data/data/standards/export/ashrae_90_1/ashrae_90_1_2004/data/ashrae_90_1_2004.heat_pumps.json +508 -0
- data/data/standards/export/ashrae_90_1/ashrae_90_1_2004/data/ashrae_90_1_2004.heat_pumps_heating.json +156 -0
- data/data/standards/export/ashrae_90_1/ashrae_90_1_2004/data/ashrae_90_1_2004.heat_rejection.json +44 -0
- data/data/standards/export/ashrae_90_1/ashrae_90_1_2004/data/ashrae_90_1_2004.motors.json +184 -0
- data/data/standards/export/ashrae_90_1/ashrae_90_1_2004/data/ashrae_90_1_2004.prototype_inputs.json +3094 -0
- data/data/standards/export/ashrae_90_1/ashrae_90_1_2004/data/ashrae_90_1_2004.ref_cases.json +829 -0
- data/data/standards/export/ashrae_90_1/ashrae_90_1_2004/data/ashrae_90_1_2004.ref_lnup.json +562 -0
- data/data/standards/export/ashrae_90_1/ashrae_90_1_2004/data/ashrae_90_1_2004.refrigeration_compressors.json +52 -0
- data/data/standards/export/ashrae_90_1/ashrae_90_1_2004/data/ashrae_90_1_2004.refrigeration_condenser.json +220 -0
- data/data/standards/export/ashrae_90_1/ashrae_90_1_2004/data/ashrae_90_1_2004.refrigeration_system.json +156 -0
- data/data/standards/export/ashrae_90_1/ashrae_90_1_2004/data/ashrae_90_1_2004.refrigeration_walkins.json +1316 -0
- data/data/standards/export/ashrae_90_1/ashrae_90_1_2004/data/ashrae_90_1_2004.spc_typ.json +21446 -0
- data/data/standards/export/ashrae_90_1/ashrae_90_1_2004/data/ashrae_90_1_2004.unitary_acs.json +554 -0
- data/data/standards/export/ashrae_90_1/ashrae_90_1_2004/data/ashrae_90_1_2004.water_heaters.json +68 -0
- data/data/standards/export/ashrae_90_1/ashrae_90_1_2004/data/ashrae_90_1_2004.water_source_heat_pumps.json +28 -0
- data/data/standards/export/ashrae_90_1/ashrae_90_1_2004/data/ashrae_90_1_2004.water_source_heat_pumps_heating.json +12 -0
- data/data/standards/export/ashrae_90_1/ashrae_90_1_2007/data/ashrae_90_1_2007.boilers.json +49 -0
- data/data/standards/export/ashrae_90_1/ashrae_90_1_2007/data/ashrae_90_1_2007.chillers.json +293 -0
- data/data/standards/export/ashrae_90_1/ashrae_90_1_2007/data/ashrae_90_1_2007.construction_properties.json +12487 -0
- data/data/standards/export/ashrae_90_1/ashrae_90_1_2007/data/ashrae_90_1_2007.construction_sets.json +1600 -0
- data/data/standards/export/ashrae_90_1/ashrae_90_1_2007/data/ashrae_90_1_2007.economizers.json +564 -0
- data/data/standards/export/ashrae_90_1/ashrae_90_1_2007/data/ashrae_90_1_2007.elevators.json +349 -0
- data/data/standards/export/ashrae_90_1/ashrae_90_1_2007/data/ashrae_90_1_2007.ext_ltg.json +164 -0
- data/data/standards/export/ashrae_90_1/ashrae_90_1_2007/data/ashrae_90_1_2007.ground_temperatures.json +10663 -0
- data/data/standards/export/ashrae_90_1/ashrae_90_1_2007/data/ashrae_90_1_2007.heat_pumps.json +466 -0
- data/data/standards/export/ashrae_90_1/ashrae_90_1_2007/data/ashrae_90_1_2007.heat_pumps_heating.json +137 -0
- data/data/standards/export/ashrae_90_1/ashrae_90_1_2007/data/ashrae_90_1_2007.heat_rejection.json +44 -0
- data/data/standards/export/ashrae_90_1/ashrae_90_1_2007/data/ashrae_90_1_2007.motors.json +184 -0
- data/data/standards/export/ashrae_90_1/ashrae_90_1_2007/data/ashrae_90_1_2007.prototype_inputs.json +3094 -0
- data/data/standards/export/ashrae_90_1/ashrae_90_1_2007/data/ashrae_90_1_2007.ref_cases.json +829 -0
- data/data/standards/export/ashrae_90_1/ashrae_90_1_2007/data/ashrae_90_1_2007.ref_lnup.json +562 -0
- data/data/standards/export/ashrae_90_1/ashrae_90_1_2007/data/ashrae_90_1_2007.refrigeration_compressors.json +52 -0
- data/data/standards/export/ashrae_90_1/ashrae_90_1_2007/data/ashrae_90_1_2007.refrigeration_condenser.json +220 -0
- data/data/standards/export/ashrae_90_1/ashrae_90_1_2007/data/ashrae_90_1_2007.refrigeration_system.json +156 -0
- data/data/standards/export/ashrae_90_1/ashrae_90_1_2007/data/ashrae_90_1_2007.refrigeration_walkins.json +1316 -0
- data/data/standards/export/ashrae_90_1/ashrae_90_1_2007/data/ashrae_90_1_2007.spc_typ.json +21380 -0
- data/data/standards/export/ashrae_90_1/ashrae_90_1_2007/data/ashrae_90_1_2007.unitary_acs.json +554 -0
- data/data/standards/export/ashrae_90_1/ashrae_90_1_2007/data/ashrae_90_1_2007.water_heaters.json +68 -0
- data/data/standards/export/ashrae_90_1/ashrae_90_1_2007/data/ashrae_90_1_2007.water_source_heat_pumps.json +28 -0
- data/data/standards/export/ashrae_90_1/ashrae_90_1_2007/data/ashrae_90_1_2007.water_source_heat_pumps_heating.json +12 -0
- data/data/standards/export/ashrae_90_1/ashrae_90_1_2010/data/ashrae_90_1_2010.boilers.json +49 -0
- data/data/standards/export/ashrae_90_1/ashrae_90_1_2010/data/ashrae_90_1_2010.chillers.json +395 -0
- data/data/standards/export/ashrae_90_1/ashrae_90_1_2010/data/ashrae_90_1_2010.construction_properties.json +12487 -0
- data/data/standards/export/ashrae_90_1/ashrae_90_1_2010/data/ashrae_90_1_2010.construction_sets.json +1600 -0
- data/data/standards/export/ashrae_90_1/ashrae_90_1_2010/data/ashrae_90_1_2010.economizers.json +592 -0
- data/data/standards/export/ashrae_90_1/ashrae_90_1_2010/data/ashrae_90_1_2010.elevators.json +349 -0
- data/data/standards/export/ashrae_90_1/ashrae_90_1_2010/data/ashrae_90_1_2010.energy_recovery.json +550 -0
- data/data/standards/export/ashrae_90_1/ashrae_90_1_2010/data/ashrae_90_1_2010.ext_ltg.json +164 -0
- data/data/standards/export/ashrae_90_1/ashrae_90_1_2010/data/ashrae_90_1_2010.ground_temperatures.json +10663 -0
- data/data/standards/export/ashrae_90_1/ashrae_90_1_2010/data/ashrae_90_1_2010.heat_pumps.json +466 -0
- data/data/standards/export/ashrae_90_1/ashrae_90_1_2010/data/ashrae_90_1_2010.heat_pumps_heating.json +137 -0
- data/data/standards/export/ashrae_90_1/ashrae_90_1_2010/data/ashrae_90_1_2010.heat_rejection.json +44 -0
- data/data/standards/export/ashrae_90_1/ashrae_90_1_2010/data/ashrae_90_1_2010.motors.json +238 -0
- data/data/standards/export/ashrae_90_1/ashrae_90_1_2010/data/ashrae_90_1_2010.prototype_inputs.json +3094 -0
- data/data/standards/export/ashrae_90_1/ashrae_90_1_2010/data/ashrae_90_1_2010.ref_cases.json +829 -0
- data/data/standards/export/ashrae_90_1/ashrae_90_1_2010/data/ashrae_90_1_2010.ref_lnup.json +562 -0
- data/data/standards/export/ashrae_90_1/ashrae_90_1_2010/data/ashrae_90_1_2010.refrigeration_compressors.json +52 -0
- data/data/standards/export/ashrae_90_1/ashrae_90_1_2010/data/ashrae_90_1_2010.refrigeration_condenser.json +220 -0
- data/data/standards/export/ashrae_90_1/ashrae_90_1_2010/data/ashrae_90_1_2010.refrigeration_system.json +156 -0
- data/data/standards/export/ashrae_90_1/ashrae_90_1_2010/data/ashrae_90_1_2010.refrigeration_walkins.json +1316 -0
- data/data/standards/export/ashrae_90_1/ashrae_90_1_2010/data/ashrae_90_1_2010.spc_typ.json +21548 -0
- data/data/standards/export/ashrae_90_1/ashrae_90_1_2010/data/ashrae_90_1_2010.unitary_acs.json +554 -0
- data/data/standards/export/ashrae_90_1/ashrae_90_1_2010/data/ashrae_90_1_2010.water_heaters.json +68 -0
- data/data/standards/export/ashrae_90_1/ashrae_90_1_2010/data/ashrae_90_1_2010.water_source_heat_pumps.json +28 -0
- data/data/standards/export/ashrae_90_1/ashrae_90_1_2010/data/ashrae_90_1_2010.water_source_heat_pumps_heating.json +12 -0
- data/data/standards/export/ashrae_90_1/ashrae_90_1_2013/data/ashrae_90_1_2013.boilers.json +64 -0
- data/data/standards/export/ashrae_90_1/ashrae_90_1_2013/data/ashrae_90_1_2013.chillers.json +871 -0
- data/data/standards/export/ashrae_90_1/ashrae_90_1_2013/data/ashrae_90_1_2013.construction_properties.json +12487 -0
- data/data/standards/export/ashrae_90_1/ashrae_90_1_2013/data/ashrae_90_1_2013.construction_sets.json +1600 -0
- data/data/standards/export/ashrae_90_1/ashrae_90_1_2013/data/ashrae_90_1_2013.economizers.json +592 -0
- data/data/standards/export/ashrae_90_1/ashrae_90_1_2013/data/ashrae_90_1_2013.elevators.json +349 -0
- data/data/standards/export/ashrae_90_1/ashrae_90_1_2013/data/ashrae_90_1_2013.energy_recovery.json +1096 -0
- data/data/standards/export/ashrae_90_1/ashrae_90_1_2013/data/ashrae_90_1_2013.ext_ltg.json +164 -0
- data/data/standards/export/ashrae_90_1/ashrae_90_1_2013/data/ashrae_90_1_2013.ground_temperatures.json +10663 -0
- data/data/standards/export/ashrae_90_1/ashrae_90_1_2013/data/ashrae_90_1_2013.heat_pumps.json +886 -0
- data/data/standards/export/ashrae_90_1/ashrae_90_1_2013/data/ashrae_90_1_2013.heat_pumps_heating.json +194 -0
- data/data/standards/export/ashrae_90_1/ashrae_90_1_2013/data/ashrae_90_1_2013.heat_rejection.json +44 -0
- data/data/standards/export/ashrae_90_1/ashrae_90_1_2013/data/ashrae_90_1_2013.motors.json +247 -0
- data/data/standards/export/ashrae_90_1/ashrae_90_1_2013/data/ashrae_90_1_2013.prototype_inputs.json +3094 -0
- data/data/standards/export/ashrae_90_1/ashrae_90_1_2013/data/ashrae_90_1_2013.ref_cases.json +829 -0
- data/data/standards/export/ashrae_90_1/ashrae_90_1_2013/data/ashrae_90_1_2013.ref_lnup.json +562 -0
- data/data/standards/export/ashrae_90_1/ashrae_90_1_2013/data/ashrae_90_1_2013.refrigeration_compressors.json +52 -0
- data/data/standards/export/ashrae_90_1/ashrae_90_1_2013/data/ashrae_90_1_2013.refrigeration_condenser.json +220 -0
- data/data/standards/export/ashrae_90_1/ashrae_90_1_2013/data/ashrae_90_1_2013.refrigeration_system.json +156 -0
- data/data/standards/export/ashrae_90_1/ashrae_90_1_2013/data/ashrae_90_1_2013.refrigeration_walkins.json +1316 -0
