openstudio-standards 0.1.3 → 0.1.4

This diff represents the content of publicly available package versions that have been released to one of the supported registries. The information contained in this diff is provided for informational purposes only and reflects changes between package versions as they appear in their respective public registries.
Files changed (59) hide show
  1. checksums.yaml +4 -4
  2. data/data/standards/OpenStudio_Standards.xlsx +0 -0
  3. data/data/standards/OpenStudio_Standards_chillers.json +5 -5
  4. data/data/standards/OpenStudio_Standards_construction_sets.json +2 -2
  5. data/data/standards/OpenStudio_Standards_curve_cubics.json +12 -0
  6. data/data/standards/OpenStudio_Standards_heat_pumps.json +2126 -72
  7. data/data/standards/OpenStudio_Standards_heat_pumps_heating.json +766 -14
  8. data/data/standards/OpenStudio_Standards_heat_rejection.json +172 -0
  9. data/data/standards/OpenStudio_Standards_prototype_inputs.json +355 -267
  10. data/data/standards/OpenStudio_Standards_schedules.json +262 -10
  11. data/data/standards/OpenStudio_Standards_space_types.json +1466 -794
  12. data/data/standards/manage_OpenStudio_Standards.rb +19 -21
  13. data/data/weather/weather_info.csv +96 -0
  14. data/lib/openstudio-standards/btap/btap.rb +1 -1
  15. data/lib/openstudio-standards/btap/compliance.rb +135 -40
  16. data/lib/openstudio-standards/btap/envelope.rb +26 -5
  17. data/lib/openstudio-standards/btap/geometry.rb +11 -1
  18. data/lib/openstudio-standards/btap/hvac.rb +489 -56
  19. data/lib/openstudio-standards/btap/simmanager.rb +1 -1
  20. data/lib/openstudio-standards/hvac_sizing/HVACSizing.CoilHeatingDXMultiSpeed.rb +120 -0
  21. data/lib/openstudio-standards/hvac_sizing/Siz.CoilCoolingDXMultiSpeed.rb +151 -7
  22. data/lib/openstudio-standards/hvac_sizing/Siz.CoilHeatingGasMultiStage.rb +48 -7
  23. data/lib/openstudio-standards/hvac_sizing/Siz.Model.rb +14 -12
  24. data/lib/openstudio-standards/prototypes/Prototype.AirTerminalSingleDuctVAVReheat.rb +33 -7
  25. data/lib/openstudio-standards/prototypes/Prototype.Model.hvac.rb +123 -91
  26. data/lib/openstudio-standards/prototypes/Prototype.Model.rb +130 -45
  27. data/lib/openstudio-standards/prototypes/Prototype.Model.swh.rb +13 -7
  28. data/lib/openstudio-standards/prototypes/Prototype.full_service_restaurant.rb +332 -324
  29. data/lib/openstudio-standards/prototypes/Prototype.hospital.rb +401 -99
  30. data/lib/openstudio-standards/prototypes/Prototype.hvac_systems.rb +309 -222
  31. data/lib/openstudio-standards/prototypes/Prototype.large_hotel.rb +100 -80
  32. data/lib/openstudio-standards/prototypes/Prototype.large_office.rb +37 -22
  33. data/lib/openstudio-standards/prototypes/Prototype.medium_office.rb +68 -53
  34. data/lib/openstudio-standards/prototypes/Prototype.mid_rise_apartment.rb +109 -88
  35. data/lib/openstudio-standards/prototypes/Prototype.outpatient.rb +52 -4
  36. data/lib/openstudio-standards/prototypes/Prototype.primary_school.rb +230 -213
  37. data/lib/openstudio-standards/prototypes/Prototype.quick_service_restaurant.rb +225 -218
  38. data/lib/openstudio-standards/prototypes/Prototype.retail_standalone.rb +29 -17
  39. data/lib/openstudio-standards/prototypes/Prototype.retail_stripmall.rb +42 -32
  40. data/lib/openstudio-standards/prototypes/Prototype.secondary_school.rb +331 -314
  41. data/lib/openstudio-standards/prototypes/Prototype.small_hotel.rb +233 -219
  42. data/lib/openstudio-standards/prototypes/Prototype.small_office.rb +40 -32
  43. data/lib/openstudio-standards/prototypes/Prototype.warehouse.rb +19 -6
  44. data/lib/openstudio-standards/standards/Standards.AirLoopHVAC.rb +576 -555
  45. data/lib/openstudio-standards/standards/Standards.AirTerminalSingleDuctVAVReheat.rb +3 -1
  46. data/lib/openstudio-standards/standards/Standards.BoilerHotWater.rb +35 -17
  47. data/lib/openstudio-standards/standards/Standards.ChillerElectricEIR.rb +51 -23
  48. data/lib/openstudio-standards/standards/Standards.CoilCoolingDXMultiSpeed.rb +255 -0
  49. data/lib/openstudio-standards/standards/Standards.CoilHeatingDXMultiSpeed.rb +192 -0
  50. data/lib/openstudio-standards/standards/Standards.CoilHeatingGasMultiStage.rb +65 -0
  51. data/lib/openstudio-standards/standards/Standards.Fan.rb +37 -6
  52. data/lib/openstudio-standards/standards/Standards.Model.rb +28 -3
  53. data/lib/openstudio-standards/standards/Standards.SpaceType.rb +3 -1
  54. data/lib/openstudio-standards/standards/Standards.WaterHeaterMixed.rb +41 -15
  55. data/lib/openstudio-standards/version.rb +1 -1
  56. data/lib/openstudio-standards/weather/Weather.Model.rb +509 -5
  57. data/lib/openstudio-standards/weather/Weather.stat_file.rb +145 -5
  58. metadata +8 -3
  59. data/lib/openstudio-standards/btap/environment.rb +0 -718
checksums.yaml CHANGED
@@ -1,7 +1,7 @@
1
1
  ---
2
2
  SHA1:
3
- metadata.gz: 3b528f4fbfe4f287e792b723a0eca90ab045cd22
4
- data.tar.gz: 8a5d326de020f16dc1803900c901cdbfbd94b289
3
+ metadata.gz: b164bdb48d7e7d6fc4b9ca722b6dc98bdd472add
4
+ data.tar.gz: 84460c4c20503fe84ab53b0d3a148c4473c90033
5
5
  SHA512:
6
- metadata.gz: 993958fe7f17a8ee6ec9d5a853889965a39787e7d76fe198773da1d054bc8440712cbb5b938f1c7bff23d73a00ee59112811f18bdc8fd6f236f2a023cde4d324
7
- data.tar.gz: c7e95e06ca70daafe9aa056ec08ef2a88ce78aee4c4f0d648512979d54c37bfe16f4c35351f6d26bcbb00f3c639ad7f2d1557859ac38b39718183e5d7d069cff
6
+ metadata.gz: 24852edd6486495cd5c7d67fe300c1fc6d2b9021daac50c0ea55e7771e145ae063d1be558445b8706b54da826857c5dbcb23f7a50ed1263e36989d798c30f0cb
7
+ data.tar.gz: 373c8413336635a360f75c1df37ace49cdeab8b57656d0a729d7160efd67eb8317544b8f467696ffdb921edf8f2e0311253848d3168b59bf4d7ff2188e730d60
@@ -207,7 +207,7 @@
207
207
  "minimum_integrated_part_load_value": 0.55,
208
208
  "capft": "WaterCooled_Centrifugal_Chiller_GT150_2004_CAPFT",
209
209
  "eirft": "WaterCooled_Centrifugal_Chiller_GT150_2004_EIRFT",
210
- "eirfplr": "ChlrWtrCentPathBGtEql600tonEIRRatio_fQRatio",
210
+ "eirfplr": "ChlrWtrCentPathAAllEIRRatio_fQRatio",
211
211
  "notes": null
212
212
  },
213
213
  {
@@ -492,7 +492,7 @@
492
492
  "minimum_integrated_part_load_value": 0.549,
493
493
  "capft": "WaterCooled_Centrifugal_Chiller_GT150_2004_CAPFT",
494
494
  "eirft": "WaterCooled_Centrifugal_Chiller_GT150_2004_EIRFT",
495
- "eirfplr": "ChlrWtrCentPathBGtEql300Lt600tonEIRRatio_fQRatio",
495
+ "eirfplr": "ChlrWtrCentPathAAllEIRRatio_fQRatio",
496
496
  "notes": "Path A Minimum Efficiencies"
497
497
  },
498
498
  {
@@ -507,7 +507,7 @@
507
507
  "minimum_integrated_part_load_value": 0.539,
508
508
  "capft": "WaterCooled_Centrifugal_Chiller_GT150_2004_CAPFT",
509
509
  "eirft": "WaterCooled_Centrifugal_Chiller_GT150_2004_EIRFT",
510
- "eirfplr": "ChlrWtrCentPathBGtEql600tonEIRRatio_fQRatio",
510
+ "eirfplr": "ChlrWtrCentPathAAllEIRRatio_fQRatio",
511
511
  "notes": "Path A Minimum Efficiencies"
512
512
  },
513
513
  {
@@ -1197,7 +1197,7 @@
1197
1197
  "minimum_integrated_part_load_value": 0.5,
1198
1198
  "capft": "WaterCooled_Centrifugal_Chiller_2010_PathB_CAPFT",
1199
1199
  "eirft": "WaterCooled_Centrifugal_Chiller_2010_PathB_EIRFT",
1200
- "eirfplr": "ChlrWtrCentPathBGtEql300Lt600tonEIRRatio_fQRatio",
1200
+ "eirfplr": "ChlrWtrCentPathAAllEIRRatio_fQRatio",
1201
1201
  "notes": null
1202
1202
  },
1203
1203
  {
@@ -1212,7 +1212,7 @@
1212
1212
  "minimum_integrated_part_load_value": 0.5,
1213
1213
  "capft": "WaterCooled_Centrifugal_Chiller_2010_PathB_CAPFT",
1214
1214
  "eirft": "WaterCooled_Centrifugal_Chiller_2010_PathB_EIRFT",
1215
- "eirfplr": "ChlrWtrCentPathBGtEql600tonEIRRatio_fQRatio",
1215
+ "eirfplr": "ChlrWtrCentPathAAllEIRRatio_fQRatio",
1216
1216
  "notes": "Add but unsure what to put for Minimum full load efficiency and min IPLV"
1217
1217
  },
1218
1218
  {
@@ -4967,7 +4967,7 @@
4967
4967
  "space_type": "PatRoom",
4968
4968
  "is_residential": "No",
4969
4969
  "exterior_wall_standards_construction_type": "Mass",
4970
- "exterior_wall_building_category": "Residential",
4970
+ "exterior_wall_building_category": "Nonresidential",
4971
4971
  "exterior_floor_standards_construction_type": "Mass",
4972
4972
  "exterior_floor_building_category": "Residential",
4973
4973
  "exterior_roof_standards_construction_type": "IEAD",
@@ -5910,7 +5910,7 @@
5910
5910
  "space_type": "PatRoom",
5911
5911
  "is_residential": "No",
5912
5912
  "exterior_wall_standards_construction_type": "Mass",
5913
- "exterior_wall_building_category": "Residential",
5913
+ "exterior_wall_building_category": "Nonresidential",
5914
5914
  "exterior_floor_standards_construction_type": "Mass",
5915
5915
  "exterior_floor_building_category": "Residential",
5916
5916
  "exterior_roof_standards_construction_type": "IEAD",
@@ -444,6 +444,18 @@
444
444
  "max_out": null,
445
445
  "notes": "From Prototype Buildings"
446
446
  },
447
+ {
448
+ "name": "VSD-TWR-FAN-FPLR",
449
+ "coeff_1": 0.33162901,
450
+ "coeff_2": -0.88567609,
451
+ "coeff_3": 0.60556507,
452
+ "coeff_4": 0.9484823,
453
+ "min_x": 0.0,
454
+ "max_x": 1.0,
455
+ "min_out": null,
456
+ "max_out": null,
457
+ "notes": "From PNNL PRM Reference Manual"
458
+ },
447
459
  {
448
460
  "name": "VarVolFan-AFBIFanCurve-NECB2011-FPLR",
449
461
  "coeff_1": -2.4176,
@@ -1,83 +1,16 @@
1
1
  {
2
2
  "heat_pumps": [
3
- {
4
- "template": "90.1-2010",
5
- "cooling_type": "AirCooled",
6
- "heating_type": "Electric Resistance or None",
7
- "subcategory": "Split System",
8
- "minimum_capacity": 0.0,
9
- "maximum_capacity": 9999999.0,
10
- "minimum_seasonal_efficiency": 13.0,
11
- "minimum_full_load_efficiency": null,
12
- "minimum_iplv": null,
13
- "cool_cap_ft": "HPACCoolCapFT",
14
- "cool_cap_fflow": "HPACCoolCapFFF",
15
- "cool_eir_ft": "HPACCOOLEIRFT",
16
- "cool_eir_fflow": "HPACCOOLEIRFFF",
17
- "cool_plf_fplr": "HPACCOOLPLFFPLR",
18
- "notes": null
19
- },
20
- {
21
- "template": "90.1-2010",
22
- "cooling_type": "AirCooled",
23
- "heating_type": "All Other",
24
- "subcategory": "Split System",
25
- "minimum_capacity": 0.0,
26
- "maximum_capacity": 9999999.0,
27
- "minimum_seasonal_efficiency": 13.0,
28
- "minimum_full_load_efficiency": null,
29
- "minimum_iplv": null,
30
- "cool_cap_ft": "HPACCoolCapFT",
31
- "cool_cap_fflow": "HPACCoolCapFFF",
32
- "cool_eir_ft": "HPACCOOLEIRFT",
33
- "cool_eir_fflow": "HPACCOOLEIRFFF",
34
- "cool_plf_fplr": "HPACCOOLPLFFPLR",
35
- "notes": null
36
- },
37
- {
38
- "template": "90.1-2010",
39
- "cooling_type": "AirCooled",
40
- "heating_type": "Electric Resistance or None",
41
- "subcategory": "Single Package",
42
- "minimum_capacity": 0.0,
43
- "maximum_capacity": 9999999.0,
44
- "minimum_seasonal_efficiency": 13.0,
45
- "minimum_full_load_efficiency": null,
46
- "minimum_iplv": null,
47
- "cool_cap_ft": "HPACCoolCapFT",
48
- "cool_cap_fflow": "HPACCoolCapFFF",
49
- "cool_eir_ft": "HPACCOOLEIRFT",
50
- "cool_eir_fflow": "HPACCOOLEIRFFF",
51
- "cool_plf_fplr": "HPACCOOLPLFFPLR",
52
- "notes": null
53
- },
54
- {
55
- "template": "90.1-2010",
56
- "cooling_type": "AirCooled",
57
- "heating_type": "All Other",
58
- "subcategory": "Single Package",
59
- "minimum_capacity": 0.0,
60
- "maximum_capacity": 9999999.0,
61
- "minimum_seasonal_efficiency": 13.0,
62
- "minimum_full_load_efficiency": null,
63
- "minimum_iplv": null,
64
- "cool_cap_ft": "HPACCoolCapFT",
65
- "cool_cap_fflow": "HPACCoolCapFFF",
66
- "cool_eir_ft": "HPACCOOLEIRFT",
67
- "cool_eir_fflow": "HPACCOOLEIRFFF",
68
- "cool_plf_fplr": "HPACCOOLPLFFPLR",
69
- "notes": null
70
- },
71
3
  {
72
4
  "template": "NECB 2011",
73
5
  "cooling_type": "AirCooled",
74
6
  "heating_type": "Electric Resistance or None",
75
7
  "subcategory": "Single Package",
76
- "minimum_capacity": "-",
8
+ "minimum_capacity": 0.0,
77
9
  "maximum_capacity": 65000.0,
78
10
  "minimum_seasonal_efficiency": null,
79
11
  "minimum_full_load_efficiency": 10.0,
80
12
  "minimum_iplv": null,
13
+ "minimum_integrated_energy_efficiency_ratio": null,
81
14
  "cool_cap_ft": "DXCOOL-NECB2011-REF-CAPFT",
82
15
  "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW",
83
16
  "cool_eir_ft": "DXCOOL-NECB2011-REF-COOLEIRFT",
@@ -90,11 +23,12 @@
90
23
  "cooling_type": "AirCooled",
91
24
  "heating_type": "All Other",
92
25
  "subcategory": "Single Package",
93