- data/data/standards/export/ashrae_90_1/ashrae_90_1_2013/data/ashrae_90_1_2013.spc_typ.json +22079 -0
- data/data/standards/export/ashrae_90_1/ashrae_90_1_2013/data/ashrae_90_1_2013.unitary_acs.json +994 -0
- data/data/standards/export/ashrae_90_1/ashrae_90_1_2013/data/ashrae_90_1_2013.water_heaters.json +68 -0
- data/data/standards/export/ashrae_90_1/ashrae_90_1_2013/data/ashrae_90_1_2013.water_source_heat_pumps.json +28 -0
- data/data/standards/export/ashrae_90_1/ashrae_90_1_2013/data/ashrae_90_1_2013.water_source_heat_pumps_heating.json +12 -0
- data/data/standards/manage_OpenStudio_Standards.rb +87 -37
- data/data/standards/metadata_units_OpenStudio_Standards-ashrae_90_1-ALL-comstockspace_types.csv +236 -0
- data/data/standards/metadata_units_OpenStudio_Standards-ashrae_90_1.csv +622 -0
- data/data/standards/metadata_units_OpenStudio_Standards-ashrae_90_1space_types.csv +191 -0
- data/data/standards/openstudio_standards_duplicates_log.csv +17 -0
- data/data/standards/test_performance_expected_dd_results.csv +1971 -1171
- data/lib/openstudio-standards.rb +76 -18
- data/lib/openstudio-standards/btap/btap.model.rb +1 -1
- data/lib/openstudio-standards/btap/economics.rb +14 -11
- data/lib/openstudio-standards/btap/envelope.rb +185 -257
- data/lib/openstudio-standards/btap/fileio.rb +1 -0
- data/lib/openstudio-standards/btap/geometry.rb +21 -1
- data/lib/openstudio-standards/btap/measures.rb +12 -11
- data/lib/openstudio-standards/btap/schedules.rb +3 -12
- data/lib/openstudio-standards/hvac_sizing/Siz.AirLoopHVACUnitaryHeatPumpAirToAirMultiSpeed.rb +178 -0
- data/lib/openstudio-standards/hvac_sizing/Siz.CoilCoolingDXMultiSpeed.rb +8 -8
- data/lib/openstudio-standards/hvac_sizing/Siz.Model.rb +3 -0
- data/lib/openstudio-standards/prototypes/ashrae_90_1/ashrae_90_1_2004/ashrae_90_1_2004.PumpVariableSpeed.rb +28 -0
- data/lib/openstudio-standards/prototypes/ashrae_90_1/ashrae_90_1_2007/ashrae_90_1_2007.FanVariableVolume.rb +0 -1
- data/lib/openstudio-standards/prototypes/ashrae_90_1/ashrae_90_1_2007/ashrae_90_1_2007.PumpVariableSpeed.rb +28 -0
- data/lib/openstudio-standards/prototypes/ashrae_90_1/ashrae_90_1_2010/ashrae_90_1_2010.Model.rb +53 -2
- data/lib/openstudio-standards/prototypes/ashrae_90_1/ashrae_90_1_2010/ashrae_90_1_2010.PumpVariableSpeed.rb +29 -0
- data/lib/openstudio-standards/prototypes/ashrae_90_1/ashrae_90_1_2013/ashrae_90_1_2013.Model.rb +157 -2
- data/lib/openstudio-standards/prototypes/ashrae_90_1/ashrae_90_1_2013/ashrae_90_1_2013.PumpVariableSpeed.rb +29 -0
- data/lib/openstudio-standards/prototypes/ashrae_90_1/ashrae_90_1_2016/ashrae_90_1_2016.AirTerminalSingleDuctVAVReheat.rb +24 -0
- data/lib/openstudio-standards/prototypes/ashrae_90_1/ashrae_90_1_2016/ashrae_90_1_2016.FanConstantVolume.rb +32 -0
- data/lib/openstudio-standards/prototypes/ashrae_90_1/ashrae_90_1_2016/ashrae_90_1_2016.FanOnOff.rb +33 -0
- data/lib/openstudio-standards/prototypes/ashrae_90_1/ashrae_90_1_2016/ashrae_90_1_2016.FanVariableVolume.rb +32 -0
- data/lib/openstudio-standards/prototypes/ashrae_90_1/ashrae_90_1_2016/ashrae_90_1_2016.Model.elevators.rb +25 -0
- data/lib/openstudio-standards/prototypes/ashrae_90_1/ashrae_90_1_2016/ashrae_90_1_2016.Model.rb +366 -0
- data/lib/openstudio-standards/prototypes/ashrae_90_1/ashrae_90_1_2016/ashrae_90_1_2016.PumpVariableSpeed.rb +144 -0
- data/lib/openstudio-standards/prototypes/ashrae_90_1/ashrae_90_1_2016/ashrae_90_1_2016.hvac_systems.rb +11 -0
- data/lib/openstudio-standards/prototypes/ashrae_90_1/ashrae_90_1_2019/ashrae_90_1_2019.AirTerminalSingleDuctVAVReheat.rb +24 -0
- data/lib/openstudio-standards/prototypes/ashrae_90_1/ashrae_90_1_2019/ashrae_90_1_2019.FanConstantVolume.rb +32 -0
- data/lib/openstudio-standards/prototypes/ashrae_90_1/ashrae_90_1_2019/ashrae_90_1_2019.FanOnOff.rb +33 -0
- data/lib/openstudio-standards/prototypes/ashrae_90_1/ashrae_90_1_2019/ashrae_90_1_2019.FanVariableVolume.rb +32 -0
- data/lib/openstudio-standards/prototypes/ashrae_90_1/ashrae_90_1_2019/ashrae_90_1_2019.Model.elevators.rb +25 -0
- data/lib/openstudio-standards/prototypes/ashrae_90_1/ashrae_90_1_2019/ashrae_90_1_2019.Model.rb +367 -0
- data/lib/openstudio-standards/prototypes/ashrae_90_1/ashrae_90_1_2019/ashrae_90_1_2019.PumpVariableSpeed.rb +144 -0
- data/lib/openstudio-standards/prototypes/ashrae_90_1/ashrae_90_1_2019/ashrae_90_1_2019.hvac_systems.rb +11 -0
- data/lib/openstudio-standards/prototypes/ashrae_90_1/doe_ref_1980_2004/doe_ref_1980_2004.AirTerminalSingleDuctVAVReheat.rb +0 -1
- data/lib/openstudio-standards/prototypes/ashrae_90_1/doe_ref_pre_1980/doe_ref_pre_1980.AirTerminalSingleDuctVAVReheat.rb +0 -1
- data/lib/openstudio-standards/prototypes/ashrae_90_1/nrel_nze_ready_2017/nrel_zne_ready_2017.HeatExchangerAirToAirSensibleAndLatent.rb +1 -1
- data/lib/openstudio-standards/prototypes/ashrae_90_1/nrel_nze_ready_2017/nrel_zne_ready_2017.Model.rb +1 -1
- data/lib/openstudio-standards/prototypes/ashrae_90_1/ze_aedg_multifamily/ze_aedg_multifamily.HeatExchangerAirToAirSensibleAndLatent.rb +1 -1
- data/lib/openstudio-standards/prototypes/ashrae_90_1/ze_aedg_multifamily/ze_aedg_multifamily.Model.rb +1 -1
- data/lib/openstudio-standards/prototypes/common/buildings/Prototype.College.rb +3 -3
- data/lib/openstudio-standards/prototypes/common/buildings/Prototype.Courthouse.rb +74 -0
- data/lib/openstudio-standards/prototypes/common/buildings/Prototype.FullServiceRestaurant.rb +46 -30
- data/lib/openstudio-standards/prototypes/common/buildings/Prototype.HighRiseApartment.rb +23 -8
- data/lib/openstudio-standards/prototypes/common/buildings/Prototype.Hospital.rb +26 -15
- data/lib/openstudio-standards/prototypes/common/buildings/Prototype.Laboratory.rb +8 -11
- data/lib/openstudio-standards/prototypes/common/buildings/Prototype.LargeDataCenterHighITE.rb +54 -60
- data/lib/openstudio-standards/prototypes/common/buildings/Prototype.LargeDataCenterLowITE.rb +56 -60
- data/lib/openstudio-standards/prototypes/common/buildings/Prototype.LargeHotel.rb +38 -12
- data/lib/openstudio-standards/prototypes/common/buildings/Prototype.LargeOffice.rb +218 -134
- data/lib/openstudio-standards/prototypes/common/buildings/Prototype.LargeOfficeDetailed.rb +6 -2
- data/lib/openstudio-standards/prototypes/common/buildings/Prototype.MediumOffice.rb +230 -134
- data/lib/openstudio-standards/prototypes/common/buildings/Prototype.MediumOfficeDetailed.rb +60 -62
- data/lib/openstudio-standards/prototypes/common/buildings/Prototype.MidriseApartment.rb +25 -15
- data/lib/openstudio-standards/prototypes/common/buildings/Prototype.Outpatient.rb +34 -22
- data/lib/openstudio-standards/prototypes/common/buildings/Prototype.PrimarySchool.rb +31 -7
- data/lib/openstudio-standards/prototypes/common/buildings/Prototype.QuickServiceRestaurant.rb +43 -28
- data/lib/openstudio-standards/prototypes/common/buildings/Prototype.RetailStandalone.rb +48 -38
- data/lib/openstudio-standards/prototypes/common/buildings/Prototype.RetailStripmall.rb +9 -5
- data/lib/openstudio-standards/prototypes/common/buildings/Prototype.SecondarySchool.rb +575 -345
- data/lib/openstudio-standards/prototypes/common/buildings/Prototype.SmallDataCenterHighITE.rb +13 -19
- data/lib/openstudio-standards/prototypes/common/buildings/Prototype.SmallDataCenterLowITE.rb +13 -17
- data/lib/openstudio-standards/prototypes/common/buildings/Prototype.SmallHotel.rb +9 -5
- data/lib/openstudio-standards/prototypes/common/buildings/Prototype.SmallOffice.rb +79 -51
- data/lib/openstudio-standards/prototypes/common/buildings/Prototype.SmallOfficeDetailed.rb +60 -60
- data/lib/openstudio-standards/prototypes/common/buildings/Prototype.SuperMarket.rb +2 -4
- data/lib/openstudio-standards/prototypes/common/buildings/Prototype.SuperTallBuilding.rb +133 -120
- data/lib/openstudio-standards/prototypes/common/buildings/Prototype.TallBuilding.rb +124 -112
- data/lib/openstudio-standards/prototypes/common/buildings/Prototype.Warehouse.rb +138 -66
- data/lib/openstudio-standards/prototypes/common/do_not_edit_metaclasses.rb +7275 -199
- data/lib/openstudio-standards/prototypes/common/objects/Prototype.AirConditionerVariableRefrigerantFlow.rb +35 -35
- data/lib/openstudio-standards/prototypes/common/objects/Prototype.BoilerHotWater.rb +2 -2
- data/lib/openstudio-standards/prototypes/common/objects/Prototype.CentralAirSourceHeatPump.rb +2 -2
- data/lib/openstudio-standards/prototypes/common/objects/Prototype.CoilCoolingDXSingleSpeed.rb +3 -3
- data/lib/openstudio-standards/prototypes/common/objects/Prototype.CoilCoolingDXTwoSpeed.rb +1 -1
- data/lib/openstudio-standards/prototypes/common/objects/Prototype.CoilCoolingWater.rb +2 -2
- data/lib/openstudio-standards/prototypes/common/objects/Prototype.CoilCoolingWaterToAirHeatPumpEquationFit.rb +2 -2
- data/lib/openstudio-standards/prototypes/common/objects/Prototype.CoilHeatingDXSingleSpeed.rb +1 -1
- data/lib/openstudio-standards/prototypes/common/objects/Prototype.CoilHeatingElectric.rb +2 -2
- data/lib/openstudio-standards/prototypes/common/objects/Prototype.CoilHeatingWater.rb +2 -2
- data/lib/openstudio-standards/prototypes/common/objects/Prototype.CoilHeatingWaterToAirHeatPumpEquationFit.rb +2 -2
- data/lib/openstudio-standards/prototypes/common/objects/Prototype.CoolingTower.rb +1 -1
- data/lib/openstudio-standards/prototypes/common/objects/Prototype.Fan.rb +4 -3
- data/lib/openstudio-standards/prototypes/common/objects/Prototype.FanConstantVolume.rb +7 -8
- data/lib/openstudio-standards/prototypes/common/objects/Prototype.FanOnOff.rb +7 -8
- data/lib/openstudio-standards/prototypes/common/objects/Prototype.FanVariableVolume.rb +13 -14
- data/lib/openstudio-standards/prototypes/common/objects/Prototype.FanZoneExhaust.rb +7 -5
- data/lib/openstudio-standards/prototypes/common/objects/Prototype.Model.elevators.rb +4 -1
- data/lib/openstudio-standards/prototypes/common/objects/Prototype.Model.exterior_lights.rb +0 -1
- data/lib/openstudio-standards/prototypes/common/objects/Prototype.Model.hvac.rb +25 -14
- data/lib/openstudio-standards/prototypes/common/objects/Prototype.Model.rb +474 -89
- data/lib/openstudio-standards/prototypes/common/objects/Prototype.Model.swh.rb +35 -33
- data/lib/openstudio-standards/prototypes/common/objects/Prototype.Pump.rb +3 -0
- data/lib/openstudio-standards/prototypes/common/objects/Prototype.PumpVariableSpeed.rb +72 -0
- data/lib/openstudio-standards/prototypes/common/objects/Prototype.ServiceWaterHeating.rb +120 -120
- data/lib/openstudio-standards/prototypes/common/objects/Prototype.hvac_systems.rb +142 -154
- data/lib/openstudio-standards/prototypes/common/objects/Prototype.radiant_system_controls.rb +9 -3
- data/lib/openstudio-standards/prototypes/common/objects/Prototype.refrigeration.rb +11 -5
- data/lib/openstudio-standards/prototypes/common/objects/Prototype.utilities.rb +26 -14
- data/lib/openstudio-standards/prototypes/common/prototype_metaprogramming.rb +270 -247
- data/lib/openstudio-standards/prototypes/deer/deer.Model.rb +1 -1
- data/lib/openstudio-standards/refs/references.rb +5 -2
- data/lib/openstudio-standards/standards/Standards.AirLoopHVAC.rb +70 -51
- data/lib/openstudio-standards/standards/Standards.AirTerminalSingleDuctVAVReheat.rb +0 -1
- data/lib/openstudio-standards/standards/Standards.BoilerHotWater.rb +0 -1
- data/lib/openstudio-standards/standards/Standards.BuildingStory.rb +1 -0
- data/lib/openstudio-standards/standards/Standards.ChillerElectricEIR.rb +2 -4
- data/lib/openstudio-standards/standards/Standards.CoilCoolingDXMultiSpeed.rb +91 -2
- data/lib/openstudio-standards/standards/Standards.CoilCoolingDXSingleSpeed.rb +4 -5
- data/lib/openstudio-standards/standards/Standards.CoilCoolingDXTwoSpeed.rb +0 -1
- data/lib/openstudio-standards/standards/Standards.CoilCoolingWaterToAirHeatPumpEquationFit.rb +1 -1
- data/lib/openstudio-standards/standards/Standards.CoilDX.rb +30 -9
- data/lib/openstudio-standards/standards/Standards.CoilHeatingDXMultiSpeed.rb +2 -1
- data/lib/openstudio-standards/standards/Standards.CoilHeatingDXSingleSpeed.rb +3 -1
- data/lib/openstudio-standards/standards/Standards.CoilHeatingGas.rb +0 -3
- data/lib/openstudio-standards/standards/Standards.CoilHeatingGasMultiStage.rb +37 -1
- data/lib/openstudio-standards/standards/Standards.CoilHeatingWaterToAirHeatPumpEquationFit.rb +1 -3
- data/lib/openstudio-standards/standards/Standards.Construction.rb +124 -118
- data/lib/openstudio-standards/standards/Standards.CoolingTower.rb +0 -1
- data/lib/openstudio-standards/standards/Standards.CoolingTowerSingleSpeed.rb +0 -1
- data/lib/openstudio-standards/standards/Standards.CoolingTowerTwoSpeed.rb +0 -1
- data/lib/openstudio-standards/standards/Standards.CoolingTowerVariableSpeed.rb +0 -1
- data/lib/openstudio-standards/standards/Standards.Fan.rb +0 -1
- data/lib/openstudio-standards/standards/Standards.FanConstantVolume.rb +0 -1
- data/lib/openstudio-standards/standards/Standards.FanOnOff.rb +0 -1
- data/lib/openstudio-standards/standards/Standards.FanVariableVolume.rb +2 -4
- data/lib/openstudio-standards/standards/Standards.FanZoneExhaust.rb +0 -1
- data/lib/openstudio-standards/standards/Standards.FluidCooler.rb +10 -3
- data/lib/openstudio-standards/standards/Standards.HeaderedPumpsConstantSpeed.rb +0 -1
- data/lib/openstudio-standards/standards/Standards.HeaderedPumpsVariableSpeed.rb +0 -1
- data/lib/openstudio-standards/standards/Standards.Model.rb +305 -247
- data/lib/openstudio-standards/standards/Standards.PlanarSurface.rb +2 -0
- data/lib/openstudio-standards/standards/Standards.PlantLoop.rb +11 -9
- data/lib/openstudio-standards/standards/Standards.Pump.rb +0 -1
- data/lib/openstudio-standards/standards/Standards.PumpConstantSpeed.rb +0 -1
- data/lib/openstudio-standards/standards/Standards.PumpVariableSpeed.rb +0 -1
- data/lib/openstudio-standards/standards/Standards.ScheduleCompact.rb +0 -1
- data/lib/openstudio-standards/standards/Standards.ScheduleConstant.rb +0 -1
- data/lib/openstudio-standards/standards/Standards.ScheduleRuleset.rb +103 -121
- data/lib/openstudio-standards/standards/Standards.Space.rb +42 -35
- data/lib/openstudio-standards/standards/Standards.SpaceType.rb +9 -17
- data/lib/openstudio-standards/standards/Standards.SubSurface.rb +25 -27
- data/lib/openstudio-standards/standards/Standards.Surface.rb +97 -52
- data/lib/openstudio-standards/standards/Standards.ThermalZone.rb +76 -25
- data/lib/openstudio-standards/standards/Standards.WaterHeaterMixed.rb +6 -7
- data/lib/openstudio-standards/standards/Standards.ZoneHVACComponent.rb +85 -7
- data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1.Standards.FanVariableVolume.rb +0 -1
- data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2004/ashrae_90_1_2004.AirLoopHVAC.rb +10 -2
- data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2004/ashrae_90_1_2004.Model.rb +2 -2
- data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2004/comstock_ashrae_90_1_2004/data/ashrae_90_1.schedules.json +63 -99
- data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2004/comstock_ashrae_90_1_2004/data/comstock_ashrae_90_1_2004.ext_ltg.json +7 -7
- data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2004/data/ashrae_90_1_2004.construction_properties.json +2420 -0
- data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2004/data/ashrae_90_1_2004.economizers.json +32 -0
- data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2004/data/ashrae_90_1_2004.heat_rejection.json +9 -0
- data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2004/data/ashrae_90_1_2004.prototype_inputs.json +70 -40
- data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2004/data/ashrae_90_1_2004.spc_typ.json +105 -40
- data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2004/data/ashrae_90_1_2004.unitary_acs.json +15 -15
- data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2007/ashrae_90_1_2007.AirLoopHVAC.rb +5 -1
- data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2007/comstock_ashrae_90_1_2007/data/ashrae_90_1.schedules.json +63 -99
- data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2007/comstock_ashrae_90_1_2007/data/comstock_ashrae_90_1_2007.ext_ltg.json +7 -7
- data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2007/data/ashrae_90_1_2007.construction_properties.json +1460 -0
- data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2007/data/ashrae_90_1_2007.economizers.json +32 -0
- data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2007/data/ashrae_90_1_2007.heat_rejection.json +9 -0
- data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2007/data/ashrae_90_1_2007.prototype_inputs.json +123 -39
- data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2007/data/ashrae_90_1_2007.spc_typ.json +104 -17
- data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2007/data/ashrae_90_1_2007.unitary_acs.json +15 -15
- data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2010/ashrae_90_1_2010.AirLoopHVAC.rb +32 -15
- data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2010/ashrae_90_1_2010.Space.rb +1 -1
- data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2010/comstock_ashrae_90_1_2010/data/ashrae_90_1.schedules.json +63 -99
- data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2010/comstock_ashrae_90_1_2010/data/comstock_ashrae_90_1_2010.ext_ltg.json +7 -7
- data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2010/data/ashrae_90_1_2010.construction_properties.json +1460 -0
- data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2010/data/ashrae_90_1_2010.economizers.json +64 -0
- data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2010/data/ashrae_90_1_2010.energy_recovery.json +52 -0
- data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2010/data/ashrae_90_1_2010.heat_rejection.json +9 -0
- data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2010/data/ashrae_90_1_2010.prototype_inputs.json +123 -39
- data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2010/data/ashrae_90_1_2010.spc_typ.json +112 -25
- data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2010/data/ashrae_90_1_2010.unitary_acs.json +5 -5
- data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2013/ashrae_90_1_2013.AirLoopHVAC.rb +37 -14
- data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2013/ashrae_90_1_2013.WaterHeaterMixed.rb +1 -1
- data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2013/comstock_ashrae_90_1_2013/data/ashrae_90_1.schedules.json +63 -99