- "minimum_capacity": "-",
26
+ "minimum_capacity": 0.0,
94
27
  "maximum_capacity": 65000.0,
95
28
  "minimum_seasonal_efficiency": null,
96
29
  "minimum_full_load_efficiency": 10.0,
97
30
  "minimum_iplv": null,
31
+ "minimum_integrated_energy_efficiency_ratio": null,
98
32
  "cool_cap_ft": "DXCOOL-NECB2011-REF-CAPFT",
99
33
  "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW",
100
34
  "cool_eir_ft": "DXCOOL-NECB2011-REF-COOLEIRFT",
@@ -107,11 +41,12 @@
107
41
  "cooling_type": "AirCooled",
108
42
  "heating_type": "Electric Resistance or None",
109
43
  "subcategory": "Split System",
110
- "minimum_capacity": "-",
44
+ "minimum_capacity": 0.0,
111
45
  "maximum_capacity": 65000.0,
112
46
  "minimum_seasonal_efficiency": null,
113
47
  "minimum_full_load_efficiency": 10.0,
114
48
  "minimum_iplv": null,
49
+ "minimum_integrated_energy_efficiency_ratio": null,
115
50
  "cool_cap_ft": "DXCOOL-NECB2011-REF-CAPFT",
116
51
  "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW",
117
52
  "cool_eir_ft": "DXCOOL-NECB2011-REF-COOLEIRFT",
@@ -124,11 +59,12 @@
124
59
  "cooling_type": "AirCooled",
125
60
  "heating_type": "All Other",
126
61
  "subcategory": "Split System",
127
- "minimum_capacity": "-",
62
+ "minimum_capacity": 0.0,
128
63
  "maximum_capacity": 65000.0,
129
64
  "minimum_seasonal_efficiency": null,
130
65
  "minimum_full_load_efficiency": 10.0,
131
66
  "minimum_iplv": null,
67
+ "minimum_integrated_energy_efficiency_ratio": null,
132
68
  "cool_cap_ft": "DXCOOL-NECB2011-REF-CAPFT",
133
69
  "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW",
134
70
  "cool_eir_ft": "DXCOOL-NECB2011-REF-COOLEIRFT",
@@ -146,6 +82,7 @@
146
82
  "minimum_seasonal_efficiency": null,
147
83
  "minimum_full_load_efficiency": 9.26,
148
84
  "minimum_iplv": null,
85
+ "minimum_integrated_energy_efficiency_ratio": null,
149
86
  "cool_cap_ft": "DXCOOL-NECB2011-REF-CAPFT",
150
87
  "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW",
151
88
  "cool_eir_ft": "DXCOOL-NECB2011-REF-COOLEIRFT",
@@ -163,6 +100,7 @@
163
100
  "minimum_seasonal_efficiency": null,
164
101
  "minimum_full_load_efficiency": 9.08,
165
102
  "minimum_iplv": null,
103
+ "minimum_integrated_energy_efficiency_ratio": null,
166
104
  "cool_cap_ft": "DXCOOL-NECB2011-REF-CAPFT",
167
105
  "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW",
168
106
  "cool_eir_ft": "DXCOOL-NECB2011-REF-COOLEIRFT",
@@ -180,6 +118,7 @@
180
118
  "minimum_seasonal_efficiency": null,
181
119
  "minimum_full_load_efficiency": 9.26,
182
120
  "minimum_iplv": null,
121
+ "minimum_integrated_energy_efficiency_ratio": null,
183
122
  "cool_cap_ft": "DXCOOL-NECB2011-REF-CAPFT",
184
123
  "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW",
185
124
  "cool_eir_ft": "DXCOOL-NECB2011-REF-COOLEIRFT",
@@ -197,6 +136,7 @@
197
136
  "minimum_seasonal_efficiency": null,
198
137
  "minimum_full_load_efficiency": 9.08,
199
138
  "minimum_iplv": null,
139
+ "minimum_integrated_energy_efficiency_ratio": null,
200
140
  "cool_cap_ft": "DXCOOL-NECB2011-REF-CAPFT",
201
141
  "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW",
202
142
  "cool_eir_ft": "DXCOOL-NECB2011-REF-COOLEIRFT",
@@ -214,6 +154,7 @@
214
154
  "minimum_seasonal_efficiency": null,
215
155
  "minimum_full_load_efficiency": 8.9,
216
156
  "minimum_iplv": null,
157
+ "minimum_integrated_energy_efficiency_ratio": null,
217
158
  "cool_cap_ft": "DXCOOL-NECB2011-REF-CAPFT",
218
159
  "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW",
219
160
  "cool_eir_ft": "DXCOOL-NECB2011-REF-COOLEIRFT",
@@ -231,6 +172,7 @@
231
172
  "minimum_seasonal_efficiency": null,
232
173
  "minimum_full_load_efficiency": 8.72,
233
174
  "minimum_iplv": null,
175
+ "minimum_integrated_energy_efficiency_ratio": null,
234
176
  "cool_cap_ft": "DXCOOL-NECB2011-REF-CAPFT",
235
177
  "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW",
236
178
  "cool_eir_ft": "DXCOOL-NECB2011-REF-COOLEIRFT",
@@ -248,6 +190,7 @@
248
190
  "minimum_seasonal_efficiency": null,
249
191
  "minimum_full_load_efficiency": 8.9,
250
192
  "minimum_iplv": null,
193
+ "minimum_integrated_energy_efficiency_ratio": null,
251
194
  "cool_cap_ft": "DXCOOL-NECB2011-REF-CAPFT",
252
195
  "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW",
253
196
  "cool_eir_ft": "DXCOOL-NECB2011-REF-COOLEIRFT",
@@ -265,6 +208,7 @@
265
208
  "minimum_seasonal_efficiency": null,
266
209
  "minimum_full_load_efficiency": 8.72,
267
210
  "minimum_iplv": null,
211
+ "minimum_integrated_energy_efficiency_ratio": null,
268
212
  "cool_cap_ft": "DXCOOL-NECB2011-REF-CAPFT",
269
213
  "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW",
270
214
  "cool_eir_ft": "DXCOOL-NECB2011-REF-COOLEIRFT",
@@ -282,6 +226,7 @@
282
226
  "minimum_seasonal_efficiency": null,
283
227
  "minimum_full_load_efficiency": 7.94,
284
228
  "minimum_iplv": null,
229
+ "minimum_integrated_energy_efficiency_ratio": null,
285
230
  "cool_cap_ft": "DXCOOL-NECB2011-REF-CAPFT",
286
231
  "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW",
287
232
  "cool_eir_ft": "DXCOOL-NECB2011-REF-COOLEIRFT",
@@ -299,6 +244,7 @@
299
244
  "minimum_seasonal_efficiency": null,
300
245
  "minimum_full_load_efficiency": 7.76,
301
246
  "minimum_iplv": null,
247
+ "minimum_integrated_energy_efficiency_ratio": null,
302
248
  "cool_cap_ft": "DXCOOL-NECB2011-REF-CAPFT",
303
249
  "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW",
304
250
  "cool_eir_ft": "DXCOOL-NECB2011-REF-COOLEIRFT",
@@ -316,6 +262,7 @@
316
262
  "minimum_seasonal_efficiency": null,
317
263
  "minimum_full_load_efficiency": 7.94,
318
264
  "minimum_iplv": null,
265
+ "minimum_integrated_energy_efficiency_ratio": null,
319
266
  "cool_cap_ft": "DXCOOL-NECB2011-REF-CAPFT",
320
267
  "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW",
321
268
  "cool_eir_ft": "DXCOOL-NECB2011-REF-COOLEIRFT",
@@ -333,12 +280,2119 @@
333
280
  "minimum_seasonal_efficiency": null,
334
281
  "minimum_full_load_efficiency": 7.76,
335
282
  "minimum_iplv": null,
283
+ "minimum_integrated_energy_efficiency_ratio": null,
336
284
  "cool_cap_ft": "DXCOOL-NECB2011-REF-CAPFT",
337
285
  "cool_cap_fflow": "DXCOOL-NECB2011-REF-CAPFFLOW",
338
286
  "cool_eir_ft": "DXCOOL-NECB2011-REF-COOLEIRFT",
339
287
  "cool_eir_fflow": "DXCOOL-NECB2011-REF-COOLEIRFFLOW",
340
288
  "cool_plf_fplr": "DXCOOL-NECB2011-REF-COOLPLFFPLR",
341
289
  "notes": null
290
+ },
291
+ {
292
+ "template": "DOE Ref Pre-1980",
293
+ "cooling_type": "AirCooled",
294
+ "heating_type": null,
295
+ "subcategory": "Split System",
296
+ "minimum_capacity": 0.0,
297
+ "maximum_capacity": 64999.0,
298
+ "minimum_seasonal_efficiency": 10.0,
299
+ "minimum_full_load_efficiency": null,
300
+ "minimum_iplv": null,
301
+ "minimum_integrated_energy_efficiency_ratio": null,
302
+ "cool_cap_ft": "HPACCoolCapFT",
303
+ "cool_cap_fflow": "HPACCoolCapFFF",
304
+ "cool_eir_ft": "HPACCOOLEIRFT",
305
+ "cool_eir_fflow": "HPACCOOLEIRFFF",
306
+ "cool_plf_fplr": "HPACCOOLPLFFPLR",
307
+ "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
308
+ },
309
+ {
310
+ "template": "DOE Ref Pre-1980",
311
+ "cooling_type": "AirCooled",
312
+ "heating_type": null,
313
+ "subcategory": "Single Package",
314
+ "minimum_capacity": 0.0,
315
+ "maximum_capacity": 64999.0,
316
+ "minimum_seasonal_efficiency": 9.7,
317
+ "minimum_full_load_efficiency": null,
318
+ "minimum_iplv": null,
319
+ "minimum_integrated_energy_efficiency_ratio": null,
320
+ "cool_cap_ft": "HPACCoolCapFT",
321
+ "cool_cap_fflow": "HPACCoolCapFFF",
322
+ "cool_eir_ft": "HPACCOOLEIRFT",
323
+ "cool_eir_fflow": "HPACCOOLEIRFFF",
324
+ "cool_plf_fplr": "HPACCOOLPLFFPLR",
325
+ "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
326
+ },
327
+ {
328
+ "template": "DOE Ref Pre-1980",
329
+ "cooling_type": "ThroughWall",
330
+ "heating_type": null,
331
+ "subcategory": "Split System",
332
+ "minimum_capacity": 0.0,
333
+ "maximum_capacity": 29999.0,
334
+ "minimum_seasonal_efficiency": 10.0,
335
+ "minimum_full_load_efficiency": null,
336
+ "minimum_iplv": null,
337
+ "minimum_integrated_energy_efficiency_ratio": null,
338
+ "cool_cap_ft": "HPACCoolCapFT",
339
+ "cool_cap_fflow": "HPACCoolCapFFF",
340
+ "cool_eir_ft": "HPACCOOLEIRFT",
341
+ "cool_eir_fflow": "HPACCOOLEIRFFF",
342
+ "cool_plf_fplr": "HPACCOOLPLFFPLR",
343
+ "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
344
+ },
345
+ {
346
+ "template": "DOE Ref Pre-1980",
347
+ "cooling_type": "ThroughWall",
348
+ "heating_type": null,
349
+ "subcategory": "Single Package",
350
+ "minimum_capacity": 0.0,
351
+ "maximum_capacity": 29999.0,
352
+ "minimum_seasonal_efficiency": 9.7,
353
+ "minimum_full_load_efficiency": null,
354
+ "minimum_iplv": null,
355
+ "minimum_integrated_energy_efficiency_ratio": null,
356
+ "cool_cap_ft": "HPACCoolCapFT",
357
+ "cool_cap_fflow": "HPACCoolCapFFF",
358
+ "cool_eir_ft": "HPACCOOLEIRFT",
359
+ "cool_eir_fflow": "HPACCOOLEIRFFF",
360
+ "cool_plf_fplr": "HPACCOOLPLFFPLR",
361
+ "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
362
+ },
363
+ {
364
+ "template": "DOE Ref Pre-1980",
365
+ "cooling_type": "SmallDuctHighVelocity",
366
+ "heating_type": null,
367
+ "subcategory": "Split System",
368
+ "minimum_capacity": 0.0,
369
+ "maximum_capacity": 64999.0,
370
+ "minimum_seasonal_efficiency": 10.0,
371
+ "minimum_full_load_efficiency": null,
372
+ "minimum_iplv": null,
373
+ "minimum_integrated_energy_efficiency_ratio": null,
374
+ "cool_cap_ft": "HPACCoolCapFT",
375
+ "cool_cap_fflow": "HPACCoolCapFFF",
376
+ "cool_eir_ft": "HPACCOOLEIRFT",
377
+ "cool_eir_fflow": "HPACCOOLEIRFFF",
378
+ "cool_plf_fplr": "HPACCOOLPLFFPLR",
379
+ "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
380
+ },
381
+ {
382
+ "template": "DOE Ref Pre-1980",
383
+ "cooling_type": "AirCooled",
384
+ "heating_type": "Electric Resistance or None",
385
+ "subcategory": "Split System",
386
+ "minimum_capacity": 65000.0,
387
+ "maximum_capacity": 134999.0,
388
+ "minimum_seasonal_efficiency": null,
389
+ "minimum_full_load_efficiency": 10.1,
390
+ "minimum_iplv": null,
391
+ "minimum_integrated_energy_efficiency_ratio": null,
392
+ "cool_cap_ft": "HPACCoolCapFT",
393
+ "cool_cap_fflow": "HPACCoolCapFFF",
394
+ "cool_eir_ft": "HPACCOOLEIRFT",
395
+ "cool_eir_fflow": "HPACCOOLEIRFFF",
396
+ "cool_plf_fplr": "HPACCOOLPLFFPLR",
397
+ "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
398
+ },
399
+ {
400
+ "template": "DOE Ref Pre-1980",
401
+ "cooling_type": "AirCooled",
402
+ "heating_type": "Electric Resistance or None",
403
+ "subcategory": "Single Package",
404
+ "minimum_capacity": 65000.0,
405
+ "maximum_capacity": 134999.0,
406
+ "minimum_seasonal_efficiency": null,
407
+ "minimum_full_load_efficiency": 10.1,
408
+ "minimum_iplv": null,
409
+ "minimum_integrated_energy_efficiency_ratio": null,
410
+ "cool_cap_ft": "HPACCoolCapFT",
411
+ "cool_cap_fflow": "HPACCoolCapFFF",
412
+ "cool_eir_ft": "HPACCOOLEIRFT",
413
+ "cool_eir_fflow": "HPACCOOLEIRFFF",
414
+ "cool_plf_fplr": "HPACCOOLPLFFPLR",
415
+ "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
416
+ },
417
+ {
418
+ "template": "DOE Ref Pre-1980",
419
+ "cooling_type": "AirCooled",
420
+ "heating_type": "All Other",
421
+ "subcategory": "Split System",
422
+ "minimum_capacity": 65000.0,
423
+ "maximum_capacity": 134999.0,
424
+ "minimum_seasonal_efficiency": null,
425
+ "minimum_full_load_efficiency": 9.9,
426
+ "minimum_iplv": null,
427
+ "minimum_integrated_energy_efficiency_ratio": null,
428
+ "cool_cap_ft": "HPACCoolCapFT",
429
+ "cool_cap_fflow": "HPACCoolCapFFF",
430
+ "cool_eir_ft": "HPACCOOLEIRFT",
431
+ "cool_eir_fflow": "HPACCOOLEIRFFF",
432
+ "cool_plf_fplr": "HPACCOOLPLFFPLR",
433
+ "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
434
+ },
435
+ {
436
+ "template": "DOE Ref Pre-1980",
437
+ "cooling_type": "AirCooled",
438
+ "heating_type": "All Other",
439
+ "subcategory": "Single Package",
440
+ "minimum_capacity": 65000.0,
441
+ "maximum_capacity": 134999.0,
442
+ "minimum_seasonal_efficiency": null,
443
+ "minimum_full_load_efficiency": 9.9,
444
+ "minimum_iplv": null,
445
+ "minimum_integrated_energy_efficiency_ratio": null,
446
+ "cool_cap_ft": "HPACCoolCapFT",
447
+ "cool_cap_fflow": "HPACCoolCapFFF",
448
+ "cool_eir_ft": "HPACCOOLEIRFT",
449
+ "cool_eir_fflow": "HPACCOOLEIRFFF",
450
+ "cool_plf_fplr": "HPACCOOLPLFFPLR",
451
+ "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
452
+ },
453
+ {
454
+ "template": "DOE Ref Pre-1980",
455
+ "cooling_type": "AirCooled",
456
+ "heating_type": "Electric Resistance or None",
457
+ "subcategory": "Split System",
458
+ "minimum_capacity": 135000.0,
459
+ "maximum_capacity": 239999.0,
460
+ "minimum_seasonal_efficiency": null,
461
+ "minimum_full_load_efficiency": 9.3,
462
+ "minimum_iplv": null,
463
+ "minimum_integrated_energy_efficiency_ratio": null,
464
+ "cool_cap_ft": "HPACCoolCapFT",
465
+ "cool_cap_fflow": "HPACCoolCapFFF",
466
+ "cool_eir_ft": "HPACCOOLEIRFT",
467
+ "cool_eir_fflow": "HPACCOOLEIRFFF",
468
+ "cool_plf_fplr": "HPACCOOLPLFFPLR",
469
+ "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
470
+ },
471
+ {
472
+ "template": "DOE Ref Pre-1980",
473
+ "cooling_type": "AirCooled",
474
+ "heating_type": "Electric Resistance or None",
475
+ "subcategory": "Single Package",
476
+ "minimum_capacity": 135000.0,
477
+ "maximum_capacity": 239999.0,
478
+ "minimum_seasonal_efficiency": null,
479
+ "minimum_full_load_efficiency": 9.3,
480
+ "minimum_iplv": null,
481
+ "minimum_integrated_energy_efficiency_ratio": null,
482
+ "cool_cap_ft": "HPACCoolCapFT",
483
+ "cool_cap_fflow": "HPACCoolCapFFF",
484
+ "cool_eir_ft": "HPACCOOLEIRFT",
485
+ "cool_eir_fflow": "HPACCOOLEIRFFF",
486
+ "cool_plf_fplr": "HPACCOOLPLFFPLR",
487
+ "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
488
+ },
489
+ {
490
+ "template": "DOE Ref Pre-1980",
491
+ "cooling_type": "AirCooled",
492
+ "heating_type": "All Other",
493
+ "subcategory": "Split System",
494
+ "minimum_capacity": 135000.0,
495
+ "maximum_capacity": 239999.0,
496
+ "minimum_seasonal_efficiency": null,
497
+ "minimum_full_load_efficiency": 9.1,
498
+ "minimum_iplv": null,
499
+ "minimum_integrated_energy_efficiency_ratio": null,
500
+ "cool_cap_ft": "HPACCoolCapFT",
501
+ "cool_cap_fflow": "HPACCoolCapFFF",
502
+ "cool_eir_ft": "HPACCOOLEIRFT",
503
+ "cool_eir_fflow": "HPACCOOLEIRFFF",
504
+ "cool_plf_fplr": "HPACCOOLPLFFPLR",
505
+ "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
506
+ },
507
+ {
508
+ "template": "DOE Ref Pre-1980",
509
+ "cooling_type": "AirCooled",
510
+ "heating_type": "All Other",
511
+ "subcategory": "Single Package",
512
+ "minimum_capacity": 135000.0,
513
+ "maximum_capacity": 239999.0,
514
+ "minimum_seasonal_efficiency": null,
515
+ "minimum_full_load_efficiency": 9.1,
516
+ "minimum_iplv": null,
517
+ "minimum_integrated_energy_efficiency_ratio": null,
518
+ "cool_cap_ft": "HPACCoolCapFT",
519
+ "cool_cap_fflow": "HPACCoolCapFFF",
520
+ "cool_eir_ft": "HPACCOOLEIRFT",
521
+ "cool_eir_fflow": "HPACCOOLEIRFFF",
522
+ "cool_plf_fplr": "HPACCOOLPLFFPLR",
523
+ "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
524
+ },
525
+ {
526
+ "template": "DOE Ref Pre-1980",
527
+ "cooling_type": "AirCooled",
528
+ "heating_type": "Electric Resistance or None",
529
+ "subcategory": "Split System",
530
+ "minimum_capacity": 240000.0,
531
+ "maximum_capacity": 9999999.0,
532
+ "minimum_seasonal_efficiency": null,
533
+ "minimum_full_load_efficiency": 9.0,
534
+ "minimum_iplv": 9.2,
535
+ "minimum_integrated_energy_efficiency_ratio": null,
536
+ "cool_cap_ft": "HPACCoolCapFT",
537
+ "cool_cap_fflow": "HPACCoolCapFFF",
538
+ "cool_eir_ft": "HPACCOOLEIRFT",
539
+ "cool_eir_fflow": "HPACCOOLEIRFFF",
540
+ "cool_plf_fplr": "HPACCOOLPLFFPLR",
541
+ "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
542
+ },
543
+ {
544
+ "template": "DOE Ref Pre-1980",
545
+ "cooling_type": "AirCooled",
546
+ "heating_type": "Electric Resistance or None",
547
+ "subcategory": "Single Package",
548
+ "minimum_capacity": 240000.0,
549
+ "maximum_capacity": 9999999.0,
550
+ "minimum_seasonal_efficiency": null,
551
+ "minimum_full_load_efficiency": 9.0,
552
+ "minimum_iplv": 9.2,
553
+ "minimum_integrated_energy_efficiency_ratio": null,
554
+ "cool_cap_ft": "HPACCoolCapFT",
555
+ "cool_cap_fflow": "HPACCoolCapFFF",
556
+ "cool_eir_ft": "HPACCOOLEIRFT",
557
+ "cool_eir_fflow": "HPACCOOLEIRFFF",
558
+ "cool_plf_fplr": "HPACCOOLPLFFPLR",
559
+ "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
560
+ },
561
+ {
562
+ "template": "DOE Ref Pre-1980",
563
+ "cooling_type": "AirCooled",
564
+ "heating_type": "All Other",
565
+ "subcategory": "Split System",
566
+ "minimum_capacity": 240000.0,
567
+ "maximum_capacity": 9999999.0,
568
+ "minimum_seasonal_efficiency": null,
569
+ "minimum_full_load_efficiency": 8.8,
570
+ "minimum_iplv": 9.0,
571
+ "minimum_integrated_energy_efficiency_ratio": null,
572
+ "cool_cap_ft": "HPACCoolCapFT",
573
+ "cool_cap_fflow": "HPACCoolCapFFF",
574
+ "cool_eir_ft": "HPACCOOLEIRFT",
575
+ "cool_eir_fflow": "HPACCOOLEIRFFF",
576
+ "cool_plf_fplr": "HPACCOOLPLFFPLR",
577
+ "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
578
+ },
579
+ {
580
+ "template": "DOE Ref Pre-1980",
581
+ "cooling_type": "AirCooled",
582
+ "heating_type": "All Other",
583
+ "subcategory": "Single Package",
584
+ "minimum_capacity": 240000.0,
585
+ "maximum_capacity": 9999999.0,
586
+ "minimum_seasonal_efficiency": null,
587
+ "minimum_full_load_efficiency": 8.8,
588
+ "minimum_iplv": 9.0,
589
+ "minimum_integrated_energy_efficiency_ratio": null,
590
+ "cool_cap_ft": "HPACCoolCapFT",
591
+ "cool_cap_fflow": "HPACCoolCapFFF",
592
+ "cool_eir_ft": "HPACCOOLEIRFT",
593
+ "cool_eir_fflow": "HPACCOOLEIRFFF",
594
+ "cool_plf_fplr": "HPACCOOLPLFFPLR",
595
+ "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
596
+ },
597
+ {
598
+ "template": "DOE Ref 1980-2004",
599
+ "cooling_type": "AirCooled",
600
+ "heating_type": null,
601
+ "subcategory": "Split System",
602
+ "minimum_capacity": 0.0,
603
+ "maximum_capacity": 64999.0,
604
+ "minimum_seasonal_efficiency": 10.0,
605
+ "minimum_full_load_efficiency": null,
606
+ "minimum_iplv": null,
607
+ "minimum_integrated_energy_efficiency_ratio": null,
608
+ "cool_cap_ft": "HPACCoolCapFT",
609
+ "cool_cap_fflow": "HPACCoolCapFFF",
610
+ "cool_eir_ft": "HPACCOOLEIRFT",
611
+ "cool_eir_fflow": "HPACCOOLEIRFFF",
612
+ "cool_plf_fplr": "HPACCOOLPLFFPLR",
613
+ "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
614
+ },
615
+ {
616
+ "template": "DOE Ref 1980-2004",
617
+ "cooling_type": "AirCooled",
618
+ "heating_type": null,
619
+ "subcategory": "Single Package",
620
+ "minimum_capacity": 0.0,
621
+ "maximum_capacity": 64999.0,
622
+ "minimum_seasonal_efficiency": 9.7,
623
+ "minimum_full_load_efficiency": null,
624
+ "minimum_iplv": null,
625
+ "minimum_integrated_energy_efficiency_ratio": null,
626
+ "cool_cap_ft": "HPACCoolCapFT",
627
+ "cool_cap_fflow": "HPACCoolCapFFF",
628
+ "cool_eir_ft": "HPACCOOLEIRFT",
629
+ "cool_eir_fflow": "HPACCOOLEIRFFF",
630
+ "cool_plf_fplr": "HPACCOOLPLFFPLR",
631
+ "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
632
+ },
633
+ {
634
+ "template": "DOE Ref 1980-2004",
635
+ "cooling_type": "ThroughWall",
636
+ "heating_type": null,
637
+ "subcategory": "Split System",
638
+ "minimum_capacity": 0.0,
639
+ "maximum_capacity": 29999.0,
640
+ "minimum_seasonal_efficiency": 10.0,
641
+ "minimum_full_load_efficiency": null,
642
+ "minimum_iplv": null,
643
+ "minimum_integrated_energy_efficiency_ratio": null,
644
+ "cool_cap_ft": "HPACCoolCapFT",
645
+ "cool_cap_fflow": "HPACCoolCapFFF",
646
+ "cool_eir_ft": "HPACCOOLEIRFT",
647
+ "cool_eir_fflow": "HPACCOOLEIRFFF",
648
+ "cool_plf_fplr": "HPACCOOLPLFFPLR",
649
+ "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
650
+ },
651
+ {
652
+ "template": "DOE Ref 1980-2004",
653
+ "cooling_type": "ThroughWall",
654
+ "heating_type": null,
655
+ "subcategory": "Single Package",
656
+ "minimum_capacity": 0.0,
657
+ "maximum_capacity": 29999.0,
658
+ "minimum_seasonal_efficiency": 9.7,
659
+ "minimum_full_load_efficiency": null,
660
+ "minimum_iplv": null,
661
+ "minimum_integrated_energy_efficiency_ratio": null,
662
+ "cool_cap_ft": "HPACCoolCapFT",
663
+ "cool_cap_fflow": "HPACCoolCapFFF",
664
+ "cool_eir_ft": "HPACCOOLEIRFT",
665
+ "cool_eir_fflow": "HPACCOOLEIRFFF",
666
+ "cool_plf_fplr": "HPACCOOLPLFFPLR",
667
+ "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
668
+ },
669
+ {
670
+ "template": "DOE Ref 1980-2004",
671
+ "cooling_type": "SmallDuctHighVelocity",
672
+ "heating_type": null,
673
+ "subcategory": "Split System",
674
+ "minimum_capacity": 0.0,
675
+ "maximum_capacity": 64999.0,
676
+ "minimum_seasonal_efficiency": 10.0,
677
+ "minimum_full_load_efficiency": null,
678
+ "minimum_iplv": null,
679
+ "minimum_integrated_energy_efficiency_ratio": null,
680
+ "cool_cap_ft": "HPACCoolCapFT",
681
+ "cool_cap_fflow": "HPACCoolCapFFF",
682
+ "cool_eir_ft": "HPACCOOLEIRFT",
683
+ "cool_eir_fflow": "HPACCOOLEIRFFF",
684
+ "cool_plf_fplr": "HPACCOOLPLFFPLR",
685
+ "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
686
+ },
687
+ {
688
+ "template": "DOE Ref 1980-2004",
689
+ "cooling_type": "AirCooled",
690
+ "heating_type": "Electric Resistance or None",
691
+ "subcategory": "Split System",
692
+ "minimum_capacity": 65000.0,
693
+ "maximum_capacity": 134999.0,
694
+ "minimum_seasonal_efficiency": null,
695
+ "minimum_full_load_efficiency": 10.1,
696
+ "minimum_iplv": null,
697
+ "minimum_integrated_energy_efficiency_ratio": null,
698
+ "cool_cap_ft": "HPACCoolCapFT",
699
+ "cool_cap_fflow": "HPACCoolCapFFF",
700
+ "cool_eir_ft": "HPACCOOLEIRFT",
701
+ "cool_eir_fflow": "HPACCOOLEIRFFF",
702
+ "cool_plf_fplr": "HPACCOOLPLFFPLR",
703
+ "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
704
+ },
705
+ {
706
+ "template": "DOE Ref 1980-2004",
707
+ "cooling_type": "AirCooled",
708
+ "heating_type": "Electric Resistance or None",
709
+ "subcategory": "Single Package",
710
+ "minimum_capacity": 65000.0,
711
+ "maximum_capacity": 134999.0,
712
+ "minimum_seasonal_efficiency": null,
713
+ "minimum_full_load_efficiency": 10.1,
714
+ "minimum_iplv": null,
715
+ "minimum_integrated_energy_efficiency_ratio": null,
716
+ "cool_cap_ft": "HPACCoolCapFT",
717
+ "cool_cap_fflow": "HPACCoolCapFFF",
718
+ "cool_eir_ft": "HPACCOOLEIRFT",
719
+ "cool_eir_fflow": "HPACCOOLEIRFFF",
720
+ "cool_plf_fplr": "HPACCOOLPLFFPLR",
721
+ "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
722
+ },
723
+ {
724
+ "template": "DOE Ref 1980-2004",
725
+ "cooling_type": "AirCooled",
726
+ "heating_type": "All Other",
727
+ "subcategory": "Split System",
728
+ "minimum_capacity": 65000.0,
729
+ "maximum_capacity": 134999.0,
730
+ "minimum_seasonal_efficiency": null,
731
+ "minimum_full_load_efficiency": 9.9,
732
+ "minimum_iplv": null,
733
+ "minimum_integrated_energy_efficiency_ratio": null,
734
+ "cool_cap_ft": "HPACCoolCapFT",
735
+ "cool_cap_fflow": "HPACCoolCapFFF",
736
+ "cool_eir_ft": "HPACCOOLEIRFT",
737
+ "cool_eir_fflow": "HPACCOOLEIRFFF",
738
+ "cool_plf_fplr": "HPACCOOLPLFFPLR",
739
+ "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
740
+ },
741
+ {
742
+ "template": "DOE Ref 1980-2004",
743
+ "cooling_type": "AirCooled",
744
+ "heating_type": "All Other",
745
+ "subcategory": "Single Package",
746
+ "minimum_capacity": 65000.0,
747
+ "maximum_capacity": 134999.0,
748
+ "minimum_seasonal_efficiency": null,
749
+ "minimum_full_load_efficiency": 9.9,
750
+ "minimum_iplv": null,
751
+ "minimum_integrated_energy_efficiency_ratio": null,
752
+ "cool_cap_ft": "HPACCoolCapFT",
753
+ "cool_cap_fflow": "HPACCoolCapFFF",
754
+ "cool_eir_ft": "HPACCOOLEIRFT",
755
+ "cool_eir_fflow": "HPACCOOLEIRFFF",
756
+ "cool_plf_fplr": "HPACCOOLPLFFPLR",
757
+ "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
758
+ },
759
+ {
760
+ "template": "DOE Ref 1980-2004",
761
+ "cooling_type": "AirCooled",
762
+ "heating_type": "Electric Resistance or None",
763
+ "subcategory": "Split System",
764
+ "minimum_capacity": 135000.0,
765
+ "maximum_capacity": 239999.0,
766
+ "minimum_seasonal_efficiency": null,
767
+ "minimum_full_load_efficiency": 9.3,
768
+ "minimum_iplv": null,
769
+ "minimum_integrated_energy_efficiency_ratio": null,
770
+ "cool_cap_ft": "HPACCoolCapFT",
771
+ "cool_cap_fflow": "HPACCoolCapFFF",
772
+ "cool_eir_ft": "HPACCOOLEIRFT",
773
+ "cool_eir_fflow": "HPACCOOLEIRFFF",
774
+ "cool_plf_fplr": "HPACCOOLPLFFPLR",
775