- data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2013/comstock_ashrae_90_1_2013/data/comstock_ashrae_90_1_2013.ext_ltg.json +7 -7
- data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2013/data/ashrae_90_1_2013.boilers.json +1 -1
- data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2013/data/ashrae_90_1_2013.chillers.json +2 -2
- data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2013/data/ashrae_90_1_2013.construction_properties.json +1460 -0
- data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2013/data/ashrae_90_1_2013.economizers.json +64 -0
- data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2013/data/ashrae_90_1_2013.energy_recovery.json +104 -0
- data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2013/data/ashrae_90_1_2013.heat_rejection.json +9 -0
- data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2013/data/ashrae_90_1_2013.prototype_inputs.json +125 -41
- data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2013/data/ashrae_90_1_2013.spc_typ.json +172 -55
- data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2013/data/ashrae_90_1_2013.unitary_acs.json +15 -15
- data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2013/data/ashrae_90_1_2013.water_heaters.json +4 -4
- data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2013/data/ashrae_90_1_2013.water_source_heat_pumps_heating.json +1 -1
- data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2016/ashrae_90_1_2016.AirLoopHVAC.rb +456 -0
- data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2016/ashrae_90_1_2016.AirTerminalSingleDuctVAVReheat.rb +24 -0
- data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2016/ashrae_90_1_2016.CoolingTower.rb +19 -0
- data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2016/ashrae_90_1_2016.CoolingTowerSingleSpeed.rb +5 -0
- data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2016/ashrae_90_1_2016.CoolingTowerTwoSpeed.rb +5 -0
- data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2016/ashrae_90_1_2016.CoolingTowerVariableSpeed.rb +16 -0
- data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2016/ashrae_90_1_2016.FanVariableVolume.rb +37 -0
- data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2016/ashrae_90_1_2016.Space.rb +189 -0
- data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2016/ashrae_90_1_2016.ThermalZone.rb +57 -0
- data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2016/ashrae_90_1_2016.ZoneHVACComponent.rb +22 -0
- data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2016/ashrae_90_1_2016.rb +16 -0
- data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2016/data/ashrae_90_1_2016.boilers.json +68 -0
- data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2016/data/ashrae_90_1_2016.chillers.json +490 -0
- data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2016/data/ashrae_90_1_2016.construction_properties.json +21244 -0
- data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2016/data/ashrae_90_1_2016.construction_sets.json +2111 -0
- data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2016/data/ashrae_90_1_2016.economizers.json +676 -0
- data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2016/data/ashrae_90_1_2016.elevators.json +372 -0
- data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2016/data/ashrae_90_1_2016.energy_recovery.json +1096 -0
- data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2016/data/ashrae_90_1_2016.ext_ltg.json +169 -0
- data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2016/data/ashrae_90_1_2016.heat_pumps.json +532 -0
- data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2016/data/ashrae_90_1_2016.heat_pumps_heating.json +164 -0
- data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2016/data/ashrae_90_1_2016.heat_rejection.json +49 -0
- data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2016/data/ashrae_90_1_2016.motors.json +274 -0
- data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2016/data/ashrae_90_1_2016.prototype_inputs.json +3094 -0
- data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2016/data/ashrae_90_1_2016.ref_cases.json +854 -0
- data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2016/data/ashrae_90_1_2016.ref_lnup.json +562 -0
- data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2016/data/ashrae_90_1_2016.refrigeration_compressors.json +58 -0
- data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2016/data/ashrae_90_1_2016.refrigeration_condenser.json +238 -0
- data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2016/data/ashrae_90_1_2016.refrigeration_system.json +12 -0
- data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2016/data/ashrae_90_1_2016.refrigeration_walkins.json +1316 -0
- data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2016/data/ashrae_90_1_2016.spc_typ.json +23067 -0
- data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2016/data/ashrae_90_1_2016.unitary_acs.json +648 -0
- data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2016/data/ashrae_90_1_2016.water_heaters.json +72 -0
- data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2016/data/ashrae_90_1_2016.water_source_heat_pumps.json +31 -0
- data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2016/data/ashrae_90_1_2016.water_source_heat_pumps_heating.json +13 -0
- data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2019/ashrae_90_1_2019.AirLoopHVAC.rb +456 -0
- data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2019/ashrae_90_1_2019.AirTerminalSingleDuctVAVReheat.rb +24 -0
- data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2019/ashrae_90_1_2019.CoolingTower.rb +19 -0
- data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2019/ashrae_90_1_2019.CoolingTowerSingleSpeed.rb +5 -0
- data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2019/ashrae_90_1_2019.CoolingTowerTwoSpeed.rb +5 -0
- data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2019/ashrae_90_1_2019.CoolingTowerVariableSpeed.rb +16 -0
- data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2019/ashrae_90_1_2019.FanVariableVolume.rb +37 -0
- data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2019/ashrae_90_1_2019.Space.rb +189 -0
- data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2019/ashrae_90_1_2019.ThermalZone.rb +57 -0
- data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2019/ashrae_90_1_2019.ZoneHVACComponent.rb +22 -0
- data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2019/ashrae_90_1_2019.rb +16 -0
- data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2019/data/ashrae_90_1_2019.boilers.json +68 -0
- data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2019/data/ashrae_90_1_2019.chillers.json +490 -0
- data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2019/data/ashrae_90_1_2019.construction_properties.json +21244 -0
- data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2019/data/ashrae_90_1_2019.construction_sets.json +2111 -0
- data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2019/data/ashrae_90_1_2019.economizers.json +676 -0
- data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2019/data/ashrae_90_1_2019.elevators.json +372 -0
- data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2019/data/ashrae_90_1_2019.energy_recovery.json +1096 -0
- data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2019/data/ashrae_90_1_2019.ext_ltg.json +169 -0
- data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2019/data/ashrae_90_1_2019.heat_pumps.json +664 -0
- data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2019/data/ashrae_90_1_2019.heat_pumps_heating.json +204 -0
- data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2019/data/ashrae_90_1_2019.heat_rejection.json +49 -0
- data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2019/data/ashrae_90_1_2019.motors.json +274 -0
- data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2019/data/ashrae_90_1_2019.prototype_inputs.json +3094 -0
- data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2019/data/ashrae_90_1_2019.ref_cases.json +854 -0
- data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2019/data/ashrae_90_1_2019.ref_lnup.json +562 -0
- data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2019/data/ashrae_90_1_2019.refrigeration_compressors.json +58 -0
- data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2019/data/ashrae_90_1_2019.refrigeration_condenser.json +238 -0
- data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2019/data/ashrae_90_1_2019.refrigeration_system.json +12 -0
- data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2019/data/ashrae_90_1_2019.refrigeration_walkins.json +1316 -0
- data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2019/data/ashrae_90_1_2019.spc_typ.json +23067 -0
- data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2019/data/ashrae_90_1_2019.unitary_acs.json +671 -0
- data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2019/data/ashrae_90_1_2019.water_heaters.json +72 -0
- data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2019/data/ashrae_90_1_2019.water_source_heat_pumps.json +31 -0
- data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2019/data/ashrae_90_1_2019.water_source_heat_pumps_heating.json +13 -0