+ "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
776
+ },
777
+ {
778
+ "template": "DOE Ref 1980-2004",
779
+ "cooling_type": "AirCooled",
780
+ "heating_type": "Electric Resistance or None",
781
+ "subcategory": "Single Package",
782
+ "minimum_capacity": 135000.0,
783
+ "maximum_capacity": 239999.0,
784
+ "minimum_seasonal_efficiency": null,
785
+ "minimum_full_load_efficiency": 9.3,
786
+ "minimum_iplv": null,
787
+ "minimum_integrated_energy_efficiency_ratio": null,
788
+ "cool_cap_ft": "HPACCoolCapFT",
789
+ "cool_cap_fflow": "HPACCoolCapFFF",
790
+ "cool_eir_ft": "HPACCOOLEIRFT",
791
+ "cool_eir_fflow": "HPACCOOLEIRFFF",
792
+ "cool_plf_fplr": "HPACCOOLPLFFPLR",
793
+ "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
794
+ },
795
+ {
796
+ "template": "DOE Ref 1980-2004",
797
+ "cooling_type": "AirCooled",
798
+ "heating_type": "All Other",
799
+ "subcategory": "Split System",
800
+ "minimum_capacity": 135000.0,
801
+ "maximum_capacity": 239999.0,
802
+ "minimum_seasonal_efficiency": null,
803
+ "minimum_full_load_efficiency": 9.1,
804
+ "minimum_iplv": null,
805
+ "minimum_integrated_energy_efficiency_ratio": null,
806
+ "cool_cap_ft": "HPACCoolCapFT",
807
+ "cool_cap_fflow": "HPACCoolCapFFF",
808
+ "cool_eir_ft": "HPACCOOLEIRFT",
809
+ "cool_eir_fflow": "HPACCOOLEIRFFF",
810
+ "cool_plf_fplr": "HPACCOOLPLFFPLR",
811
+ "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
812
+ },
813
+ {
814
+ "template": "DOE Ref 1980-2004",
815
+ "cooling_type": "AirCooled",
816
+ "heating_type": "All Other",
817
+ "subcategory": "Single Package",
818
+ "minimum_capacity": 135000.0,
819
+ "maximum_capacity": 239999.0,
820
+ "minimum_seasonal_efficiency": null,
821
+ "minimum_full_load_efficiency": 9.1,
822
+ "minimum_iplv": null,
823
+ "minimum_integrated_energy_efficiency_ratio": null,
824
+ "cool_cap_ft": "HPACCoolCapFT",
825
+ "cool_cap_fflow": "HPACCoolCapFFF",
826
+ "cool_eir_ft": "HPACCOOLEIRFT",
827
+ "cool_eir_fflow": "HPACCOOLEIRFFF",
828
+ "cool_plf_fplr": "HPACCOOLPLFFPLR",
829
+ "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
830
+ },
831
+ {
832
+ "template": "DOE Ref 1980-2004",
833
+ "cooling_type": "AirCooled",
834
+ "heating_type": "Electric Resistance or None",
835
+ "subcategory": "Split System",
836
+ "minimum_capacity": 240000.0,
837
+ "maximum_capacity": 9999999.0,
838
+ "minimum_seasonal_efficiency": null,
839
+ "minimum_full_load_efficiency": 9.0,
840
+ "minimum_iplv": 9.2,
841
+ "minimum_integrated_energy_efficiency_ratio": null,
842
+ "cool_cap_ft": "HPACCoolCapFT",
843
+ "cool_cap_fflow": "HPACCoolCapFFF",
844
+ "cool_eir_ft": "HPACCOOLEIRFT",
845
+ "cool_eir_fflow": "HPACCOOLEIRFFF",
846
+ "cool_plf_fplr": "HPACCOOLPLFFPLR",
847
+ "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
848
+ },
849
+ {
850
+ "template": "DOE Ref 1980-2004",
851
+ "cooling_type": "AirCooled",
852
+ "heating_type": "Electric Resistance or None",
853
+ "subcategory": "Single Package",
854
+ "minimum_capacity": 240000.0,
855
+ "maximum_capacity": 9999999.0,
856
+ "minimum_seasonal_efficiency": null,
857
+ "minimum_full_load_efficiency": 9.0,
858
+ "minimum_iplv": 9.2,
859
+ "minimum_integrated_energy_efficiency_ratio": null,
860
+ "cool_cap_ft": "HPACCoolCapFT",
861
+ "cool_cap_fflow": "HPACCoolCapFFF",
862
+ "cool_eir_ft": "HPACCOOLEIRFT",
863
+ "cool_eir_fflow": "HPACCOOLEIRFFF",
864
+ "cool_plf_fplr": "HPACCOOLPLFFPLR",
865
+ "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
866
+ },
867
+ {
868
+ "template": "DOE Ref 1980-2004",
869
+ "cooling_type": "AirCooled",
870
+ "heating_type": "All Other",
871
+ "subcategory": "Split System",
872
+ "minimum_capacity": 240000.0,
873
+ "maximum_capacity": 9999999.0,
874
+ "minimum_seasonal_efficiency": null,
875
+ "minimum_full_load_efficiency": 8.8,
876
+ "minimum_iplv": 9.0,
877
+ "minimum_integrated_energy_efficiency_ratio": null,
878
+ "cool_cap_ft": "HPACCoolCapFT",
879
+ "cool_cap_fflow": "HPACCoolCapFFF",
880
+ "cool_eir_ft": "HPACCOOLEIRFT",
881
+ "cool_eir_fflow": "HPACCOOLEIRFFF",
882
+ "cool_plf_fplr": "HPACCOOLPLFFPLR",
883
+ "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
884
+ },
885
+ {
886
+ "template": "DOE Ref 1980-2004",
887
+ "cooling_type": "AirCooled",
888
+ "heating_type": "All Other",
889
+ "subcategory": "Single Package",
890
+ "minimum_capacity": 240000.0,
891
+ "maximum_capacity": 9999999.0,
892
+ "minimum_seasonal_efficiency": null,
893
+ "minimum_full_load_efficiency": 8.8,
894
+ "minimum_iplv": 9.0,
895
+ "minimum_integrated_energy_efficiency_ratio": null,
896
+ "cool_cap_ft": "HPACCoolCapFT",
897
+ "cool_cap_fflow": "HPACCoolCapFFF",
898
+ "cool_eir_ft": "HPACCOOLEIRFT",
899
+ "cool_eir_fflow": "HPACCOOLEIRFFF",
900
+ "cool_plf_fplr": "HPACCOOLPLFFPLR",
901
+ "notes": "From 90.1-2004 since DOE Reference Buildings did not have any heat pumps"
902
+ },
903
+ {
904
+ "template": "90.1-2004",
905
+ "cooling_type": "AirCooled",
906
+ "heating_type": null,
907
+ "subcategory": "Split System",
908
+ "minimum_capacity": 0.0,
909
+ "maximum_capacity": 64999.0,
910
+ "minimum_seasonal_efficiency": 10.0,
911
+ "minimum_full_load_efficiency": null,
912
+ "minimum_iplv": null,
913
+ "minimum_integrated_energy_efficiency_ratio": null,
914
+ "cool_cap_ft": "HPACCoolCapFT",
915
+ "cool_cap_fflow": "HPACCoolCapFFF",
916
+ "cool_eir_ft": "HPACCOOLEIRFT",
917
+ "cool_eir_fflow": "HPACCOOLEIRFFF",
918
+ "cool_plf_fplr": "HPACCOOLPLFFPLR",
919
+ "notes": "From 90.1-2004 Table 6.8.1B, Before 1/23/2006"
920
+ },
921
+ {
922
+ "template": "90.1-2004",
923
+ "cooling_type": "AirCooled",
924
+ "heating_type": null,
925
+ "subcategory": "Single Package",
926
+ "minimum_capacity": 0.0,
927
+ "maximum_capacity": 64999.0,
928
+ "minimum_seasonal_efficiency": 9.7,
929
+ "minimum_full_load_efficiency": null,
930
+ "minimum_iplv": null,
931
+ "minimum_integrated_energy_efficiency_ratio": null,
932
+ "cool_cap_ft": "HPACCoolCapFT",
933
+ "cool_cap_fflow": "HPACCoolCapFFF",
934
+ "cool_eir_ft": "HPACCOOLEIRFT",
935
+ "cool_eir_fflow": "HPACCOOLEIRFFF",
936
+ "cool_plf_fplr": "HPACCOOLPLFFPLR",
937
+ "notes": "From 90.1-2004 Table 6.8.1B, Before 1/23/2006"
938
+ },
939
+ {
940
+ "template": "90.1-2004",
941
+ "cooling_type": "ThroughWall",
942
+ "heating_type": null,
943
+ "subcategory": "Split System",
944
+ "minimum_capacity": 0.0,
945
+ "maximum_capacity": 29999.0,
946
+ "minimum_seasonal_efficiency": 10.0,
947
+ "minimum_full_load_efficiency": null,
948
+ "minimum_iplv": null,
949
+ "minimum_integrated_energy_efficiency_ratio": null,
950
+ "cool_cap_ft": "HPACCoolCapFT",
951
+ "cool_cap_fflow": "HPACCoolCapFFF",
952
+ "cool_eir_ft": "HPACCOOLEIRFT",
953
+ "cool_eir_fflow": "HPACCOOLEIRFFF",
954
+ "cool_plf_fplr": "HPACCOOLPLFFPLR",
955
+ "notes": "From 90.1-2004 Table 6.8.1B, Before 1/23/2006"
956
+ },
957
+ {
958
+ "template": "90.1-2004",
959
+ "cooling_type": "ThroughWall",
960
+ "heating_type": null,
961
+ "subcategory": "Single Package",
962
+ "minimum_capacity": 0.0,
963
+ "maximum_capacity": 29999.0,
964
+ "minimum_seasonal_efficiency": 9.7,
965
+ "minimum_full_load_efficiency": null,
966
+ "minimum_iplv": null,
967
+ "minimum_integrated_energy_efficiency_ratio": null,
968
+ "cool_cap_ft": "HPACCoolCapFT",
969
+ "cool_cap_fflow": "HPACCoolCapFFF",
970
+ "cool_eir_ft": "HPACCOOLEIRFT",
971
+ "cool_eir_fflow": "HPACCOOLEIRFFF",
972
+ "cool_plf_fplr": "HPACCOOLPLFFPLR",
973
+ "notes": "From 90.1-2004 Table 6.8.1B, Before 1/23/2006"
974
+ },
975
+ {
976
+ "template": "90.1-2004",
977
+ "cooling_type": "SmallDuctHighVelocity",
978
+ "heating_type": null,
979
+ "subcategory": "Split System",
980
+ "minimum_capacity": 0.0,
981
+ "maximum_capacity": 64999.0,
982
+ "minimum_seasonal_efficiency": 10.0,
983
+ "minimum_full_load_efficiency": null,
984
+ "minimum_iplv": null,
985
+ "minimum_integrated_energy_efficiency_ratio": null,
986
+ "cool_cap_ft": "HPACCoolCapFT",
987
+ "cool_cap_fflow": "HPACCoolCapFFF",
988
+ "cool_eir_ft": "HPACCOOLEIRFT",
989
+ "cool_eir_fflow": "HPACCOOLEIRFFF",
990
+ "cool_plf_fplr": "HPACCOOLPLFFPLR",
991
+ "notes": "From 90.1-2004 Table 6.8.1B"
992
+ },
993
+ {
994
+ "template": "90.1-2004",
995
+ "cooling_type": "AirCooled",
996
+ "heating_type": "Electric Resistance or None",
997
+ "subcategory": "Split System",
998
+ "minimum_capacity": 65000.0,
999
+ "maximum_capacity": 134999.0,
1000
+ "minimum_seasonal_efficiency": null,
1001
+ "minimum_full_load_efficiency": 10.1,
1002
+ "minimum_iplv": null,
1003
+ "minimum_integrated_energy_efficiency_ratio": null,
1004
+ "cool_cap_ft": "HPACCoolCapFT",
1005
+ "cool_cap_fflow": "HPACCoolCapFFF",
1006
+ "cool_eir_ft": "HPACCOOLEIRFT",
1007
+ "cool_eir_fflow": "HPACCOOLEIRFFF",
1008
+ "cool_plf_fplr": "HPACCOOLPLFFPLR",
1009
+ "notes": "From 90.1-2004 Table 6.8.1B"
1010
+ },
1011
+ {
1012
+ "template": "90.1-2004",
1013
+ "cooling_type": "AirCooled",
1014
+ "heating_type": "Electric Resistance or None",
1015
+ "subcategory": "Single Package",
1016
+ "minimum_capacity": 65000.0,
1017
+ "maximum_capacity": 134999.0,
1018
+ "minimum_seasonal_efficiency": null,
1019
+ "minimum_full_load_efficiency": 10.1,
1020
+ "minimum_iplv": null,
1021
+ "minimum_integrated_energy_efficiency_ratio": null,
1022
+ "cool_cap_ft": "HPACCoolCapFT",
1023
+ "cool_cap_fflow": "HPACCoolCapFFF",
1024
+ "cool_eir_ft": "HPACCOOLEIRFT",
1025
+ "cool_eir_fflow": "HPACCOOLEIRFFF",
1026
+ "cool_plf_fplr": "HPACCOOLPLFFPLR",
1027
+ "notes": "From 90.1-2004 Table 6.8.1B"
1028
+ },
1029
+ {
1030
+ "template": "90.1-2004",
1031
+ "cooling_type": "AirCooled",
1032
+ "heating_type": "All Other",
1033
+ "subcategory": "Split System",
1034
+ "minimum_capacity": 65000.0,
1035
+ "maximum_capacity": 134999.0,
1036
+ "minimum_seasonal_efficiency": null,
1037
+ "minimum_full_load_efficiency": 9.9,
1038
+ "minimum_iplv": null,
1039
+ "minimum_integrated_energy_efficiency_ratio": null,
1040
+ "cool_cap_ft": "HPACCoolCapFT",
1041
+ "cool_cap_fflow": "HPACCoolCapFFF",
1042
+ "cool_eir_ft": "HPACCOOLEIRFT",
1043
+ "cool_eir_fflow": "HPACCOOLEIRFFF",
1044
+ "cool_plf_fplr": "HPACCOOLPLFFPLR",
1045
+ "notes": "From 90.1-2004 Table 6.8.1B"
1046
+ },
1047
+ {
1048
+ "template": "90.1-2004",
1049
+ "cooling_type": "AirCooled",
1050
+ "heating_type": "All Other",
1051
+ "subcategory": "Single Package",
1052
+ "minimum_capacity": 65000.0,
1053
+ "maximum_capacity": 134999.0,
1054
+ "minimum_seasonal_efficiency": null,
1055
+ "minimum_full_load_efficiency": 9.9,
1056
+ "minimum_iplv": null,
1057
+ "minimum_integrated_energy_efficiency_ratio": null,
1058
+ "cool_cap_ft": "HPACCoolCapFT",
1059
+ "cool_cap_fflow": "HPACCoolCapFFF",
1060
+ "cool_eir_ft": "HPACCOOLEIRFT",
1061
+ "cool_eir_fflow": "HPACCOOLEIRFFF",
1062
+ "cool_plf_fplr": "HPACCOOLPLFFPLR",
1063
+ "notes": "From 90.1-2004 Table 6.8.1B"
1064
+ },
1065
+ {
1066
+ "template": "90.1-2004",
1067
+ "cooling_type": "AirCooled",
1068
+ "heating_type": "Electric Resistance or None",
1069
+ "subcategory": "Split System",
1070
+ "minimum_capacity": 135000.0,
1071
+ "maximum_capacity": 239999.0,
1072
+ "minimum_seasonal_efficiency": null,
1073
+ "minimum_full_load_efficiency": 9.3,
1074
+ "minimum_iplv": null,
1075
+ "minimum_integrated_energy_efficiency_ratio": null,
1076
+ "cool_cap_ft": "HPACCoolCapFT",
1077
+ "cool_cap_fflow": "HPACCoolCapFFF",
1078
+ "cool_eir_ft": "HPACCOOLEIRFT",
1079
+ "cool_eir_fflow": "HPACCOOLEIRFFF",
1080
+ "cool_plf_fplr": "HPACCOOLPLFFPLR",
1081
+ "notes": "From 90.1-2004 Table 6.8.1B"
1082
+ },
1083
+ {
1084
+ "template": "90.1-2004",
1085
+ "cooling_type": "AirCooled",
1086
+ "heating_type": "Electric Resistance or None",
1087
+ "subcategory": "Single Package",
1088
+ "minimum_capacity": 135000.0,
1089
+ "maximum_capacity": 239999.0,
1090
+ "minimum_seasonal_efficiency": null,
1091
+ "minimum_full_load_efficiency": 9.3,
1092
+ "minimum_iplv": null,
1093
+ "minimum_integrated_energy_efficiency_ratio": null,
1094
+ "cool_cap_ft": "HPACCoolCapFT",
1095
+ "cool_cap_fflow": "HPACCoolCapFFF",
1096
+ "cool_eir_ft": "HPACCOOLEIRFT",
1097
+ "cool_eir_fflow": "HPACCOOLEIRFFF",
1098
+ "cool_plf_fplr": "HPACCOOLPLFFPLR",
1099
+ "notes": "From 90.1-2004 Table 6.8.1B"
1100
+ },
1101
+ {
1102
+ "template": "90.1-2004",
1103
+ "cooling_type": "AirCooled",
1104
+ "heating_type": "All Other",
1105
+ "subcategory": "Split System",
1106
+ "minimum_capacity": 135000.0,
1107
+ "maximum_capacity": 239999.0,
1108
+ "minimum_seasonal_efficiency": null,
1109
+ "minimum_full_load_efficiency": 9.1,
1110
+ "minimum_iplv": null,
1111
+ "minimum_integrated_energy_efficiency_ratio": null,
1112
+ "cool_cap_ft": "HPACCoolCapFT",
1113
+ "cool_cap_fflow": "HPACCoolCapFFF",
1114
+ "cool_eir_ft": "HPACCOOLEIRFT",
1115
+ "cool_eir_fflow": "HPACCOOLEIRFFF",
1116
+ "cool_plf_fplr": "HPACCOOLPLFFPLR",
1117
+ "notes": "From 90.1-2004 Table 6.8.1B"
1118
+ },
1119
+ {
1120
+ "template": "90.1-2004",
1121
+ "cooling_type": "AirCooled",
1122
+ "heating_type": "All Other",
1123
+ "subcategory": "Single Package",
1124
+ "minimum_capacity": 135000.0,
1125
+ "maximum_capacity": 239999.0,
1126
+ "minimum_seasonal_efficiency": null,
1127
+ "minimum_full_load_efficiency": 9.1,
1128
+ "minimum_iplv": null,
1129
+ "minimum_integrated_energy_efficiency_ratio": null,
1130
+ "cool_cap_ft": "HPACCoolCapFT",
1131
+ "cool_cap_fflow": "HPACCoolCapFFF",
1132
+ "cool_eir_ft": "HPACCOOLEIRFT",
1133
+ "cool_eir_fflow": "HPACCOOLEIRFFF",
1134
+ "cool_plf_fplr": "HPACCOOLPLFFPLR",
1135
+ "notes": "From 90.1-2004 Table 6.8.1B"
1136
+ },
1137
+ {
1138
+ "template": "90.1-2004",
1139
+ "cooling_type": "AirCooled",
1140
+ "heating_type": "Electric Resistance or None",
1141
+ "subcategory": "Split System",
1142
+ "minimum_capacity": 240000.0,
1143
+ "maximum_capacity": 9999999.0,
1144
+ "minimum_seasonal_efficiency": null,
1145
+ "minimum_full_load_efficiency": 9.0,
1146
+ "minimum_iplv": 9.2,
1147
+ "minimum_integrated_energy_efficiency_ratio": null,
1148
+ "cool_cap_ft": "HPACCoolCapFT",
1149
+ "cool_cap_fflow": "HPACCoolCapFFF",
1150
+ "cool_eir_ft": "HPACCOOLEIRFT",
1151
+ "cool_eir_fflow": "HPACCOOLEIRFFF",
1152
+ "cool_plf_fplr": "HPACCOOLPLFFPLR",
1153
+ "notes": "From 90.1-2004 Table 6.8.1B"
1154
+ },
1155
+ {
1156
+ "template": "90.1-2004",
1157
+ "cooling_type": "AirCooled",
1158
+ "heating_type": "Electric Resistance or None",
1159
+ "subcategory": "Single Package",
1160
+ "minimum_capacity": 240000.0,
1161
+ "maximum_capacity": 9999999.0,
1162
+ "minimum_seasonal_efficiency": null,
1163
+ "minimum_full_load_efficiency": 9.0,
1164
+ "minimum_iplv": 9.2,
1165
+ "minimum_integrated_energy_efficiency_ratio": null,
1166
+ "cool_cap_ft": "HPACCoolCapFT",
1167
+ "cool_cap_fflow": "HPACCoolCapFFF",
1168
+ "cool_eir_ft": "HPACCOOLEIRFT",
1169
+ "cool_eir_fflow": "HPACCOOLEIRFFF",
1170
+ "cool_plf_fplr": "HPACCOOLPLFFPLR",
1171
+ "notes": "From 90.1-2004 Table 6.8.1B"
1172
+ },
1173
+ {
1174
+ "template": "90.1-2004",
1175
+ "cooling_type": "AirCooled",
1176
+ "heating_type": "All Other",
1177
+ "subcategory": "Split System",
1178
+ "minimum_capacity": 240000.0,
1179
+ "maximum_capacity": 9999999.0,
1180
+ "minimum_seasonal_efficiency": null,
1181
+ "minimum_full_load_efficiency": 8.8,
1182
+ "minimum_iplv": 9.0,
1183
+ "minimum_integrated_energy_efficiency_ratio": null,
1184
+ "cool_cap_ft": "HPACCoolCapFT",
1185
+ "cool_cap_fflow": "HPACCoolCapFFF",
1186
+ "cool_eir_ft": "HPACCOOLEIRFT",
1187
+ "cool_eir_fflow": "HPACCOOLEIRFFF",
1188
+ "cool_plf_fplr": "HPACCOOLPLFFPLR",
1189
+ "notes": "From 90.1-2004 Table 6.8.1B"
1190
+ },
1191
+ {
1192
+ "template": "90.1-2004",
1193
+ "cooling_type": "AirCooled",
1194
+ "heating_type": "All Other",
1195
+ "subcategory": "Single Package",
1196
+ "minimum_capacity": 240000.0,
1197
+ "maximum_capacity": 9999999.0,
1198
+ "minimum_seasonal_efficiency": null,
1199
+ "minimum_full_load_efficiency": 8.8,
1200
+ "minimum_iplv": 9.0,
1201
+ "minimum_integrated_energy_efficiency_ratio": null,
1202
+ "cool_cap_ft": "HPACCoolCapFT",
1203
+ "cool_cap_fflow": "HPACCoolCapFFF",
1204
+ "cool_eir_ft": "HPACCOOLEIRFT",
1205
+ "cool_eir_fflow": "HPACCOOLEIRFFF",
1206
+ "cool_plf_fplr": "HPACCOOLPLFFPLR",
1207
+ "notes": "From 90.1-2004 Table 6.8.1B"
1208
+ },
1209
+ {
1210
+ "template": "90.1-2007",
1211
+ "cooling_type": "AirCooled",
1212
+ "heating_type": null,
1213
+ "subcategory": "Split System",
1214
+ "minimum_capacity": 0.0,
1215
+ "maximum_capacity": 64999.0,
1216
+ "minimum_seasonal_efficiency": 13.0,
1217
+ "minimum_full_load_efficiency": null,
1218
+ "minimum_iplv": null,
1219
+ "minimum_integrated_energy_efficiency_ratio": null,
1220
+ "cool_cap_ft": "HPACCoolCapFT",
1221
+ "cool_cap_fflow": "HPACCoolCapFFF",
1222
+ "cool_eir_ft": "HPACCOOLEIRFT",
1223
+ "cool_eir_fflow": "HPACCOOLEIRFFF",
1224
+ "cool_plf_fplr": "HPACCOOLPLFFPLR",
1225
+ "notes": "From 90.1-2007 Table 6.8.1B, As of 1/23/2006"
1226
+ },
1227
+ {
1228
+ "template": "90.1-2007",
1229
+ "cooling_type": "AirCooled",
1230
+ "heating_type": null,
1231
+ "subcategory": "Single Package",
1232
+ "minimum_capacity": 0.0,
1233
+ "maximum_capacity": 64999.0,
1234
+ "minimum_seasonal_efficiency": 13.0,
1235
+ "minimum_full_load_efficiency": null,
1236
+ "minimum_iplv": null,
1237
+ "minimum_integrated_energy_efficiency_ratio": null,
1238
+ "cool_cap_ft": "HPACCoolCapFT",
1239
+ "cool_cap_fflow": "HPACCoolCapFFF",
1240
+ "cool_eir_ft": "HPACCOOLEIRFT",
1241
+ "cool_eir_fflow": "HPACCOOLEIRFFF",
1242
+ "cool_plf_fplr": "HPACCOOLPLFFPLR",
1243
+ "notes": "From 90.1-2007 Table 6.8.1B, As of 1/23/2006"
1244
+ },
1245
+ {
1246
+ "template": "90.1-2007",
1247
+ "cooling_type": "ThroughWall",
1248
+ "heating_type": null,
1249
+ "subcategory": "Split System",
1250
+ "minimum_capacity": 0.0,
1251
+ "maximum_capacity": 29999.0,
1252
+ "minimum_seasonal_efficiency": 10.9,
1253
+ "minimum_full_load_efficiency": null,
1254
+ "minimum_iplv": null,
1255
+ "minimum_integrated_energy_efficiency_ratio": null,
1256
+ "cool_cap_ft": "HPACCoolCapFT",
1257
+ "cool_cap_fflow": "HPACCoolCapFFF",
1258
+ "cool_eir_ft": "HPACCOOLEIRFT",
1259
+ "cool_eir_fflow": "HPACCOOLEIRFFF",
1260
+ "cool_plf_fplr": "HPACCOOLPLFFPLR",
1261
+ "notes": "From 90.1-2007 Table 6.8.1B, As of 1/23/2006"
1262
+ },
1263
+ {
1264
+ "template": "90.1-2007",
1265
+ "cooling_type": "ThroughWall",
1266
+ "heating_type": null,
1267
+ "subcategory": "Single Package",
1268
+ "minimum_capacity": 0.0,
1269
+ "maximum_capacity": 29999.0,
1270
+ "minimum_seasonal_efficiency": 10.6,
1271
+ "minimum_full_load_efficiency": null,
1272
+ "minimum_iplv": null,
1273
+ "minimum_integrated_energy_efficiency_ratio": null,
1274
+ "cool_cap_ft": "HPACCoolCapFT",
1275
+ "cool_cap_fflow": "HPACCoolCapFFF",
1276
+ "cool_eir_ft": "HPACCOOLEIRFT",
1277
+ "cool_eir_fflow": "HPACCOOLEIRFFF",
1278
+ "cool_plf_fplr": "HPACCOOLPLFFPLR",
1279
+ "notes": "From 90.1-2007 Table 6.8.1B, As of 1/23/2006"
1280
+ },
1281
+ {
1282
+ "template": "90.1-2007",
1283
+ "cooling_type": "AirCooled",
1284
+ "heating_type": "Electric Resistance or None",
1285
+ "subcategory": "Split System",
1286
+ "minimum_capacity": 65000.0,
1287
+ "maximum_capacity": 134999.0,
1288
+ "minimum_seasonal_efficiency": null,
1289
+ "minimum_full_load_efficiency": 10.1,
1290
+ "minimum_iplv": null,
1291
+ "minimum_integrated_energy_efficiency_ratio": null,
1292
+ "cool_cap_ft": "HPACCoolCapFT",
1293
+ "cool_cap_fflow": "HPACCoolCapFFF",
1294
+ "cool_eir_ft": "HPACCOOLEIRFT",
1295
+ "cool_eir_fflow": "HPACCOOLEIRFFF",
1296
+ "cool_plf_fplr": "HPACCOOLPLFFPLR",
1297
+ "notes": "From 90.1-2007 Table 6.8.1B, Before 1/1/2010"
1298
+ },
1299
+ {
1300
+ "template": "90.1-2007",
1301
+ "cooling_type": "AirCooled",
1302
+ "heating_type": "Electric Resistance or None",
1303
+ "subcategory": "Single Package",
1304
+ "minimum_capacity": 65000.0,
1305
+ "maximum_capacity": 134999.0,
1306
+ "minimum_seasonal_efficiency": null,
1307
+ "minimum_full_load_efficiency": 10.1,
1308
+ "minimum_iplv": null,
1309
+ "minimum_integrated_energy_efficiency_ratio": null,
1310
+ "cool_cap_ft": "HPACCoolCapFT",
1311
+ "cool_cap_fflow": "HPACCoolCapFFF",
1312
+ "cool_eir_ft": "HPACCOOLEIRFT",
1313
+ "cool_eir_fflow": "HPACCOOLEIRFFF",
1314
+ "cool_plf_fplr": "HPACCOOLPLFFPLR",
1315
+ "notes": "From 90.1-2007 Table 6.8.1B, Before 1/1/2010"
1316
+ },
1317
+ {
1318
+ "template": "90.1-2007",
1319
+ "cooling_type": "AirCooled",
1320
+ "heating_type": "All Other",
1321
+ "subcategory": "Split System",
1322
+ "minimum_capacity": 65000.0,
1323
+ "maximum_capacity": 134999.0,
1324
+ "minimum_seasonal_efficiency": null,
1325
+ "minimum_full_load_efficiency": 9.9,
1326
+ "minimum_iplv": null,
1327
+ "minimum_integrated_energy_efficiency_ratio": null,
1328
+ "cool_cap_ft": "HPACCoolCapFT",
1329
+ "cool_cap_fflow": "HPACCoolCapFFF",
1330
+ "cool_eir_ft": "HPACCOOLEIRFT",
1331
+ "cool_eir_fflow": "HPACCOOLEIRFFF",
1332
+ "cool_plf_fplr": "HPACCOOLPLFFPLR",
1333
+ "notes": "From 90.1-2007 Table 6.8.1B, Before 1/1/2010"
1334
+ },
1335
+ {
1336
+ "template": "90.1-2007",
1337
+ "cooling_type": "AirCooled",
1338
+ "heating_type": "All Other",
1339
+ "subcategory": "Single Package",
1340
+ "minimum_capacity": 65000.0,
1341
+ "maximum_capacity": 134999.0,
1342
+ "minimum_seasonal_efficiency": null,
1343
+ "minimum_full_load_efficiency": 9.9,
1344
+ "minimum_iplv": null,
1345
+ "minimum_integrated_energy_efficiency_ratio": null,
1346
+ "cool_cap_ft": "HPACCoolCapFT",
1347
+ "cool_cap_fflow": "HPACCoolCapFFF",
1348
+ "cool_eir_ft": "HPACCOOLEIRFT",
1349
+ "cool_eir_fflow": "HPACCOOLEIRFFF",
1350
+ "cool_plf_fplr": "HPACCOOLPLFFPLR",
1351
+ "notes": "From 90.1-2007 Table 6.8.1B, Before 1/1/2010"
1352
+ },
1353
+ {
1354
+ "template": "90.1-2007",
1355
+ "cooling_type": "AirCooled",
1356
+ "heating_type": "Electric Resistance or None",
1357
+ "subcategory": "Split System",
1358
+ "minimum_capacity": 135000.0,
1359
+ "maximum_capacity": 239999.0,
1360
+ "minimum_seasonal_efficiency": null,
1361
+ "minimum_full_load_efficiency": 9.3,
1362
+ "minimum_iplv": null,
1363
+ "minimum_integrated_energy_efficiency_ratio": null,
1364
+ "cool_cap_ft": "HPACCoolCapFT",
1365
+ "cool_cap_fflow": "HPACCoolCapFFF",
1366
+ "cool_eir_ft": "HPACCOOLEIRFT",
1367
+ "cool_eir_fflow": "HPACCOOLEIRFFF",
1368
+ "cool_plf_fplr": "HPACCOOLPLFFPLR",
1369
+ "notes": "From 90.1-2007 Table 6.8.1B, Before 1/1/2010"
1370
+ },
1371
+ {
1372
+ "template": "90.1-2007",
1373
+ "cooling_type": "AirCooled",
1374
+ "heating_type": "Electric Resistance or None",
1375
+ "subcategory": "Single Package",
1376
+ "minimum_capacity": 135000.0,
1377
+ "maximum_capacity": 239999.0,
1378
+ "minimum_seasonal_efficiency": null,
1379
+ "minimum_full_load_efficiency": 9.3,
1380
+ "minimum_iplv": null,
1381
+ "minimum_integrated_energy_efficiency_ratio": null,
1382
+ "cool_cap_ft": "HPACCoolCapFT",
1383
+ "cool_cap_fflow": "HPACCoolCapFFF",
1384
+ "cool_eir_ft": "HPACCOOLEIRFT",
1385
+ "cool_eir_fflow": "HPACCOOLEIRFFF",
1386
+ "cool_plf_fplr": "HPACCOOLPLFFPLR",
1387
+ "notes": "From 90.1-2007 Table 6.8.1B, Before 1/1/2010"
1388
+ },
1389
+ {
1390
+ "template": "90.1-2007",
1391
+ "cooling_type": "AirCooled",
1392
+ "heating_type": "All Other",
1393
+ "subcategory": "Split System",
1394
+ "minimum_capacity": 135000.0,
1395
+ "maximum_capacity": 239999.0,
1396
+ "minimum_seasonal_efficiency": null,
1397
+ "minimum_full_load_efficiency": 9.1,
1398
+ "minimum_iplv": null,
1399
+ "minimum_integrated_energy_efficiency_ratio": null,
1400
+ "cool_cap_ft": "HPACCoolCapFT",
1401
+ "cool_cap_fflow": "HPACCoolCapFFF",
1402
+ "cool_eir_ft": "HPACCOOLEIRFT",
1403
+ "cool_eir_fflow": "HPACCOOLEIRFFF",
1404
+ "cool_plf_fplr": "HPACCOOLPLFFPLR",
1405
+ "notes": "From 90.1-2007 Table 6.8.1B, Before 1/1/2010"
1406
+ },
1407
+ {
1408
+ "template": "90.1-2007",
1409
+ "cooling_type": "AirCooled",
1410
+ "heating_type": "All Other",
1411
+ "subcategory": "Single Package",
1412
+ "minimum_capacity": 135000.0,
1413
+ "maximum_capacity": 239999.0,
1414
+ "minimum_seasonal_efficiency": null,
1415
+ "minimum_full_load_efficiency": 9.1,
1416
+ "minimum_iplv": null,
1417
+ "minimum_integrated_energy_efficiency_ratio": null,
1418
+ "cool_cap_ft": "HPACCoolCapFT",
1419
+ "cool_cap_fflow": "HPACCoolCapFFF",
1420
+ "cool_eir_ft": "HPACCOOLEIRFT",
1421
+ "cool_eir_fflow": "HPACCOOLEIRFFF",
1422
+ "cool_plf_fplr": "HPACCOOLPLFFPLR",
1423
+ "notes": "From 90.1-2007 Table 6.8.1B, Before 1/1/2010"
1424
+ },
1425
+ {
1426
+ "template": "90.1-2007",
1427
+ "cooling_type": "AirCooled",
1428
+ "heating_type": "Electric Resistance or None",