- data/lib/openstudio-standards/standards/ashrae_90_1/data/ashrae_90_1.constructions.json +1662 -332
- data/lib/openstudio-standards/standards/ashrae_90_1/data/ashrae_90_1.fans.json +1 -1
- data/lib/openstudio-standards/standards/ashrae_90_1/data/ashrae_90_1.materials.json +4994 -234
- data/lib/openstudio-standards/standards/ashrae_90_1/data/ashrae_90_1.schedules.json +1743 -161
- data/lib/openstudio-standards/standards/ashrae_90_1/doe_ref_1980_2004/comstock_doe_ref_1980_2004/data/ashrae_90_1.schedules.json +63 -99
- data/lib/openstudio-standards/standards/ashrae_90_1/doe_ref_1980_2004/comstock_doe_ref_1980_2004/data/comstock_doe_ref_1980_2004.ext_ltg.json +11 -11
- data/lib/openstudio-standards/standards/ashrae_90_1/doe_ref_1980_2004/data/doe_ref_1980_2004.heat_rejection.json +9 -0
- data/lib/openstudio-standards/standards/ashrae_90_1/doe_ref_1980_2004/data/doe_ref_1980_2004.prototype_inputs.json +8 -8
- data/lib/openstudio-standards/standards/ashrae_90_1/doe_ref_1980_2004/data/doe_ref_1980_2004.spc_typ.json +5967 -2727
- data/lib/openstudio-standards/standards/ashrae_90_1/doe_ref_1980_2004/doe_ref_1980_2004.Model.rb +4 -4
- data/lib/openstudio-standards/standards/ashrae_90_1/doe_ref_pre_1980/comstock_doe_ref_pre_1980/data/ashrae_90_1.schedules.json +63 -99
- data/lib/openstudio-standards/standards/ashrae_90_1/doe_ref_pre_1980/comstock_doe_ref_pre_1980/data/comstock_doe_ref_pre_1980.ext_ltg.json +10 -10
- data/lib/openstudio-standards/standards/ashrae_90_1/doe_ref_pre_1980/data/doe_ref_pre_1980.heat_rejection.json +9 -0
- data/lib/openstudio-standards/standards/ashrae_90_1/doe_ref_pre_1980/data/doe_ref_pre_1980.prototype_inputs.json +7 -7
- data/lib/openstudio-standards/standards/ashrae_90_1/doe_ref_pre_1980/data/doe_ref_pre_1980.spc_typ.json +5920 -2700
- data/lib/openstudio-standards/standards/ashrae_90_1/doe_ref_pre_1980/doe_ref_pre_1980.Model.rb +4 -4
- data/lib/openstudio-standards/standards/ashrae_90_1/nrel_zne_ready_2017/data/nrel_zne_ready_2017.heat_rejection.json +9 -0
- data/lib/openstudio-standards/standards/ashrae_90_1/nrel_zne_ready_2017/data/nrel_zne_ready_2017.spc_typ.json +2011 -1112
- data/lib/openstudio-standards/standards/ashrae_90_1/nrel_zne_ready_2017/nrel_zne_ready_2017.AirLoopHVAC.rb +0 -1
- data/lib/openstudio-standards/standards/ashrae_90_1/nrel_zne_ready_2017/nrel_zne_ready_2017.Model.rb +4 -4
- data/lib/openstudio-standards/standards/ashrae_90_1/nrel_zne_ready_2017/nrel_zne_ready_2017.PlantLoop.rb +1 -1
- data/lib/openstudio-standards/standards/ashrae_90_1/nrel_zne_ready_2017/nrel_zne_ready_2017.ZoneHVACComponent.rb +1 -1
- data/lib/openstudio-standards/standards/ashrae_90_1/ze_aedg_multifamily/data/ze_aedg_multifamily.heat_rejection.json +9 -0
- data/lib/openstudio-standards/standards/ashrae_90_1/ze_aedg_multifamily/data/ze_aedg_multifamily.spc_typ.json +1946 -1106
- data/lib/openstudio-standards/standards/ashrae_90_1/ze_aedg_multifamily/data/ze_aedg_multifamily.water_heaters.json +2 -2
- data/lib/openstudio-standards/standards/ashrae_90_1/ze_aedg_multifamily/ze_aedg_multifamily.AirLoopHVAC.rb +3 -6
- data/lib/openstudio-standards/standards/ashrae_90_1/ze_aedg_multifamily/ze_aedg_multifamily.Model.rb +4 -4
- data/lib/openstudio-standards/standards/ashrae_90_1/ze_aedg_multifamily/ze_aedg_multifamily.PlantLoop.rb +1 -1
- data/lib/openstudio-standards/standards/ashrae_90_1/ze_aedg_multifamily/ze_aedg_multifamily.ZoneHVACComponent.rb +1 -1
- data/lib/openstudio-standards/standards/cbes/cbes.Model.rb +1 -3
- data/lib/openstudio-standards/standards/cbes/cbes.rb +1 -1
- data/lib/openstudio-standards/standards/deer/deer.AirLoopHVAC.rb +8 -13
- data/lib/openstudio-standards/standards/deer/deer.Model.rb +2 -2
- data/lib/openstudio-standards/standards/deer/deer.PlanarSurface.rb +2 -0
- data/lib/openstudio-standards/standards/deer/deer.Space.rb +1 -1
- data/lib/openstudio-standards/standards/deer/deer_2011/deer_2011.rb +0 -1
- data/lib/openstudio-standards/standards/deer/deer_2014/deer_2014.Space.rb +0 -1
- data/lib/openstudio-standards/standards/deer/deer_2014/deer_2014.rb +0 -1
- data/lib/openstudio-standards/standards/deer/deer_2015/deer_2015.Space.rb +0 -1
- data/lib/openstudio-standards/standards/deer/deer_2017/deer_2017.Space.rb +0 -1
- data/lib/openstudio-standards/standards/deer/deer_2020/deer_2020.AirLoopHVAC.rb +1 -1
- data/lib/openstudio-standards/standards/deer/deer_2020/deer_2020.FanVariableVolume.rb +1 -1
- data/lib/openstudio-standards/standards/deer/deer_2020/deer_2020.Space.rb +0 -1
- data/lib/openstudio-standards/standards/deer/deer_2025/deer_2025.AirLoopHVAC.rb +1 -1
- data/lib/openstudio-standards/standards/deer/deer_2025/deer_2025.FanVariableVolume.rb +1 -1
- data/lib/openstudio-standards/standards/deer/deer_2025/deer_2025.Space.rb +0 -1
- data/lib/openstudio-standards/standards/deer/deer_2030/deer_2030.AirLoopHVAC.rb +1 -1
- data/lib/openstudio-standards/standards/deer/deer_2030/deer_2030.FanVariableVolume.rb +1 -1
- data/lib/openstudio-standards/standards/deer/deer_2030/deer_2030.Space.rb +0 -1
- data/lib/openstudio-standards/standards/deer/deer_2035/deer_2035.AirLoopHVAC.rb +1 -1
- data/lib/openstudio-standards/standards/deer/deer_2035/deer_2035.FanVariableVolume.rb +1 -1
- data/lib/openstudio-standards/standards/deer/deer_2035/deer_2035.Space.rb +0 -1
- data/lib/openstudio-standards/standards/deer/deer_2040/deer_2040.AirLoopHVAC.rb +1 -1
- data/lib/openstudio-standards/standards/deer/deer_2040/deer_2040.FanVariableVolume.rb +1 -1
- data/lib/openstudio-standards/standards/deer/deer_2040/deer_2040.Space.rb +0 -1
- data/lib/openstudio-standards/standards/deer/deer_2045/deer_2045.AirLoopHVAC.rb +1 -1
- data/lib/openstudio-standards/standards/deer/deer_2045/deer_2045.FanVariableVolume.rb +1 -1
- data/lib/openstudio-standards/standards/deer/deer_2045/deer_2045.Space.rb +0 -1
- data/lib/openstudio-standards/standards/deer/deer_2050/deer_2050.AirLoopHVAC.rb +1 -1
- data/lib/openstudio-standards/standards/deer/deer_2050/deer_2050.FanVariableVolume.rb +1 -1
- data/lib/openstudio-standards/standards/deer/deer_2050/deer_2050.Space.rb +0 -1
- data/lib/openstudio-standards/standards/deer/deer_2055/deer_2055.AirLoopHVAC.rb +1 -1
- data/lib/openstudio-standards/standards/deer/deer_2055/deer_2055.FanVariableVolume.rb +1 -1
- data/lib/openstudio-standards/standards/deer/deer_2055/deer_2055.Space.rb +0 -1
- data/lib/openstudio-standards/standards/deer/deer_2060/deer_2060.AirLoopHVAC.rb +1 -1
- data/lib/openstudio-standards/standards/deer/deer_2060/deer_2060.FanVariableVolume.rb +1 -1
- data/lib/openstudio-standards/standards/deer/deer_2060/deer_2060.Space.rb +0 -1
- data/lib/openstudio-standards/standards/deer/deer_2065/deer_2065.AirLoopHVAC.rb +1 -1
- data/lib/openstudio-standards/standards/deer/deer_2065/deer_2065.FanVariableVolume.rb +1 -1
- data/lib/openstudio-standards/standards/deer/deer_2065/deer_2065.Space.rb +0 -1
- data/lib/openstudio-standards/standards/deer/deer_2070/deer_2070.AirLoopHVAC.rb +1 -1
- data/lib/openstudio-standards/standards/deer/deer_2070/deer_2070.FanVariableVolume.rb +1 -1
- data/lib/openstudio-standards/standards/deer/deer_2070/deer_2070.Space.rb +0 -1
- data/lib/openstudio-standards/standards/deer/deer_2075/deer_2075.AirLoopHVAC.rb +1 -1
- data/lib/openstudio-standards/standards/deer/deer_2075/deer_2075.FanVariableVolume.rb +1 -1
- data/lib/openstudio-standards/standards/deer/deer_2075/deer_2075.Space.rb +0 -1
- data/lib/openstudio-standards/standards/icc_iecc/icc_iecc_2015/icc_iecc_2015.rb +0 -1
- data/lib/openstudio-standards/standards/necb/BTAP1980TO2010/btap_1980to2010.rb +2 -18
- data/lib/openstudio-standards/standards/necb/BTAP1980TO2010/data/space_types.json +1677 -1005
- data/lib/openstudio-standards/standards/necb/BTAPPRE1980/btap_pre1980.rb +87 -15
- data/lib/openstudio-standards/standards/necb/BTAPPRE1980/building_envelope.rb +31 -19
- data/lib/openstudio-standards/standards/necb/BTAPPRE1980/data/curves.json +75 -0
- data/lib/openstudio-standards/standards/necb/BTAPPRE1980/data/heat_pumps.json +16 -16
- data/lib/openstudio-standards/standards/necb/BTAPPRE1980/data/space_types.json +1677 -1005
- data/lib/openstudio-standards/standards/necb/BTAPPRE1980/hvac_system_3_and_8_single_speed.rb +16 -2
- data/lib/openstudio-standards/standards/necb/BTAPPRE1980/hvac_system_4.rb +15 -0
- data/lib/openstudio-standards/standards/necb/BTAPPRE1980/hvac_system_6.rb +14 -0
- data/lib/openstudio-standards/standards/necb/ECMS/data/boiler_set.json +29 -0
- data/lib/openstudio-standards/standards/necb/ECMS/data/curves.json +913 -0
- data/lib/openstudio-standards/standards/necb/ECMS/data/equip_eff_lim.json +52 -0
- data/lib/openstudio-standards/standards/necb/ECMS/data/erv.json +109 -0
- data/lib/openstudio-standards/standards/necb/ECMS/data/furnace_set.json +23 -0
- data/lib/openstudio-standards/standards/necb/ECMS/data/heat_pumps.json +803 -0
- data/lib/openstudio-standards/standards/necb/ECMS/data/heat_pumps_heating.json +787 -0
- data/lib/openstudio-standards/standards/necb/ECMS/data/pv.json +112 -0
- data/lib/openstudio-standards/standards/necb/ECMS/data/shw_set.json +29 -0
- data/lib/openstudio-standards/standards/necb/ECMS/data/unitary_acs.json +50 -0