1429
+ "subcategory": "Split System",
1430
+ "minimum_capacity": 240000.0,
1431
+ "maximum_capacity": 9999999.0,
1432
+ "minimum_seasonal_efficiency": null,
1433
+ "minimum_full_load_efficiency": 9.0,
1434
+ "minimum_iplv": 9.2,
1435
+ "minimum_integrated_energy_efficiency_ratio": null,
1436
+ "cool_cap_ft": "HPACCoolCapFT",
1437
+ "cool_cap_fflow": "HPACCoolCapFFF",
1438
+ "cool_eir_ft": "HPACCOOLEIRFT",
1439
+ "cool_eir_fflow": "HPACCOOLEIRFFF",
1440
+ "cool_plf_fplr": "HPACCOOLPLFFPLR",
1441
+ "notes": "From 90.1-2007 Table 6.8.1B, Before 1/1/2010"
1442
+ },
1443
+ {
1444
+ "template": "90.1-2007",
1445
+ "cooling_type": "AirCooled",
1446
+ "heating_type": "Electric Resistance or None",
1447
+ "subcategory": "Single Package",
1448
+ "minimum_capacity": 240000.0,
1449
+ "maximum_capacity": 9999999.0,
1450
+ "minimum_seasonal_efficiency": null,
1451
+ "minimum_full_load_efficiency": 9.0,
1452
+ "minimum_iplv": 9.2,
1453
+ "minimum_integrated_energy_efficiency_ratio": null,
1454
+ "cool_cap_ft": "HPACCoolCapFT",
1455
+ "cool_cap_fflow": "HPACCoolCapFFF",
1456
+ "cool_eir_ft": "HPACCOOLEIRFT",
1457
+ "cool_eir_fflow": "HPACCOOLEIRFFF",
1458
+ "cool_plf_fplr": "HPACCOOLPLFFPLR",
1459
+ "notes": "From 90.1-2007 Table 6.8.1B, Before 1/1/2010"
1460
+ },
1461
+ {
1462
+ "template": "90.1-2007",
1463
+ "cooling_type": "AirCooled",
1464
+ "heating_type": "All Other",
1465
+ "subcategory": "Split System",
1466
+ "minimum_capacity": 240000.0,
1467
+ "maximum_capacity": 9999999.0,
1468
+ "minimum_seasonal_efficiency": null,
1469
+ "minimum_full_load_efficiency": 8.8,
1470
+ "minimum_iplv": 9.0,
1471
+ "minimum_integrated_energy_efficiency_ratio": null,
1472
+ "cool_cap_ft": "HPACCoolCapFT",
1473
+ "cool_cap_fflow": "HPACCoolCapFFF",
1474
+ "cool_eir_ft": "HPACCOOLEIRFT",
1475
+ "cool_eir_fflow": "HPACCOOLEIRFFF",
1476
+ "cool_plf_fplr": "HPACCOOLPLFFPLR",
1477
+ "notes": "From 90.1-2007 Table 6.8.1B, Before 1/1/2010"
1478
+ },
1479
+ {
1480
+ "template": "90.1-2007",
1481
+ "cooling_type": "AirCooled",
1482
+ "heating_type": "All Other",
1483
+ "subcategory": "Single Package",
1484
+ "minimum_capacity": 240000.0,
1485
+ "maximum_capacity": 9999999.0,
1486
+ "minimum_seasonal_efficiency": null,
1487
+ "minimum_full_load_efficiency": 8.8,
1488
+ "minimum_iplv": 9.0,
1489
+ "minimum_integrated_energy_efficiency_ratio": null,
1490
+ "cool_cap_ft": "HPACCoolCapFT",
1491
+ "cool_cap_fflow": "HPACCoolCapFFF",
1492
+ "cool_eir_ft": "HPACCOOLEIRFT",
1493
+ "cool_eir_fflow": "HPACCOOLEIRFFF",
1494
+ "cool_plf_fplr": "HPACCOOLPLFFPLR",
1495
+ "notes": "From 90.1-2007 Table 6.8.1B, Before 1/1/2010"
1496
+ },
1497
+ {
1498
+ "template": "90.1-2010",
1499
+ "cooling_type": "AirCooled",
1500
+ "heating_type": null,
1501
+ "subcategory": "Split System",
1502
+ "minimum_capacity": 0.0,
1503
+ "maximum_capacity": 64999.0,
1504
+ "minimum_seasonal_efficiency": 13.0,
1505
+ "minimum_full_load_efficiency": null,
1506
+ "minimum_iplv": null,
1507
+ "minimum_integrated_energy_efficiency_ratio": null,
1508
+ "cool_cap_ft": "HPACCoolCapFT",
1509
+ "cool_cap_fflow": "HPACCoolCapFFF",
1510
+ "cool_eir_ft": "HPACCOOLEIRFT",
1511
+ "cool_eir_fflow": "HPACCOOLEIRFFF",
1512
+ "cool_plf_fplr": "HPACCOOLPLFFPLR",
1513
+ "notes": "From 90.1-2010 Table 6.8.1B"
1514
+ },
1515
+ {
1516
+ "template": "90.1-2010",
1517
+ "cooling_type": "AirCooled",
1518
+ "heating_type": null,
1519
+ "subcategory": "Single Package",
1520
+ "minimum_capacity": 0.0,
1521
+ "maximum_capacity": 64999.0,
1522
+ "minimum_seasonal_efficiency": 13.0,
1523
+ "minimum_full_load_efficiency": null,
1524
+ "minimum_iplv": null,
1525
+ "minimum_integrated_energy_efficiency_ratio": null,
1526
+ "cool_cap_ft": "HPACCoolCapFT",
1527
+ "cool_cap_fflow": "HPACCoolCapFFF",
1528
+ "cool_eir_ft": "HPACCOOLEIRFT",
1529
+ "cool_eir_fflow": "HPACCOOLEIRFFF",
1530
+ "cool_plf_fplr": "HPACCOOLPLFFPLR",
1531
+ "notes": "From 90.1-2010 Table 6.8.1B"
1532
+ },
1533
+ {
1534
+ "template": "90.1-2010",
1535
+ "cooling_type": "ThroughWall",
1536
+ "heating_type": null,
1537
+ "subcategory": "Split System",
1538
+ "minimum_capacity": 0.0,
1539
+ "maximum_capacity": 29999.0,
1540
+ "minimum_seasonal_efficiency": 12.0,
1541
+ "minimum_full_load_efficiency": null,
1542
+ "minimum_iplv": null,
1543
+ "minimum_integrated_energy_efficiency_ratio": null,
1544
+ "cool_cap_ft": "HPACCoolCapFT",
1545
+ "cool_cap_fflow": "HPACCoolCapFFF",
1546
+ "cool_eir_ft": "HPACCOOLEIRFT",
1547
+ "cool_eir_fflow": "HPACCOOLEIRFFF",
1548
+ "cool_plf_fplr": "HPACCOOLPLFFPLR",
1549
+ "notes": "From 90.1-2010 Table 6.8.1B"
1550
+ },
1551
+ {
1552
+ "template": "90.1-2010",
1553
+ "cooling_type": "ThroughWall",
1554
+ "heating_type": null,
1555
+ "subcategory": "Single Package",
1556
+ "minimum_capacity": 0.0,
1557
+ "maximum_capacity": 29999.0,
1558
+ "minimum_seasonal_efficiency": 12.0,
1559
+ "minimum_full_load_efficiency": null,
1560
+ "minimum_iplv": null,
1561
+ "minimum_integrated_energy_efficiency_ratio": null,
1562
+ "cool_cap_ft": "HPACCoolCapFT",
1563
+ "cool_cap_fflow": "HPACCoolCapFFF",
1564
+ "cool_eir_ft": "HPACCOOLEIRFT",
1565
+ "cool_eir_fflow": "HPACCOOLEIRFFF",
1566
+ "cool_plf_fplr": "HPACCOOLPLFFPLR",
1567
+ "notes": "From 90.1-2010 Table 6.8.1B"
1568
+ },
1569
+ {
1570
+ "template": "90.1-2010",
1571
+ "cooling_type": "AirCooled",
1572
+ "heating_type": "Electric Resistance or None",
1573
+ "subcategory": "Split System",
1574
+ "minimum_capacity": 65000.0,
1575
+ "maximum_capacity": 134999.0,
1576
+ "minimum_seasonal_efficiency": null,
1577
+ "minimum_full_load_efficiency": 11.0,
1578
+ "minimum_iplv": null,
1579
+ "minimum_integrated_energy_efficiency_ratio": 11.2,
1580
+ "cool_cap_ft": "HPACCoolCapFT",
1581
+ "cool_cap_fflow": "HPACCoolCapFFF",
1582
+ "cool_eir_ft": "HPACCOOLEIRFT",
1583
+ "cool_eir_fflow": "HPACCOOLEIRFFF",
1584
+ "cool_plf_fplr": "HPACCOOLPLFFPLR",
1585
+ "notes": "From 90.1-2010 Table 6.8.1B"
1586
+ },
1587
+ {
1588
+ "template": "90.1-2010",
1589
+ "cooling_type": "AirCooled",
1590
+ "heating_type": "Electric Resistance or None",
1591
+ "subcategory": "Single Package",
1592
+ "minimum_capacity": 65000.0,
1593
+ "maximum_capacity": 134999.0,
1594
+ "minimum_seasonal_efficiency": null,
1595
+ "minimum_full_load_efficiency": 11.0,
1596
+ "minimum_iplv": null,
1597
+ "minimum_integrated_energy_efficiency_ratio": 11.2,
1598
+ "cool_cap_ft": "HPACCoolCapFT",
1599
+ "cool_cap_fflow": "HPACCoolCapFFF",
1600
+ "cool_eir_ft": "HPACCOOLEIRFT",
1601
+ "cool_eir_fflow": "HPACCOOLEIRFFF",
1602
+ "cool_plf_fplr": "HPACCOOLPLFFPLR",
1603
+ "notes": "From 90.1-2010 Table 6.8.1B"
1604
+ },
1605
+ {
1606
+ "template": "90.1-2010",
1607
+ "cooling_type": "AirCooled",
1608
+ "heating_type": "All Other",
1609
+ "subcategory": "Split System",
1610
+ "minimum_capacity": 65000.0,
1611
+ "maximum_capacity": 134999.0,
1612
+ "minimum_seasonal_efficiency": null,
1613
+ "minimum_full_load_efficiency": 10.8,
1614
+ "minimum_iplv": null,
1615
+ "minimum_integrated_energy_efficiency_ratio": 11.0,
1616
+ "cool_cap_ft": "HPACCoolCapFT",
1617
+ "cool_cap_fflow": "HPACCoolCapFFF",
1618
+ "cool_eir_ft": "HPACCOOLEIRFT",
1619
+ "cool_eir_fflow": "HPACCOOLEIRFFF",
1620
+ "cool_plf_fplr": "HPACCOOLPLFFPLR",
1621
+ "notes": "From 90.1-2010 Table 6.8.1B"
1622
+ },
1623
+ {
1624
+ "template": "90.1-2010",
1625
+ "cooling_type": "AirCooled",
1626
+ "heating_type": "All Other",
1627
+ "subcategory": "Single Package",
1628
+ "minimum_capacity": 65000.0,
1629
+ "maximum_capacity": 134999.0,
1630
+ "minimum_seasonal_efficiency": null,
1631
+ "minimum_full_load_efficiency": 10.8,
1632
+ "minimum_iplv": null,
1633
+ "minimum_integrated_energy_efficiency_ratio": 11.0,
1634
+ "cool_cap_ft": "HPACCoolCapFT",
1635
+ "cool_cap_fflow": "HPACCoolCapFFF",
1636
+ "cool_eir_ft": "HPACCOOLEIRFT",
1637
+ "cool_eir_fflow": "HPACCOOLEIRFFF",
1638
+ "cool_plf_fplr": "HPACCOOLPLFFPLR",
1639
+ "notes": "From 90.1-2010 Table 6.8.1B"
1640
+ },
1641
+ {
1642
+ "template": "90.1-2010",
1643
+ "cooling_type": "AirCooled",
1644
+ "heating_type": "Electric Resistance or None",
1645
+ "subcategory": "Split System",
1646
+ "minimum_capacity": 135000.0,
1647
+ "maximum_capacity": 239999.0,
1648
+ "minimum_seasonal_efficiency": null,
1649
+ "minimum_full_load_efficiency": 10.6,
1650
+ "minimum_iplv": null,
1651
+ "minimum_integrated_energy_efficiency_ratio": 10.7,
1652
+ "cool_cap_ft": "HPACCoolCapFT",
1653
+ "cool_cap_fflow": "HPACCoolCapFFF",
1654
+ "cool_eir_ft": "HPACCOOLEIRFT",
1655
+ "cool_eir_fflow": "HPACCOOLEIRFFF",
1656
+ "cool_plf_fplr": "HPACCOOLPLFFPLR",
1657
+ "notes": "From 90.1-2010 Table 6.8.1B"
1658
+ },
1659
+ {
1660
+ "template": "90.1-2010",
1661
+ "cooling_type": "AirCooled",
1662
+ "heating_type": "Electric Resistance or None",
1663
+ "subcategory": "Single Package",
1664
+ "minimum_capacity": 135000.0,
1665
+ "maximum_capacity": 239999.0,
1666
+ "minimum_seasonal_efficiency": null,
1667
+ "minimum_full_load_efficiency": 10.6,
1668
+ "minimum_iplv": null,
1669
+ "minimum_integrated_energy_efficiency_ratio": 10.7,
1670
+ "cool_cap_ft": "HPACCoolCapFT",
1671
+ "cool_cap_fflow": "HPACCoolCapFFF",
1672
+ "cool_eir_ft": "HPACCOOLEIRFT",
1673
+ "cool_eir_fflow": "HPACCOOLEIRFFF",
1674
+ "cool_plf_fplr": "HPACCOOLPLFFPLR",
1675
+ "notes": "From 90.1-2010 Table 6.8.1B"
1676
+ },
1677
+ {
1678
+ "template": "90.1-2010",
1679
+ "cooling_type": "AirCooled",
1680
+ "heating_type": "All Other",
1681
+ "subcategory": "Split System",
1682
+ "minimum_capacity": 135000.0,
1683
+ "maximum_capacity": 239999.0,
1684
+ "minimum_seasonal_efficiency": null,
1685
+ "minimum_full_load_efficiency": 10.4,
1686
+ "minimum_iplv": null,
1687
+ "minimum_integrated_energy_efficiency_ratio": 10.5,
1688
+ "cool_cap_ft": "HPACCoolCapFT",
1689
+ "cool_cap_fflow": "HPACCoolCapFFF",
1690
+ "cool_eir_ft": "HPACCOOLEIRFT",
1691
+ "cool_eir_fflow": "HPACCOOLEIRFFF",
1692
+ "cool_plf_fplr": "HPACCOOLPLFFPLR",
1693
+ "notes": "From 90.1-2010 Table 6.8.1B"
1694
+ },
1695
+ {
1696
+ "template": "90.1-2010",
1697
+ "cooling_type": "AirCooled",
1698
+ "heating_type": "All Other",
1699
+ "subcategory": "Single Package",
1700
+ "minimum_capacity": 135000.0,
1701
+ "maximum_capacity": 239999.0,
1702
+ "minimum_seasonal_efficiency": null,
1703
+ "minimum_full_load_efficiency": 10.4,
1704
+ "minimum_iplv": null,
1705
+ "minimum_integrated_energy_efficiency_ratio": 10.5,
1706
+ "cool_cap_ft": "HPACCoolCapFT",
1707
+ "cool_cap_fflow": "HPACCoolCapFFF",
1708
+ "cool_eir_ft": "HPACCOOLEIRFT",
1709
+ "cool_eir_fflow": "HPACCOOLEIRFFF",
1710
+ "cool_plf_fplr": "HPACCOOLPLFFPLR",
1711
+ "notes": "From 90.1-2010 Table 6.8.1B"
1712
+ },
1713
+ {
1714
+ "template": "90.1-2010",
1715
+ "cooling_type": "AirCooled",
1716
+ "heating_type": "Electric Resistance or None",
1717
+ "subcategory": "Split System",
1718
+ "minimum_capacity": 240000.0,
1719
+ "maximum_capacity": 9999999.0,
1720
+ "minimum_seasonal_efficiency": null,
1721
+ "minimum_full_load_efficiency": 9.5,
1722
+ "minimum_iplv": null,
1723
+ "minimum_integrated_energy_efficiency_ratio": 9.6,
1724
+ "cool_cap_ft": "HPACCoolCapFT",
1725
+ "cool_cap_fflow": "HPACCoolCapFFF",
1726
+ "cool_eir_ft": "HPACCOOLEIRFT",
1727
+ "cool_eir_fflow": "HPACCOOLEIRFFF",
1728
+ "cool_plf_fplr": "HPACCOOLPLFFPLR",
1729
+ "notes": "From 90.1-2010 Table 6.8.1B"
1730
+ },
1731
+ {
1732
+ "template": "90.1-2010",
1733
+ "cooling_type": "AirCooled",
1734
+ "heating_type": "Electric Resistance or None",
1735
+ "subcategory": "Single Package",
1736
+ "minimum_capacity": 240000.0,
1737
+ "maximum_capacity": 9999999.0,
1738
+ "minimum_seasonal_efficiency": null,
1739
+ "minimum_full_load_efficiency": 9.5,
1740
+ "minimum_iplv": null,
1741
+ "minimum_integrated_energy_efficiency_ratio": 9.6,
1742
+ "cool_cap_ft": "HPACCoolCapFT",
1743
+ "cool_cap_fflow": "HPACCoolCapFFF",
1744
+ "cool_eir_ft": "HPACCOOLEIRFT",
1745
+ "cool_eir_fflow": "HPACCOOLEIRFFF",
1746
+ "cool_plf_fplr": "HPACCOOLPLFFPLR",
1747
+ "notes": "From 90.1-2010 Table 6.8.1B"
1748
+ },
1749
+ {
1750
+ "template": "90.1-2010",
1751
+ "cooling_type": "AirCooled",
1752
+ "heating_type": "All Other",
1753
+ "subcategory": "Split System",
1754
+ "minimum_capacity": 240000.0,
1755
+ "maximum_capacity": 9999999.0,