- data/lib/openstudio-standards/standards/necb/ECMS/ecms.rb +100 -0
- data/lib/openstudio-standards/standards/necb/ECMS/erv.rb +33 -0
- data/lib/openstudio-standards/standards/necb/ECMS/hvac_systems.rb +1729 -0
- data/lib/openstudio-standards/standards/necb/ECMS/nv.rb +189 -0
- data/lib/openstudio-standards/standards/necb/ECMS/pv_ground.rb +104 -0
- data/lib/openstudio-standards/standards/necb/NECB2011/autozone.rb +68 -33
- data/lib/openstudio-standards/standards/necb/NECB2011/beps_compliance_path.rb +24 -13
- data/lib/openstudio-standards/standards/necb/NECB2011/building_envelope.rb +110 -99
- data/lib/openstudio-standards/standards/necb/NECB2011/data/constants.json +24 -24
- data/lib/openstudio-standards/standards/necb/NECB2011/data/curves.json +50 -0
- data/lib/openstudio-standards/standards/necb/NECB2011/data/erv.json +31 -0
- data/lib/openstudio-standards/standards/necb/NECB2011/data/geometry/LowriseApartment.osm +39278 -0
- data/lib/openstudio-standards/standards/necb/NECB2011/data/led_lighting_data.json +2028 -0
- data/lib/openstudio-standards/standards/necb/NECB2011/data/space_types.json +1745 -1297
- data/lib/openstudio-standards/standards/necb/NECB2011/daylighting_control.md +70 -0
- data/lib/openstudio-standards/standards/necb/NECB2011/demand_controlled_ventilation.md +46 -0
- data/lib/openstudio-standards/standards/necb/NECB2011/hvac_system_1_multi_speed.rb +69 -107
- data/lib/openstudio-standards/standards/necb/NECB2011/hvac_system_1_single_speed.rb +41 -2
- data/lib/openstudio-standards/standards/necb/NECB2011/hvac_system_2_and_5.rb +15 -0
- data/lib/openstudio-standards/standards/necb/NECB2011/hvac_system_3_and_8_multi_speed.rb +139 -141
- data/lib/openstudio-standards/standards/necb/NECB2011/hvac_system_3_and_8_single_speed.rb +38 -2
- data/lib/openstudio-standards/standards/necb/NECB2011/hvac_system_4.rb +13 -0
- data/lib/openstudio-standards/standards/necb/NECB2011/hvac_system_6.rb +12 -0
- data/lib/openstudio-standards/standards/necb/NECB2011/hvac_systems.rb +492 -240
- data/lib/openstudio-standards/standards/necb/NECB2011/led_lighting.md +51 -0
- data/lib/openstudio-standards/standards/necb/NECB2011/lighting.rb +75 -9
- data/lib/openstudio-standards/standards/necb/NECB2011/necb_2011.rb +1229 -37
- data/lib/openstudio-standards/standards/necb/NECB2011/nv.md +74 -0
- data/lib/openstudio-standards/standards/necb/NECB2011/pv_ground.md +44 -0
- data/lib/openstudio-standards/standards/necb/NECB2011/qaqc/necb_qaqc.rb +11 -3
- data/lib/openstudio-standards/standards/necb/NECB2011/qaqc/qaqc_resources/neb_end_use_prices.csv +39 -84
- data/lib/openstudio-standards/standards/necb/NECB2011/service_water_heating.rb +1 -1
- data/lib/openstudio-standards/standards/necb/NECB2015/data/led_lighting_data.json +2883 -0
- data/lib/openstudio-standards/standards/necb/NECB2015/data/space_types.json +2554 -1916
- data/lib/openstudio-standards/standards/necb/NECB2015/necb_2015.rb +32 -1
- data/lib/openstudio-standards/standards/necb/NECB2017/data/led_lighting_data.json +2883 -0
- data/lib/openstudio-standards/standards/necb/NECB2017/data/space_types.json +2554 -1916
- data/lib/openstudio-standards/standards/necb/NECB2017/necb_2017.rb +29 -0
- data/lib/openstudio-standards/standards/oeesc/oeesc_2014/oeesc_2014.rb +0 -1
- data/lib/openstudio-standards/standards/standard.rb +6 -5
- data/lib/openstudio-standards/utilities/Add_template_field_to_json.rb +3 -3
- data/lib/openstudio-standards/utilities/convert_surfaces_to_adiabatic_necb_8426.rb +54 -54
- data/lib/openstudio-standards/utilities/generate_prototype_database.rb +2 -2
- data/lib/openstudio-standards/utilities/generate_space_types.rb +3 -3
- data/lib/openstudio-standards/utilities/logging.rb +7 -7
- data/lib/openstudio-standards/utilities/necb_to_epw_map.rb +14 -14
- data/lib/openstudio-standards/utilities/os_sim_extract.rb +25 -25
- data/lib/openstudio-standards/utilities/rename_surfaces.rb +10 -13
- data/lib/openstudio-standards/utilities/round_surf_coords.rb +18 -20
- data/lib/openstudio-standards/utilities/sched_create.rb +39 -41
- data/lib/openstudio-standards/utilities/set_mult_to_adiabatic.rb +31 -31
- data/lib/openstudio-standards/utilities/simulation.rb +13 -21
- data/lib/openstudio-standards/utilities/speacetype_map_converter.rb +10 -11
- data/lib/openstudio-standards/utilities/sqlfile.rb +6 -8
- data/lib/openstudio-standards/utilities/template_measure/measure.rb +108 -0
- data/lib/openstudio-standards/utilities/template_measure/measure.xml +162 -0
- data/lib/openstudio-standards/utilities/template_measure/resources/BTAPMeasureHelper.rb +448 -0
- data/lib/openstudio-standards/utilities/template_measure/tests/test.rb +160 -0
- data/lib/openstudio-standards/utilities/weatherData1_xlsx_to_json.rb +23 -26
- data/lib/openstudio-standards/version.rb +1 -1
- data/lib/openstudio-standards/weather/Weather.Model.rb +112 -87
- data/lib/openstudio-standards/weather/Weather.stat_file.rb +17 -17
- metadata +236 -2
@@ -0,0 +1,24 @@
|
|
1
|
+
class ASHRAE9012019 < ASHRAE901
|
2
|
+
# @!group AirTerminalSingleDuctVAVReheat
|
3
|
+
|
4
|
+
# Specifies the minimum damper position for VAV dampers.
|
5
|
+
# For terminals with hot water heat and DDC, the minimum is 20%,
|
6
|
+
# otherwise the minimum is 30%.
|
7
|
+
#
|
8
|
+
# @param has_ddc [Bool] whether or not there is DDC control of the VAV terminal in question
|
9
|
+
def air_terminal_single_duct_vav_reheat_minimum_damper_position(air_terminal_single_duct_vav_reheat, has_ddc = false)
|
10
|
+
min_damper_position = nil
|
11
|
+
case air_terminal_single_duct_vav_reheat_reheat_type(air_terminal_single_duct_vav_reheat)
|
12
|
+
when 'HotWater'
|
13
|
+
min_damper_position = if has_ddc
|
14
|
+
0.2
|
15
|
+
else
|
16
|
+
0.3
|
17
|
+
end
|
18
|
+
when 'Electricity', 'NaturalGas'
|
19
|
+
min_damper_position = 0.3
|
20
|
+
end
|
21
|
+
|
22
|
+
return min_damper_position
|
23
|
+
end
|
24
|
+
end
|
@@ -0,0 +1,19 @@
|
|
1
|
+
# A variety of cooling tower methods that are the same regardless of type.
|
2
|
+
# These methods are available to CoolingTowerSingleSpeed, CoolingTowerTwoSpeed, and CoolingTowerVariableSpeed
|
3
|
+
module ASHRAE9012019CoolingTower
|
4
|
+
# @!group CoolingTower
|
5
|
+
|
6
|
+
# Above this point, centrifugal fan cooling towers must meet the limits
|
7
|
+
# of propeller or axial cooling towers instead.
|
8
|
+
# 90.1 6.5.5.3 Limit on Centrifugal Fan Open Circuit Cooling Towers.
|
9
|
+
# is 1,100 gallons per minute.
|
10
|
+
#
|
11
|
+
# @param cooling_tower [OpenStudio::Model::CoolingTowerSingleSpeed,
|
12
|
+
# OpenStudio::Model::CoolingTowerTwoSpeed,
|
13
|
+
# OpenStudio::Model::CoolingTowerVariableSpeed] the cooling tower
|
14
|
+
# @return [Double] the limit, in gallons per minute. Return nil for no limit.
|
15
|
+
def cooling_tower_apply_minimum_power_per_flow_gpm_limit(cooling_tower)
|
16
|
+
gpm_limit = 1100
|
17
|
+
return gpm_limit
|
18
|
+
end
|
19
|
+
end
|
@@ -0,0 +1,16 @@
|
|
1
|
+
class ASHRAE9012019 < ASHRAE901
|
2
|
+
# @!group CoolingTowerVariableSpeed
|
3
|
+
|
4
|
+
include ASHRAE9012019CoolingTower
|
5
|
+
|
6
|
+
# Apply the efficiency, plus Multicell heat rejection with VSD
|
7
|
+
#
|
8
|
+
# @param cooling_tower_variable_speed [OpenStudio::Model::CoolingTowerVariableSpeed] the cooling tower
|
9
|
+
def cooling_tower_variable_speed_apply_efficiency_and_curves(cooling_tower_variable_speed)
|
10
|
+
cooling_tower_apply_minimum_power_per_flow(cooling_tower_variable_speed)
|
11
|
+
|
12
|
+
cooling_tower_variable_speed.setCellControl('MaximalCell')
|
13
|
+
|
14
|
+
return true
|
15
|
+
end
|
16
|
+
end
|
@@ -0,0 +1,37 @@
|
|
1
|
+
class ASHRAE9012019 < ASHRAE901
|
2
|
+
# @!group FanVariableVolume
|
3
|
+
|
4
|
+
# The threhold horsepower below which part load control is not required.
|
5
|
+
# Per 90.1-2019, table 6.5.3.2.1: the fan motor size for chiller-water
|
6
|
+
# and evaporative cooling is 0.25 hp as of 1/1/2014 instead of 5 hp
|
7
|
+
#
|
8
|
+
# @param fan_variable_volume [OpenStudio::Model::FanVariableVolume] the fan
|
9
|
+
# @return [Double] the limit, in horsepower. Return nil for no limit by default.
|
10
|
+
def fan_variable_volume_part_load_fan_power_limitation_hp_limit(fan_variable_volume)
|
11
|
+
hp_limit = case fan_variable_volume_cooling_system_type(fan_variable_volume)
|
12
|
+
when 'dx'
|
13
|
+
0.0
|
14
|
+
when 'chw'
|
15
|
+
0.25
|
16
|
+
when 'evap'
|
17
|
+
0.25
|
18
|
+
end
|
19
|
+
|
20
|
+
return hp_limit
|
21
|
+
end
|
22
|
+
|
23
|
+
# The threhold capacity below which part load control is not required.
|
24
|
+
# Per 90.1-2019, table 6.5.3.2.1: the cooling capacity threshold is 75000
|
25
|
+
# instead of 110000 as of 1/1/2014
|
26
|
+
#
|
27
|
+
# @param fan_variable_volume [OpenStudio::Model::FanVariableVolume] the fan
|
28
|
+
# @return [Double] the limit, in Btu/hr. Return nil for no limit by default.
|
29
|
+
def fan_variable_volume_part_load_fan_power_limitation_capacity_limit(fan_variable_volume)
|
30
|
+
cap_limit_btu_per_hr = case fan_variable_volume_cooling_system_type(fan_variable_volume)
|
31
|
+
when 'dx'
|
32
|
+
65_000
|
33
|
+
end
|
34
|
+
|
35
|
+
return cap_limit_btu_per_hr
|
36
|
+
end
|
37
|
+
end
|
data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2019/ashrae_90_1_2019.Space.rb
ADDED
@@ -0,0 +1,189 @@
|
|
1
|
+
class ASHRAE9012019 < ASHRAE901
|
2
|
+
# @!group Space
|
3
|
+
|
4
|
+
# Determines the method used to extend the daylighted area horizontally
|
5
|
+
# next to a window. If the method is 'fixed', 2 ft is added to the
|
6
|
+
# width of each window. If the method is 'proportional', a distance
|
7
|
+
# equal to half of the head height of the window is added. If the method is 'none',
|
8
|
+
# no additional width is added.
|
9
|
+
#
|
10
|
+
# @return [String] returns 'fixed' or 'proportional'
|
11
|
+
def space_daylighted_area_window_width(space)
|
12
|
+
method = 'proportional'
|
13
|
+
return method
|
14
|
+
end
|
15
|
+
|
16
|
+
# Determine if the space requires daylighting controls for
|
17
|
+
# toplighting, primary sidelighting, and secondary sidelighting.
|
18
|
+
# Defaults to false for all types.
|
19
|
+
#
|
20
|
+
# @param space [OpenStudio::Model::Space] the space in question
|
21
|
+
# @param areas [Hash] a hash of daylighted areas
|
22
|
+
# @return [Array<Bool>] req_top_ctrl, req_pri_ctrl, req_sec_ctrl
|
23
|
+
def space_daylighting_control_required?(space, areas)
|
24
|
+
req_top_ctrl = true
|
25
|
+
req_pri_ctrl = true
|
26
|
+
req_sec_ctrl = true
|
27
|
+
|
28
|
+
# Get the LPD of the space
|
29
|
+
space_lpd_w_per_m2 = space.lightingPowerPerFloorArea
|
30
|
+
|
31
|
+
# Primary Sidelighting
|
32
|
+
# Check if the primary sidelit area contains less than 150W of lighting
|
33
|
+
if areas['primary_sidelighted_area'] == 0.0
|
34
|
+
OpenStudio.logFree(OpenStudio::Debug, 'openstudio.model.Space', "For #{space.name}, primary sidelighting control not required because primary sidelighted area = 0ft2 per 9.4.1.1(e).")
|
35
|
+
req_pri_ctrl = false
|
36
|
+
elsif areas['primary_sidelighted_area'] * space_lpd_w_per_m2 < 150.0
|
37
|
+
OpenStudio.logFree(OpenStudio::Info, 'openstudio.model.Space', "For #{space.name}, primary sidelighting control not required because less than 150W of lighting are present in the primary daylighted area per 9.4.1.1(e).")
|
38
|
+
req_pri_ctrl = false
|
39
|
+
else
|
40
|
+
# Check the size of the windows
|
41
|
+
if areas['total_window_area'] < OpenStudio.convert(20.0, 'ft^2', 'm^2').get
|
42
|
+
OpenStudio.logFree(OpenStudio::Info, 'openstudio.model.Space', "For #{space.name}, primary sidelighting control not required because there are less than 20ft2 of window per 9.4.1.1(e) Exception 2.")
|
43
|
+
req_pri_ctrl = false
|
44
|
+
end
|
45
|
+
end
|
46
|
+
|
47
|
+
# Secondary Sidelighting
|
48
|
+
# Check if the primary and secondary sidelit areas contains less than 300W of lighting
|
49
|
+
if areas['secondary_sidelighted_area'] == 0.0
|
50
|
+
OpenStudio.logFree(OpenStudio::Debug, 'openstudio.model.Space', "For #{space.name}, secondary sidelighting control not required because secondary sidelighted area = 0ft2 per 9.4.1.1(e).")
|
51
|
+
req_sec_ctrl = false
|
52
|
+
elsif (areas['primary_sidelighted_area'] + areas['secondary_sidelighted_area']) * space_lpd_w_per_m2 < 300
|
53
|
+
OpenStudio.logFree(OpenStudio::Info, 'openstudio.model.Space', "For #{space.name}, secondary sidelighting control not required because less than 300W of lighting are present in the combined primary and secondary daylighted areas per 9.4.1.1(e).")
|
54
|
+
req_sec_ctrl = false
|
55
|
+
else
|
56
|
+
# Check the size of the windows
|
57
|
+
if areas['total_window_area'] < OpenStudio.convert(20.0, 'ft^2', 'm^2').get
|
58
|
+
OpenStudio.logFree(OpenStudio::Info, 'openstudio.model.Space', "For #{space.name}, secondary sidelighting control not required because there are less than 20ft2 of window per 9.4.1.1(e) Exception 2.")
|
59
|
+
req_sec_ctrl = false
|
60
|
+
end
|
61
|
+
end
|
62
|
+
|
63
|
+
# Toplighting
|
64
|
+
# Check if the toplit area contains less than 150W of lighting
|
65
|
+
if areas['toplighted_area'] == 0.0
|
66
|
+
OpenStudio.logFree(OpenStudio::Debug, 'openstudio.model.Space', "For #{space.name}, toplighting control not required because toplighted area = 0ft2 per 9.4.1.1(f).")
|
67
|
+
req_top_ctrl = false
|
68
|
+
elsif areas['toplighted_area'] * space_lpd_w_per_m2 < 150
|
69
|
+
OpenStudio.logFree(OpenStudio::Info, 'openstudio.model.Space', "For #{space.name}, toplighting control not required because less than 150W of lighting are present in the toplighted area per 9.4.1.1(f).")
|
70
|
+
req_top_ctrl = false
|
71
|
+
end
|
72
|
+
|
73
|
+
# Exceptions
|
74
|
+
if space.spaceType.is_initialized
|
75
|
+
case space.spaceType.get.standardsSpaceType.to_s
|
76
|
+
# Retail spaces exception (c) to Section 9.4.1.4
|
77
|
+
# req_sec_ctrl set to true to create a second reference point
|
78
|
+
when 'Core_Retail'
|
79
|
+
req_pri_ctrl = false
|
80
|
+
req_sec_ctrl = true
|
81
|
+
when 'Entry', 'Front_Retail', 'Point_of_Sale'
|
82
|
+
req_pri_ctrl = false
|
83
|
+
req_sec_ctrl = false
|
84
|
+
# Strip mall
|
85
|
+
when 'Strip mall - type 1', 'Strip mall - type 2', 'Strip mall - type 3'
|
86
|
+
req_pri_ctrl = false
|
87
|
+
req_sec_ctrl = false
|
88
|
+
# Residential apartments
|
89
|
+
when 'Apartment', 'Apartment_topfloor_NS', 'Apartment_topfloor_WE'
|
90
|
+
req_top_ctrl = false
|
91
|
+
req_pri_ctrl = false
|
92
|
+
req_sec_ctrl = false
|
93
|
+
end
|
94
|
+
end
|
95
|
+
|
96
|
+
return [req_top_ctrl, req_pri_ctrl, req_sec_ctrl]
|
97
|
+
end
|
98
|
+
|
99
|
+
# Determine the fraction controlled by each sensor and which
|
100
|
+
# window each sensor should go near.
|
101
|
+
#
|
102
|
+
# @param space [OpenStudio::Model::Space] the space with the daylighting
|
103
|
+
# @param sorted_windows [Hash] a hash of windows, sorted by priority
|
104
|
+
# @param sorted_skylights [Hash] a hash of skylights, sorted by priority
|
105
|
+
# @param req_top_ctrl [Bool] if toplighting controls are required
|
106
|
+
# @param req_pri_ctrl [Bool] if primary sidelighting controls are required
|
107
|
+
# @param req_sec_ctrl [Bool] if secondary sidelighting controls are required
|
108
|
+
def space_daylighting_fractions_and_windows(space,
|
109
|
+
areas,
|
110
|
+
sorted_windows,
|
111
|
+
sorted_skylights,
|
112
|
+
req_top_ctrl,
|
113
|
+
req_pri_ctrl,
|
114
|
+
req_sec_ctrl)
|
115
|
+
sensor_1_frac = 0.0
|
116
|
+
sensor_2_frac = 0.0
|
117
|
+
sensor_1_window = nil
|
118
|
+
sensor_2_window = nil
|
119
|
+
|
120
|
+
# Get the area of the space
|
121
|
+
space_area_m2 = space.floorArea
|
122
|
+
|
123
|
+
# get the climate zone
|
124
|
+
climate_zone = model_standards_climate_zone(space.model)
|
125
|
+
|
126
|
+
if req_top_ctrl && req_pri_ctrl && req_sec_ctrl
|
127
|
+
# Sensor 1 controls toplighted area
|
128
|
+
sensor_1_frac = areas['toplighted_area'] / space_area_m2
|
129
|
+
sensor_1_window = sorted_skylights[0]
|
130
|
+
# Sensor 2 controls primary + secondary area
|
131
|
+
sensor_2_frac = (areas['primary_sidelighted_area'] + areas['secondary_sidelighted_area']) / space_area_m2
|
132
|
+
sensor_2_window = sorted_windows[0]
|
133
|
+
elsif !req_top_ctrl && req_pri_ctrl && req_sec_ctrl
|
134
|
+
# Sensor 1 controls primary area
|
135
|
+
sensor_1_frac = areas['primary_sidelighted_area'] / space_area_m2
|
136
|
+
sensor_1_window = sorted_windows[0]
|
137
|
+
# Sensor 2 controls secondary area
|
138
|
+
sensor_2_frac = (areas['secondary_sidelighted_area'] / space_area_m2)
|
139
|
+
sensor_2_window = sorted_windows[0]
|
140
|
+
elsif req_top_ctrl && !req_pri_ctrl && req_sec_ctrl
|
141
|
+
# Sensor 1 controls toplighted area
|
142
|
+
sensor_1_frac = areas['toplighted_area'] / space_area_m2
|
143
|
+
sensor_1_window = sorted_skylights[0]
|
144
|
+
# Sensor 2 controls secondary area
|
145
|
+
sensor_2_frac = (areas['secondary_sidelighted_area'] / space_area_m2)
|
146
|
+
# sorted_skylights[0] assigned to sensor_2_window so a second reference point is added for top daylighting
|
147
|
+
sensor_2_window = sorted_skylights[0]
|
148
|
+
elsif req_top_ctrl && !req_pri_ctrl && !req_sec_ctrl
|
149
|
+
case climate_zone
|
150
|
+
when 'ASHRAE 169-2006-6A',
|
151
|
+
'ASHRAE 169-2006-6B',
|
152
|
+
'ASHRAE 169-2006-7A',
|
153
|
+
'ASHRAE 169-2006-8A',
|
154
|
+
'ASHRAE 169-2013-6A',
|
155
|
+
'ASHRAE 169-2013-6B',
|
156
|
+
'ASHRAE 169-2013-7A',
|
157
|
+
'ASHRAE 169-2013-8A'
|
158
|
+
# Sensor 1 controls toplighted area
|
159
|
+
sensor_1_frac = areas['toplighted_area'] / space_area_m2
|
160
|
+
sensor_1_window = sorted_skylights[0]
|
161
|
+
else
|
162
|
+
# Sensor 1 controls toplighted area
|
163
|
+
sensor_1_frac = areas['toplighted_area'] / space_area_m2
|
164
|
+
sensor_1_window = sorted_skylights[0]
|
165
|
+
sensor_2_frac = sensor_1_frac
|
166
|
+
sensor_2_window = sensor_1_window
|
167
|
+
end
|
168
|
+
elsif !req_top_ctrl && req_pri_ctrl && !req_sec_ctrl
|
169
|
+
# Sensor 1 controls primary area
|
170
|
+
sensor_1_frac = areas['primary_sidelighted_area'] / space_area_m2
|
171
|
+
sensor_1_window = sorted_windows[0]
|
172
|
+
elsif !req_top_ctrl && !req_pri_ctrl && req_sec_ctrl
|
173
|
+
# Sensor 1 controls secondary area
|
174
|
+
sensor_1_frac = areas['secondary_sidelighted_area'] / space_area_m2
|
175
|
+
sensor_1_window = sorted_windows[0]
|
176
|
+
end
|
177
|
+
|
178
|
+
return [sensor_1_frac, sensor_2_frac, sensor_1_window, sensor_2_window]