1756
+ "minimum_seasonal_efficiency": null,
1757
+ "minimum_full_load_efficiency": 9.3,
1758
+ "minimum_iplv": null,
1759
+ "minimum_integrated_energy_efficiency_ratio": 9.4,
1760
+ "cool_cap_ft": "HPACCoolCapFT",
1761
+ "cool_cap_fflow": "HPACCoolCapFFF",
1762
+ "cool_eir_ft": "HPACCOOLEIRFT",
1763
+ "cool_eir_fflow": "HPACCOOLEIRFFF",
1764
+ "cool_plf_fplr": "HPACCOOLPLFFPLR",
1765
+ "notes": "From 90.1-2010 Table 6.8.1B"
1766
+ },
1767
+ {
1768
+ "template": "90.1-2010",
1769
+ "cooling_type": "AirCooled",
1770
+ "heating_type": "All Other",
1771
+ "subcategory": "Single Package",
1772
+ "minimum_capacity": 240000.0,
1773
+ "maximum_capacity": 9999999.0,
1774
+ "minimum_seasonal_efficiency": null,
1775
+ "minimum_full_load_efficiency": 9.3,
1776
+ "minimum_iplv": null,
1777
+ "minimum_integrated_energy_efficiency_ratio": 9.4,
1778
+ "cool_cap_ft": "HPACCoolCapFT",
1779
+ "cool_cap_fflow": "HPACCoolCapFFF",
1780
+ "cool_eir_ft": "HPACCOOLEIRFT",
1781
+ "cool_eir_fflow": "HPACCOOLEIRFFF",
1782
+ "cool_plf_fplr": "HPACCOOLPLFFPLR",
1783
+ "notes": "From 90.1-2010 Table 6.8.1B"
1784
+ },
1785
+ {
1786
+ "template": "90.1-2013",
1787
+ "cooling_type": "AirCooled",
1788
+ "heating_type": null,
1789
+ "subcategory": "Split System",
1790
+ "minimum_capacity": 0.0,
1791
+ "maximum_capacity": 64999.0,
1792
+ "minimum_seasonal_efficiency": 13.0,
1793
+ "minimum_full_load_efficiency": null,
1794
+ "minimum_iplv": null,
1795
+ "minimum_integrated_energy_efficiency_ratio": null,
1796
+ "cool_cap_ft": "HPACCoolCapFT",
1797
+ "cool_cap_fflow": "HPACCoolCapFFF",
1798
+ "cool_eir_ft": "HPACCOOLEIRFT",
1799
+ "cool_eir_fflow": "HPACCOOLEIRFFF",
1800
+ "cool_plf_fplr": "HPACCOOLPLFFPLR",
1801
+ "notes": "From 90.1-2010 Table 6.8.1-2 Before 1/1/2015"
1802
+ },
1803
+ {
1804
+ "template": "90.1-2013",
1805
+ "cooling_type": "AirCooled",
1806
+ "heating_type": null,
1807
+ "subcategory": "Single Package",
1808
+ "minimum_capacity": 0.0,
1809
+ "maximum_capacity": 64999.0,
1810
+ "minimum_seasonal_efficiency": 13.0,
1811
+ "minimum_full_load_efficiency": null,
1812
+ "minimum_iplv": null,
1813
+ "minimum_integrated_energy_efficiency_ratio": null,
1814
+ "cool_cap_ft": "HPACCoolCapFT",
1815
+ "cool_cap_fflow": "HPACCoolCapFFF",
1816
+ "cool_eir_ft": "HPACCOOLEIRFT",
1817
+ "cool_eir_fflow": "HPACCOOLEIRFFF",
1818
+ "cool_plf_fplr": "HPACCOOLPLFFPLR",
1819
+ "notes": "From 90.1-2010 Table 6.8.1-2 Before 1/1/2015"
1820
+ },
1821
+ {
1822
+ "template": "90.1-2013",
1823
+ "cooling_type": "ThroughWall",
1824
+ "heating_type": null,
1825
+ "subcategory": "Split System",
1826
+ "minimum_capacity": 0.0,
1827
+ "maximum_capacity": 29999.0,
1828
+ "minimum_seasonal_efficiency": 12.0,
1829
+ "minimum_full_load_efficiency": null,
1830
+ "minimum_iplv": null,
1831
+ "minimum_integrated_energy_efficiency_ratio": null,
1832
+ "cool_cap_ft": "HPACCoolCapFT",
1833
+ "cool_cap_fflow": "HPACCoolCapFFF",
1834
+ "cool_eir_ft": "HPACCOOLEIRFT",
1835
+ "cool_eir_fflow": "HPACCOOLEIRFFF",
1836
+ "cool_plf_fplr": "HPACCOOLPLFFPLR",
1837
+ "notes": "From 90.1-2010 Table 6.8.1-2"
1838
+ },
1839
+ {
1840
+ "template": "90.1-2013",
1841
+ "cooling_type": "ThroughWall",
1842
+ "heating_type": null,
1843
+ "subcategory": "Single Package",
1844
+ "minimum_capacity": 0.0,
1845
+ "maximum_capacity": 29999.0,
1846
+ "minimum_seasonal_efficiency": 12.0,
1847
+ "minimum_full_load_efficiency": null,
1848
+ "minimum_iplv": null,
1849
+ "minimum_integrated_energy_efficiency_ratio": null,
1850
+ "cool_cap_ft": "HPACCoolCapFT",
1851
+ "cool_cap_fflow": "HPACCoolCapFFF",
1852
+ "cool_eir_ft": "HPACCOOLEIRFT",
1853
+ "cool_eir_fflow": "HPACCOOLEIRFFF",
1854
+ "cool_plf_fplr": "HPACCOOLPLFFPLR",
1855
+ "notes": "From 90.1-2010 Table 6.8.1-2"
1856
+ },
1857
+ {
1858
+ "template": "90.1-2013",
1859
+ "cooling_type": "SmallDuctHighVelocity",
1860
+ "heating_type": null,
1861
+ "subcategory": "Split System",
1862
+ "minimum_capacity": 0.0,
1863
+ "maximum_capacity": 64999.0,
1864
+ "minimum_seasonal_efficiency": 11.0,
1865
+ "minimum_full_load_efficiency": null,
1866
+ "minimum_iplv": null,
1867
+ "minimum_integrated_energy_efficiency_ratio": null,
1868
+ "cool_cap_ft": "HPACCoolCapFT",
1869
+ "cool_cap_fflow": "HPACCoolCapFFF",
1870
+ "cool_eir_ft": "HPACCOOLEIRFT",
1871
+ "cool_eir_fflow": "HPACCOOLEIRFFF",
1872
+ "cool_plf_fplr": "HPACCOOLPLFFPLR",
1873
+ "notes": "From 90.1-2010 Table 6.8.1-2 Before 1/1/2016"
1874
+ },
1875
+ {
1876
+ "template": "90.1-2013",
1877
+ "cooling_type": "AirCooled",
1878
+ "heating_type": "Electric Resistance or None",
1879
+ "subcategory": "Split System",
1880
+ "minimum_capacity": 65000.0,
1881
+ "maximum_capacity": 134999.0,
1882
+ "minimum_seasonal_efficiency": null,
1883
+ "minimum_full_load_efficiency": 11.0,
1884
+ "minimum_iplv": null,
1885
+ "minimum_integrated_energy_efficiency_ratio": 11.2,
1886
+ "cool_cap_ft": "HPACCoolCapFT",
1887
+ "cool_cap_fflow": "HPACCoolCapFFF",
1888
+ "cool_eir_ft": "HPACCOOLEIRFT",
1889
+ "cool_eir_fflow": "HPACCOOLEIRFFF",
1890
+ "cool_plf_fplr": "HPACCOOLPLFFPLR",
1891
+ "notes": "From 90.1-2010 Table 6.8.1-2 Before 1/1/2016"
1892
+ },
1893
+ {
1894
+ "template": "90.1-2013",
1895
+ "cooling_type": "AirCooled",
1896
+ "heating_type": "Electric Resistance or None",
1897
+ "subcategory": "Single Package",
1898
+ "minimum_capacity": 65000.0,
1899
+ "maximum_capacity": 134999.0,
1900
+ "minimum_seasonal_efficiency": null,
1901
+ "minimum_full_load_efficiency": 11.0,
1902
+ "minimum_iplv": null,
1903
+ "minimum_integrated_energy_efficiency_ratio": 11.2,
1904
+ "cool_cap_ft": "HPACCoolCapFT",
1905
+ "cool_cap_fflow": "HPACCoolCapFFF",
1906
+ "cool_eir_ft": "HPACCOOLEIRFT",
1907
+ "cool_eir_fflow": "HPACCOOLEIRFFF",
1908
+ "cool_plf_fplr": "HPACCOOLPLFFPLR",
1909
+ "notes": "From 90.1-2010 Table 6.8.1-2 Before 1/1/2016"
1910
+ },
1911
+ {
1912
+ "template": "90.1-2013",
1913
+ "cooling_type": "AirCooled",
1914
+ "heating_type": "All Other",
1915
+ "subcategory": "Split System",
1916
+ "minimum_capacity": 65000.0,
1917
+ "maximum_capacity": 134999.0,
1918
+ "minimum_seasonal_efficiency": null,
1919
+ "minimum_full_load_efficiency": 10.8,
1920
+ "minimum_iplv": null,
1921
+ "minimum_integrated_energy_efficiency_ratio": 11.0,
1922
+ "cool_cap_ft": "HPACCoolCapFT",
1923
+ "cool_cap_fflow": "HPACCoolCapFFF",
1924
+ "cool_eir_ft": "HPACCOOLEIRFT",
1925
+ "cool_eir_fflow": "HPACCOOLEIRFFF",
1926
+ "cool_plf_fplr": "HPACCOOLPLFFPLR",
1927
+ "notes": "From 90.1-2010 Table 6.8.1-2 Before 1/1/2016"
1928
+ },
1929
+ {
1930
+ "template": "90.1-2013",
1931
+ "cooling_type": "AirCooled",
1932
+ "heating_type": "All Other",
1933
+ "subcategory": "Single Package",
1934
+ "minimum_capacity": 65000.0,
1935
+ "maximum_capacity": 134999.0,
1936
+ "minimum_seasonal_efficiency": null,
1937
+ "minimum_full_load_efficiency": 10.8,
1938
+ "minimum_iplv": null,
1939
+ "minimum_integrated_energy_efficiency_ratio": 11.0,
1940
+ "cool_cap_ft": "HPACCoolCapFT",
1941
+ "cool_cap_fflow": "HPACCoolCapFFF",
1942
+ "cool_eir_ft": "HPACCOOLEIRFT",
1943
+ "cool_eir_fflow": "HPACCOOLEIRFFF",
1944
+ "cool_plf_fplr": "HPACCOOLPLFFPLR",
1945
+ "notes": "From 90.1-2010 Table 6.8.1-2 Before 1/1/2016"
1946
+ },
1947
+ {
1948
+ "template": "90.1-2013",
1949
+ "cooling_type": "AirCooled",
1950
+ "heating_type": "Electric Resistance or None",
1951
+ "subcategory": "Split System",
1952
+ "minimum_capacity": 135000.0,
1953
+ "maximum_capacity": 239999.0,
1954
+ "minimum_seasonal_efficiency": null,
1955
+ "minimum_full_load_efficiency": 10.6,
1956
+ "minimum_iplv": null,
1957
+ "minimum_integrated_energy_efficiency_ratio": 10.7,
1958
+ "cool_cap_ft": "HPACCoolCapFT",
1959
+ "cool_cap_fflow": "HPACCoolCapFFF",
1960
+ "cool_eir_ft": "HPACCOOLEIRFT",
1961
+ "cool_eir_fflow": "HPACCOOLEIRFFF",
1962
+ "cool_plf_fplr": "HPACCOOLPLFFPLR",
1963
+ "notes": "From 90.1-2010 Table 6.8.1-2 Before 1/1/2016"
1964
+ },
1965
+ {
1966
+ "template": "90.1-2013",
1967
+ "cooling_type": "AirCooled",
1968
+ "heating_type": "Electric Resistance or None",
1969
+ "subcategory": "Single Package",
1970
+ "minimum_capacity": 135000.0,
1971
+ "maximum_capacity": 239999.0,
1972
+ "minimum_seasonal_efficiency": null,
1973
+ "minimum_full_load_efficiency": 10.6,
1974
+ "minimum_iplv": null,
1975
+ "minimum_integrated_energy_efficiency_ratio": 10.7,
1976
+ "cool_cap_ft": "HPACCoolCapFT",
1977
+ "cool_cap_fflow": "HPACCoolCapFFF",
1978
+ "cool_eir_ft": "HPACCOOLEIRFT",
1979
+ "cool_eir_fflow": "HPACCOOLEIRFFF",
1980
+ "cool_plf_fplr": "HPACCOOLPLFFPLR",
1981
+ "notes": "From 90.1-2010 Table 6.8.1-2 Before 1/1/2016"
1982
+ },
1983
+ {
1984
+ "template": "90.1-2013",
1985
+ "cooling_type": "AirCooled",
1986
+ "heating_type": "All Other",
1987
+ "subcategory": "Split System",
1988
+ "minimum_capacity": 135000.0,
1989
+ "maximum_capacity": 239999.0,
1990
+ "minimum_seasonal_efficiency": null,
1991
+ "minimum_full_load_efficiency": 10.4,
1992
+ "minimum_iplv": null,
1993
+ "minimum_integrated_energy_efficiency_ratio": 10.5,
1994
+ "cool_cap_ft": "HPACCoolCapFT",
1995
+ "cool_cap_fflow": "HPACCoolCapFFF",
1996
+ "cool_eir_ft": "HPACCOOLEIRFT",
1997
+ "cool_eir_fflow": "HPACCOOLEIRFFF",
1998
+ "cool_plf_fplr": "HPACCOOLPLFFPLR",
1999
+ "notes": "From 90.1-2010 Table 6.8.1-2 Before 1/1/2016"
2000
+ },
2001
+ {
2002
+ "template": "90.1-2013",
2003
+ "cooling_type": "AirCooled",
2004
+ "heating_type": "All Other",
2005
+ "subcategory": "Single Package",
2006
+ "minimum_capacity": 135000.0,
2007
+ "maximum_capacity": 239999.0,
2008
+ "minimum_seasonal_efficiency": null,
2009
+ "minimum_full_load_efficiency": 10.4,
2010
+ "minimum_iplv": null,
2011
+ "minimum_integrated_energy_efficiency_ratio": 10.5,
2012
+ "cool_cap_ft": "HPACCoolCapFT",
2013
+ "cool_cap_fflow": "HPACCoolCapFFF",
2014
+ "cool_eir_ft": "HPACCOOLEIRFT",
2015
+ "cool_eir_fflow": "HPACCOOLEIRFFF",
2016
+ "cool_plf_fplr": "HPACCOOLPLFFPLR",
2017
+ "notes": "From 90.1-2010 Table 6.8.1-2 Before 1/1/2016"
2018
+ },
2019
+ {
2020
+ "template": "90.1-2013",
2021
+ "cooling_type": "AirCooled",
2022
+ "heating_type": "Electric Resistance or None",
2023
+ "subcategory": "Split System",
2024
+ "minimum_capacity": 240000.0,
2025
+ "maximum_capacity": 9999999.0,
2026
+ "minimum_seasonal_efficiency": null,
2027
+ "minimum_full_load_efficiency": 9.5,
2028
+ "minimum_iplv": null,
2029
+ "minimum_integrated_energy_efficiency_ratio": 9.6,
2030
+ "cool_cap_ft": "HPACCoolCapFT",
2031
+ "cool_cap_fflow": "HPACCoolCapFFF",
2032
+ "cool_eir_ft": "HPACCOOLEIRFT",
2033
+ "cool_eir_fflow": "HPACCOOLEIRFFF",
2034
+ "cool_plf_fplr": "HPACCOOLPLFFPLR",
2035
+ "notes": "From 90.1-2010 Table 6.8.1-2 Before 1/1/2016"
2036
+ },
2037
+ {
2038
+ "template": "90.1-2013",
2039
+ "cooling_type": "AirCooled",
2040
+ "heating_type": "Electric Resistance or None",
2041
+ "subcategory": "Single Package",
2042
+ "minimum_capacity": 240000.0,
2043
+ "maximum_capacity": 9999999.0,
2044
+ "minimum_seasonal_efficiency": null,
2045
+ "minimum_full_load_efficiency": 9.5,
2046
+ "minimum_iplv": null,
2047
+ "minimum_integrated_energy_efficiency_ratio": 9.6,
2048
+ "cool_cap_ft": "HPACCoolCapFT",
2049
+ "cool_cap_fflow": "HPACCoolCapFFF",
2050
+ "cool_eir_ft": "HPACCOOLEIRFT",
2051
+ "cool_eir_fflow": "HPACCOOLEIRFFF",
2052
+ "cool_plf_fplr": "HPACCOOLPLFFPLR",
2053
+ "notes": "From 90.1-2010 Table 6.8.1-2 Before 1/1/2016"
2054
+ },
2055
+ {
2056
+ "template": "90.1-2013",
2057
+ "cooling_type": "AirCooled",
2058
+ "heating_type": "All Other",
2059
+ "subcategory": "Split System",
2060
+ "minimum_capacity": 240000.0,
2061
+ "maximum_capacity": 9999999.0,
2062
+ "minimum_seasonal_efficiency": null,
2063
+ "minimum_full_load_efficiency": 9.3,
2064
+ "minimum_iplv": null,
2065
+ "minimum_integrated_energy_efficiency_ratio": 9.4,
2066
+ "cool_cap_ft": "HPACCoolCapFT",
2067
+ "cool_cap_fflow": "HPACCoolCapFFF",
2068
+ "cool_eir_ft": "HPACCOOLEIRFT",
2069
+ "cool_eir_fflow": "HPACCOOLEIRFFF",
2070
+ "cool_plf_fplr": "HPACCOOLPLFFPLR",
2071
+ "notes": "From 90.1-2010 Table 6.8.1-2 Before 1/1/2016"
2072
+ },
2073
+ {
2074
+ "template": "90.1-2013",
2075
+ "cooling_type": "AirCooled",
2076
+ "heating_type": "All Other",
2077
+ "subcategory": "Single Package",
2078
+ "minimum_capacity": 240000.0,
2079