|
179
|
+
end
|
180
|
+
|
181
|
+
# Determine the base infiltration rate at 75 PA.
|
182
|
+
#
|
183
|
+
# @return [Double] the baseline infiltration rate, in cfm/ft^2
|
184
|
+
# defaults to no infiltration.
|
185
|
+
def space_infiltration_rate_75_pa(space)
|
186
|
+
basic_infil_rate_cfm_per_ft2 = 1.0
|
187
|
+
return basic_infil_rate_cfm_per_ft2
|
188
|
+
end
|
189
|
+
end
|
data/lib/openstudio-standards/standards/ashrae_90_1/ashrae_90_1_2019/ashrae_90_1_2019.ThermalZone.rb
ADDED
@@ -0,0 +1,57 @@
|
|
1
|
+
class ASHRAE9012019 < ASHRAE901
|
2
|
+
# @!group ThermalZone
|
3
|
+
|
4
|
+
# Determine the thermal zone's occupancy type category.
|
5
|
+
# Options are: residential, nonresidential, publicassembly, retail
|
6
|
+
#
|
7
|
+
# @return [String] the occupancy type category
|
8
|
+
# @todo Add public assembly building types
|
9
|
+
def thermal_zone_occupancy_type(thermal_zone)
|
10
|
+
occ_type = if thermal_zone_residential?(thermal_zone)
|
11
|
+
'residential'
|
12
|
+
else
|
13
|
+
'nonresidential'
|
14
|
+
end
|
15
|
+
|
16
|
+
# Based on the space type that
|
17
|
+
# represents a majority of the zone.
|
18
|
+
space_type = thermal_zone_majority_space_type(thermal_zone)
|
19
|
+
if space_type.is_initialized
|
20
|
+
space_type = space_type.get
|
21
|
+
bldg_type = space_type.standardsBuildingType
|
22
|
+
if bldg_type.is_initialized
|
23
|
+
bldg_type = bldg_type.get
|
24
|
+
case bldg_type
|
25
|
+
when 'Retail', 'StripMall', 'SuperMarket'
|
26
|
+
occ_type = 'retail'
|
27
|
+
# when 'SomeBuildingType' # TODO add publicassembly building types
|
28
|
+
# occ_type = 'publicassembly'
|
29
|
+
end
|
30
|
+
end
|
31
|
+
end
|
32
|
+
|
33
|
+
# OpenStudio::logFree(OpenStudio::Info, "openstudio.Standards.ThermalZone", "For #{self.name}, occupancy type = #{occ_type}.")
|
34
|
+
|
35
|
+
return occ_type
|
36
|
+
end
|
37
|
+
|
38
|
+
# Determine the area and occupancy level limits for
|
39
|
+
# demand control ventilation.
|
40
|
+
#
|
41
|
+
# @param thermal_zone [OpenStudio::Model::ThermalZone] the thermal zone
|
42
|
+
# @return [Array<Double>] the minimum area, in m^2
|
43
|
+
# and the minimum occupancy density in m^2/person. Returns nil
|
44
|
+
# if there is no requirement.
|
45
|
+
def thermal_zone_demand_control_ventilation_limits(thermal_zone)
|
46
|
+
min_area_ft2 = 500
|
47
|
+
min_occ_per_1000_ft2 = 25
|
48
|
+
|
49
|
+
# Convert to SI
|
50
|
+
min_area_m2 = OpenStudio.convert(min_area_ft2, 'ft^2', 'm^2').get
|
51
|
+
min_occ_per_ft2 = min_occ_per_1000_ft2 / 1000.0
|
52
|
+
min_ft2_per_occ = 1.0 / min_occ_per_ft2
|
53
|
+
min_m2_per_occ = OpenStudio.convert(min_ft2_per_occ, 'ft^2', 'm^2').get
|
54
|
+
|
55
|
+
return [min_area_m2, min_m2_per_occ]
|
56
|
+
end
|
57
|
+
end
|
@@ -0,0 +1,22 @@
|
|
1
|
+
class ASHRAE9012019 < ASHRAE901
|
2
|
+
# @!group ZoneHVACComponent
|
3
|
+
|
4
|
+
# Determine if vestibule heating control is required.
|
5
|
+
# Required for 90.1-2019 per 6.4.3.9.
|
6
|
+
#
|
7
|
+
# @ref [References::ASHRAE9012019] 6.4.3.9
|
8
|
+
# @return [Bool] returns true if successful, false if not
|
9
|
+
def zone_hvac_component_vestibule_heating_control_required?(zone_hvac_component)
|
10
|
+
# Ensure that the equipment is assigned to a thermal zone
|
11
|
+
if zone_hvac_component.thermalZone.empty?
|
12
|
+
OpenStudio.logFree(OpenStudio::Warn, 'openstudio.model.ZoneHVACComponent', "For #{zone_hvac_component.name}: equipment is not assigned to a thermal zone, cannot apply vestibule heating control.")
|
13
|
+
return false
|
14
|
+
end
|
15
|
+
|
16
|
+
# Only applies to equipment that is in vestibule zones
|
17
|
+
return true if thermal_zone_vestibule?(zone_hvac_component.thermalZone.get)
|
18
|
+
|
19
|
+
# If here, vestibule heating control not required
|
20
|
+
return false
|
21
|
+
end
|
22
|
+
end
|
@@ -0,0 +1,16 @@
|
|
1
|
+
# This class holds methods that apply ASHRAE 90.1-2019
|
2
|
+
# to a given model.
|
3
|
+
# @ref [References::ASHRAE9012019]
|
4
|
+
class ASHRAE9012019 < ASHRAE901
|
5
|
+
register_standard '90.1-2019'
|
6
|
+
attr_reader :template
|
7
|
+
|
8
|
+
def initialize
|
9
|
+
@template = '90.1-2019'
|
10
|
+
load_standards_database
|
11
|
+
end
|
12
|
+
|
13
|
+
def load_standards_database(data_directories = [])
|
14
|
+
super([__dir__] + data_directories)
|
15
|
+
end
|
16
|
+
end
|
@@ -0,0 +1,68 @@
|
|
1
|
+
{
|
2
|
+
"boilers": [
|
3
|
+
{
|
4
|
+
"template": "90.1-2019",
|
5
|
+
"fluid_type": "Hot Water",
|
6
|
+
"fuel_type": "Gas",
|
7
|
+
"condensing": null,
|
8
|
+
"condensing_control": null,
|
9
|
+
"minimum_capacity": 0.0,
|
10
|
+
"maximum_capacity": 299999.0,
|
11
|
+
"start_date": "1919-09-09T00:00:00+00:00",
|
12
|
+
"end_date": "2999-09-09T00:00:00+00:00",
|
13
|
+
"minimum_annual_fuel_utilization_efficiency": 0.82,
|
14
|
+
"minimum_thermal_efficiency": null,
|
15
|
+
"minimum_combustion_efficiency": null,
|
16
|
+
"efffplr": "Boiler with No Minimum Turndown",
|
17
|
+
"notes": "From 90.1-2019"
|
18
|
+
},
|
19
|
+
{
|
20
|
+
"template": "90.1-2019",
|
21
|
+
"fluid_type": "Hot Water",
|
22
|
+
"fuel_type": "Gas",
|
23
|
+
"condensing": null,
|
24
|
+
"condensing_control": null,
|
25
|
+
"minimum_capacity": 300000.0,
|
26
|
+
"maximum_capacity": 999999.0,
|
27
|
+
"start_date": "1919-09-09T00:00:00+00:00",
|
28
|
+
"end_date": "2999-09-09T00:00:00+00:00",
|
29
|
+
"minimum_annual_fuel_utilization_efficiency": null,
|
30
|
+
"minimum_thermal_efficiency": 0.8,
|
31
|
+
"minimum_combustion_efficiency": null,
|
32
|
+
"efffplr": "Boiler with No Minimum Turndown",
|
33
|
+
"notes": "From 90.1-2019"
|
34
|
+
},
|
35
|
+
{
|
36
|
+
"template": "90.1-2019",
|
37
|
+
"fluid_type": "Hot Water",
|
38
|
+
"fuel_type": "Gas",
|
39
|
+
"condensing": null,
|
40
|
+
"condensing_control": null,
|
41
|
+
"minimum_capacity": 1000000.0,
|
42
|
+
"maximum_capacity": 249999999.0,
|
43
|
+
"start_date": "1919-09-09T00:00:00+00:00",
|
44
|
+
"end_date": "2999-09-09T00:00:00+00:00",
|
45
|
+
"minimum_annual_fuel_utilization_efficiency": null,
|
46
|
+
"minimum_thermal_efficiency": 0.8,
|
47
|
+
"minimum_combustion_efficiency": null,
|
48
|
+
"efffplr": "Boiler with Minimum Turndown",
|
49
|
+
"notes": "From 90.1-2019"
|
50
|
+
},
|
51
|
+
{
|
52
|
+
"template": "90.1-2019",
|
53
|
+
"fluid_type": "Hot Water",
|
54
|
+
"fuel_type": "Gas",
|
55
|
+
"condensing": null,
|
56
|
+
"condensing_control": null,
|
57
|
+
"minimum_capacity": 250000000.0,
|
58
|
+
"maximum_capacity": 9999999999.0,
|
59
|
+
"start_date": "1919-09-09T00:00:00+00:00",
|
60
|
+
"end_date": "2999-09-09T00:00:00+00:00",
|
61
|
+
"minimum_annual_fuel_utilization_efficiency": null,
|
62
|
+
"minimum_thermal_efficiency": null,
|
63
|
+
"minimum_combustion_efficiency": 0.82,
|
64
|
+
"efffplr": "Boiler with Minimum Turndown",
|
65
|
+
"notes": "From 90.1-2019"
|
66
|
+
}
|
67
|
+
]
|
68
|
+
}
|