+ "maximum_capacity": 9999999.0,
2080
+ "minimum_seasonal_efficiency": null,
2081
+ "minimum_full_load_efficiency": 9.3,
2082
+ "minimum_iplv": null,
2083
+ "minimum_integrated_energy_efficiency_ratio": 9.4,
2084
+ "cool_cap_ft": "HPACCoolCapFT",
2085
+ "cool_cap_fflow": "HPACCoolCapFFF",
2086
+ "cool_eir_ft": "HPACCOOLEIRFT",
2087
+ "cool_eir_fflow": "HPACCOOLEIRFFF",
2088
+ "cool_plf_fplr": "HPACCOOLPLFFPLR",
2089
+ "notes": "From 90.1-2010 Table 6.8.1-2 Before 1/1/2016"
2090
+ },
2091
+ {
2092
+ "template": "OEESC 2014",
2093
+ "cooling_type": "AirCooled",
2094
+ "heating_type": null,
2095
+ "subcategory": "Split System",
2096
+ "minimum_capacity": 0.0,
2097
+ "maximum_capacity": 64999.0,
2098
+ "minimum_seasonal_efficiency": 14.0,
2099
+ "minimum_full_load_efficiency": null,
2100
+ "minimum_iplv": null,
2101
+ "minimum_integrated_energy_efficiency_ratio": null,
2102
+ "cool_cap_ft": "HPACCoolCapFT",
2103
+ "cool_cap_fflow": "HPACCoolCapFFF",
2104
+ "cool_eir_ft": "HPACCOOLEIRFT",
2105
+ "cool_eir_fflow": "HPACCOOLEIRFFF",
2106
+ "cool_plf_fplr": "HPACCOOLPLFFPLR",
2107
+ "notes": "From OEESC 2014 Table 503.2.3(2) Before 1/1/2016"
2108
+ },
2109
+ {
2110
+ "template": "OEESC 2014",
2111
+ "cooling_type": "AirCooled",
2112
+ "heating_type": null,
2113
+ "subcategory": "Single Package",
2114
+ "minimum_capacity": 0.0,
2115
+ "maximum_capacity": 64999.0,
2116
+ "minimum_seasonal_efficiency": 14.0,
2117
+ "minimum_full_load_efficiency": null,
2118
+ "minimum_iplv": null,
2119
+ "minimum_integrated_energy_efficiency_ratio": null,
2120
+ "cool_cap_ft": "HPACCoolCapFT",
2121
+ "cool_cap_fflow": "HPACCoolCapFFF",
2122
+ "cool_eir_ft": "HPACCOOLEIRFT",
2123
+ "cool_eir_fflow": "HPACCOOLEIRFFF",
2124
+ "cool_plf_fplr": "HPACCOOLPLFFPLR",
2125
+ "notes": "From OEESC 2014 Table 503.2.3(2) Before 1/1/2016"
2126
+ },
2127
+ {
2128
+ "template": "OEESC 2014",
2129
+ "cooling_type": "ThroughWall",
2130
+ "heating_type": null,
2131
+ "subcategory": "Split System",
2132
+ "minimum_capacity": 0.0,
2133
+ "maximum_capacity": 29999.0,
2134
+ "minimum_seasonal_efficiency": 12.0,
2135
+ "minimum_full_load_efficiency": null,
2136
+ "minimum_iplv": null,
2137
+ "minimum_integrated_energy_efficiency_ratio": null,
2138
+ "cool_cap_ft": "HPACCoolCapFT",
2139
+ "cool_cap_fflow": "HPACCoolCapFFF",
2140
+ "cool_eir_ft": "HPACCOOLEIRFT",
2141
+ "cool_eir_fflow": "HPACCOOLEIRFFF",
2142
+ "cool_plf_fplr": "HPACCOOLPLFFPLR",
2143
+ "notes": "From OEESC 2014 Table 503.2.3(2) Before 1/1/2016"
2144
+ },
2145
+ {
2146
+ "template": "OEESC 2014",
2147
+ "cooling_type": "ThroughWall",
2148
+ "heating_type": null,
2149
+ "subcategory": "Single Package",
2150
+ "minimum_capacity": 0.0,
2151
+ "maximum_capacity": 29999.0,
2152
+ "minimum_seasonal_efficiency": 12.0,
2153
+ "minimum_full_load_efficiency": null,
2154
+ "minimum_iplv": null,
2155
+ "minimum_integrated_energy_efficiency_ratio": null,
2156
+ "cool_cap_ft": "HPACCoolCapFT",
2157
+ "cool_cap_fflow": "HPACCoolCapFFF",
2158
+ "cool_eir_ft": "HPACCOOLEIRFT",
2159
+ "cool_eir_fflow": "HPACCOOLEIRFFF",
2160
+ "cool_plf_fplr": "HPACCOOLPLFFPLR",
2161
+ "notes": "From OEESC 2014 Table 503.2.3(2) Before 1/1/2016"
2162
+ },
2163
+ {
2164
+ "template": "OEESC 2014",
2165
+ "cooling_type": "SmallDuctHighVelocity",
2166
+ "heating_type": null,
2167
+ "subcategory": "Split System",
2168
+ "minimum_capacity": 0.0,
2169
+ "maximum_capacity": 64999.0,
2170
+ "minimum_seasonal_efficiency": 11.0,
2171
+ "minimum_full_load_efficiency": null,
2172
+ "minimum_iplv": null,
2173
+ "minimum_integrated_energy_efficiency_ratio": null,
2174
+ "cool_cap_ft": "HPACCoolCapFT",
2175
+ "cool_cap_fflow": "HPACCoolCapFFF",
2176
+ "cool_eir_ft": "HPACCOOLEIRFT",
2177
+ "cool_eir_fflow": "HPACCOOLEIRFFF",
2178
+ "cool_plf_fplr": "HPACCOOLPLFFPLR",
2179
+ "notes": "From OEESC 2014 Table 503.2.3(2) Before 1/1/2016"
2180
+ },
2181
+ {
2182
+ "template": "OEESC 2014",
2183
+ "cooling_type": "AirCooled",
2184
+ "heating_type": "Electric Resistance or None",
2185
+ "subcategory": "Split System",
2186
+ "minimum_capacity": 65000.0,
2187
+ "maximum_capacity": 134999.0,
2188
+ "minimum_seasonal_efficiency": null,
2189
+ "minimum_full_load_efficiency": 11.0,
2190
+ "minimum_iplv": null,
2191
+ "minimum_integrated_energy_efficiency_ratio": 11.2,
2192
+ "cool_cap_ft": "HPACCoolCapFT",
2193
+ "cool_cap_fflow": "HPACCoolCapFFF",
2194
+ "cool_eir_ft": "HPACCOOLEIRFT",
2195
+ "cool_eir_fflow": "HPACCOOLEIRFFF",
2196
+ "cool_plf_fplr": "HPACCOOLPLFFPLR",
2197
+ "notes": "From OEESC 2014 Table 503.2.3(2) Before 1/1/2016"
2198
+ },
2199
+ {
2200
+ "template": "OEESC 2014",
2201
+ "cooling_type": "AirCooled",
2202
+ "heating_type": "Electric Resistance or None",
2203
+ "subcategory": "Single Package",
2204
+ "minimum_capacity": 65000.0,
2205
+ "maximum_capacity": 134999.0,
2206
+ "minimum_seasonal_efficiency": null,
2207
+ "minimum_full_load_efficiency": 11.0,
2208
+ "minimum_iplv": null,
2209
+ "minimum_integrated_energy_efficiency_ratio": 11.2,
2210
+ "cool_cap_ft": "HPACCoolCapFT",
2211
+ "cool_cap_fflow": "HPACCoolCapFFF",
2212
+ "cool_eir_ft": "HPACCOOLEIRFT",
2213
+ "cool_eir_fflow": "HPACCOOLEIRFFF",
2214
+ "cool_plf_fplr": "HPACCOOLPLFFPLR",
2215
+ "notes": "From OEESC 2014 Table 503.2.3(2) Before 1/1/2016"
2216
+ },
2217
+ {
2218
+ "template": "OEESC 2014",
2219
+ "cooling_type": "AirCooled",
2220
+ "heating_type": "All Other",
2221
+ "subcategory": "Split System",
2222
+ "minimum_capacity": 65000.0,
2223
+ "maximum_capacity": 134999.0,
2224
+ "minimum_seasonal_efficiency": null,
2225
+ "minimum_full_load_efficiency": 10.8,
2226
+ "minimum_iplv": null,
2227
+ "minimum_integrated_energy_efficiency_ratio": 11.0,
2228
+ "cool_cap_ft": "HPACCoolCapFT",
2229
+ "cool_cap_fflow": "HPACCoolCapFFF",
2230
+ "cool_eir_ft": "HPACCOOLEIRFT",
2231
+ "cool_eir_fflow": "HPACCOOLEIRFFF",
2232
+ "cool_plf_fplr": "HPACCOOLPLFFPLR",
2233
+ "notes": "From OEESC 2014 Table 503.2.3(2) Before 1/1/2016"
2234
+ },
2235
+ {
2236
+ "template": "OEESC 2014",
2237
+ "cooling_type": "AirCooled",
2238
+ "heating_type": "All Other",
2239
+ "subcategory": "Single Package",
2240
+ "minimum_capacity": 65000.0,
2241
+ "maximum_capacity": 134999.0,
2242
+ "minimum_seasonal_efficiency": null,
2243
+ "minimum_full_load_efficiency": 10.8,
2244
+ "minimum_iplv": null,
2245
+ "minimum_integrated_energy_efficiency_ratio": 11.0,
2246
+ "cool_cap_ft": "HPACCoolCapFT",
2247
+ "cool_cap_fflow": "HPACCoolCapFFF",
2248
+ "cool_eir_ft": "HPACCOOLEIRFT",
2249
+ "cool_eir_fflow": "HPACCOOLEIRFFF",
2250
+ "cool_plf_fplr": "HPACCOOLPLFFPLR",
2251
+ "notes": "From OEESC 2014 Table 503.2.3(2) Before 1/1/2016"
2252
+ },
2253
+ {
2254
+ "template": "OEESC 2014",
2255
+ "cooling_type": "AirCooled",
2256
+ "heating_type": "Electric Resistance or None",
2257
+ "subcategory": "Split System",
2258
+ "minimum_capacity": 135000.0,
2259
+ "maximum_capacity": 239999.0,
2260
+ "minimum_seasonal_efficiency": null,
2261
+ "minimum_full_load_efficiency": 10.6,
2262
+ "minimum_iplv": null,
2263
+ "minimum_integrated_energy_efficiency_ratio": 10.7,
2264
+ "cool_cap_ft": "HPACCoolCapFT",
2265
+ "cool_cap_fflow": "HPACCoolCapFFF",
2266
+ "cool_eir_ft": "HPACCOOLEIRFT",
2267
+ "cool_eir_fflow": "HPACCOOLEIRFFF",
2268
+ "cool_plf_fplr": "HPACCOOLPLFFPLR",
2269
+ "notes": "From OEESC 2014 Table 503.2.3(2) Before 1/1/2016"
2270
+ },
2271
+ {
2272
+ "template": "OEESC 2014",
2273
+ "cooling_type": "AirCooled",
2274
+ "heating_type": "Electric Resistance or None",
2275
+ "subcategory": "Single Package",
2276
+ "minimum_capacity": 135000.0,
2277
+ "maximum_capacity": 239999.0,
2278
+ "minimum_seasonal_efficiency": null,
2279
+ "minimum_full_load_efficiency": 10.6,
2280
+ "minimum_iplv": null,
2281
+ "minimum_integrated_energy_efficiency_ratio": 10.7,
2282
+ "cool_cap_ft": "HPACCoolCapFT",
2283
+ "cool_cap_fflow": "HPACCoolCapFFF",
2284
+ "cool_eir_ft": "HPACCOOLEIRFT",
2285
+ "cool_eir_fflow": "HPACCOOLEIRFFF",
2286
+ "cool_plf_fplr": "HPACCOOLPLFFPLR",
2287
+ "notes": "From OEESC 2014 Table 503.2.3(2) Before 1/1/2016"
2288
+ },
2289
+ {
2290
+ "template": "OEESC 2014",
2291
+ "cooling_type": "AirCooled",
2292
+ "heating_type": "All Other",
2293
+ "subcategory": "Split System",
2294
+ "minimum_capacity": 135000.0,
2295
+ "maximum_capacity": 239999.0,
2296
+ "minimum_seasonal_efficiency": null,
2297
+ "minimum_full_load_efficiency": 10.4,
2298
+ "minimum_iplv": null,
2299
+ "minimum_integrated_energy_efficiency_ratio": 10.5,
2300
+ "cool_cap_ft": "HPACCoolCapFT",
2301
+ "cool_cap_fflow": "HPACCoolCapFFF",
2302
+ "cool_eir_ft": "HPACCOOLEIRFT",
2303
+ "cool_eir_fflow": "HPACCOOLEIRFFF",
2304
+ "cool_plf_fplr": "HPACCOOLPLFFPLR",
2305
+ "notes": "From OEESC 2014 Table 503.2.3(2) Before 1/1/2016"
2306
+ },
2307
+ {
2308
+ "template": "OEESC 2014",
2309
+ "cooling_type": "AirCooled",
2310
+ "heating_type": "All Other",
2311
+ "subcategory": "Single Package",
2312
+ "minimum_capacity": 135000.0,
2313
+ "maximum_capacity": 239999.0,
2314
+ "minimum_seasonal_efficiency": null,
2315
+ "minimum_full_load_efficiency": 10.4,
2316
+ "minimum_iplv": null,
2317
+ "minimum_integrated_energy_efficiency_ratio": 10.5,
2318
+ "cool_cap_ft": "HPACCoolCapFT",
2319
+ "cool_cap_fflow": "HPACCoolCapFFF",
2320
+ "cool_eir_ft": "HPACCOOLEIRFT",
2321
+ "cool_eir_fflow": "HPACCOOLEIRFFF",
2322
+ "cool_plf_fplr": "HPACCOOLPLFFPLR",
2323
+ "notes": "From OEESC 2014 Table 503.2.3(2) Before 1/1/2016"
2324
+ },
2325
+ {
2326
+ "template": "OEESC 2014",
2327
+ "cooling_type": "AirCooled",
2328
+ "heating_type": "Electric Resistance or None",
2329
+ "subcategory": "Split System",
2330
+ "minimum_capacity": 240000.0,
2331
+ "maximum_capacity": 9999999.0,
2332
+ "minimum_seasonal_efficiency": null,
2333
+ "minimum_full_load_efficiency": 9.5,
2334
+ "minimum_iplv": null,
2335
+ "minimum_integrated_energy_efficiency_ratio": 9.6,
2336
+ "cool_cap_ft": "HPACCoolCapFT",
2337
+ "cool_cap_fflow": "HPACCoolCapFFF",
2338
+ "cool_eir_ft": "HPACCOOLEIRFT",
2339
+ "cool_eir_fflow": "HPACCOOLEIRFFF",
2340
+ "cool_plf_fplr": "HPACCOOLPLFFPLR",
2341
+ "notes": "From OEESC 2014 Table 503.2.3(2) Before 1/1/2016"
2342
+ },
2343
+ {
2344
+ "template": "OEESC 2014",
2345
+ "cooling_type": "AirCooled",
2346
+ "heating_type": "Electric Resistance or None",
2347
+ "subcategory": "Single Package",
2348
+ "minimum_capacity": 240000.0,
2349
+ "maximum_capacity": 9999999.0,
2350
+ "minimum_seasonal_efficiency": null,
2351
+ "minimum_full_load_efficiency": 9.5,
2352
+ "minimum_iplv": null,
2353
+ "minimum_integrated_energy_efficiency_ratio": 9.6,
2354
+ "cool_cap_ft": "HPACCoolCapFT",
2355
+ "cool_cap_fflow": "HPACCoolCapFFF",
2356
+ "cool_eir_ft": "HPACCOOLEIRFT",
2357
+ "cool_eir_fflow": "HPACCOOLEIRFFF",
2358
+ "cool_plf_fplr": "HPACCOOLPLFFPLR",
2359
+ "notes": "From OEESC 2014 Table 503.2.3(2) Before 1/1/2016"
2360
+ },
2361
+ {
2362
+ "template": "OEESC 2014",
2363
+ "cooling_type": "AirCooled",
2364
+ "heating_type": "All Other",
2365
+ "subcategory": "Split System",
2366
+ "minimum_capacity": 240000.0,
2367
+ "maximum_capacity": 9999999.0,
2368
+ "minimum_seasonal_efficiency": null,
2369
+ "minimum_full_load_efficiency": 9.3,
2370
+ "minimum_iplv": null,
2371
+ "minimum_integrated_energy_efficiency_ratio": 9.4,
2372
+ "cool_cap_ft": "HPACCoolCapFT",
2373
+ "cool_cap_fflow": "HPACCoolCapFFF",
2374
+ "cool_eir_ft": "HPACCOOLEIRFT",
2375
+ "cool_eir_fflow": "HPACCOOLEIRFFF",
2376
+ "cool_plf_fplr": "HPACCOOLPLFFPLR",
2377
+ "notes": "From OEESC 2014 Table 503.2.3(2) Before 1/1/2016"
2378
+ },
2379
+ {
2380
+ "template": "OEESC 2014",
2381
+ "cooling_type": "AirCooled",
2382
+ "heating_type": "All Other",
2383
+ "subcategory": "Single Package",
2384
+ "minimum_capacity": 240000.0,
2385
+ "maximum_capacity": 9999999.0,
2386
+ "minimum_seasonal_efficiency": null,
2387
+ "minimum_full_load_efficiency": 9.3,
2388
+ "minimum_iplv": null,
2389
+ "minimum_integrated_energy_efficiency_ratio": 9.4,
2390
+ "cool_cap_ft": "HPACCoolCapFT",
2391
+ "cool_cap_fflow": "HPACCoolCapFFF",
2392
+ "cool_eir_ft": "HPACCOOLEIRFT",
2393
+ "cool_eir_fflow": "HPACCOOLEIRFFF",
2394
+ "cool_plf_fplr": "HPACCOOLPLFFPLR",
2395
+ "notes": "From OEESC 2014 Table 503.2.3(2) Before 1/1/2016"
342
2396
  }
343
2397
  ]
344
2398
  }