open-fdd 0.1.4__py3-none-any.whl → 0.1.6__py3-none-any.whl

This diff represents the content of publicly available package versions that have been released to one of the supported registries. The information contained in this diff is provided for informational purposes only and reflects changes between package versions as they appear in their respective public registries.
Files changed (63) hide show
  1. open_fdd/air_handling_unit/faults/__init__.py +301 -301
  2. open_fdd/air_handling_unit/reports/__init__.py +988 -0
  3. open_fdd/air_handling_unit/reports/fault_report.py +42 -0
  4. open_fdd/tests/ahu/test_ahu_fc16.py +190 -0
  5. {open_fdd-0.1.4.dist-info → open_fdd-0.1.6.dist-info}/METADATA +21 -12
  6. open_fdd-0.1.6.dist-info/RECORD +31 -0
  7. {open_fdd-0.1.4.dist-info → open_fdd-0.1.6.dist-info}/WHEEL +1 -1
  8. open_fdd/air_handling_unit/faults/fault_condition_eight.py +0 -127
  9. open_fdd/air_handling_unit/faults/fault_condition_eleven.py +0 -126
  10. open_fdd/air_handling_unit/faults/fault_condition_fifteen.py +0 -152
  11. open_fdd/air_handling_unit/faults/fault_condition_five.py +0 -123
  12. open_fdd/air_handling_unit/faults/fault_condition_four.py +0 -168
  13. open_fdd/air_handling_unit/faults/fault_condition_fourteen.py +0 -143
  14. open_fdd/air_handling_unit/faults/fault_condition_nine.py +0 -128
  15. open_fdd/air_handling_unit/faults/fault_condition_one.py +0 -112
  16. open_fdd/air_handling_unit/faults/fault_condition_seven.py +0 -114
  17. open_fdd/air_handling_unit/faults/fault_condition_six.py +0 -181
  18. open_fdd/air_handling_unit/faults/fault_condition_ten.py +0 -123
  19. open_fdd/air_handling_unit/faults/fault_condition_thirteen.py +0 -127
  20. open_fdd/air_handling_unit/faults/fault_condition_three.py +0 -113
  21. open_fdd/air_handling_unit/faults/fault_condition_twelve.py +0 -132
  22. open_fdd/air_handling_unit/faults/fault_condition_two.py +0 -113
  23. open_fdd/air_handling_unit/images/ahu1_fc1_2024-06_1.jpg +0 -0
  24. open_fdd/air_handling_unit/images/ahu1_fc1_2024-06_2.jpg +0 -0
  25. open_fdd/air_handling_unit/images/example1.jpg +0 -0
  26. open_fdd/air_handling_unit/images/example2.jpg +0 -0
  27. open_fdd/air_handling_unit/images/fc10_definition.png +0 -0
  28. open_fdd/air_handling_unit/images/fc11_definition.png +0 -0
  29. open_fdd/air_handling_unit/images/fc12_definition.png +0 -0
  30. open_fdd/air_handling_unit/images/fc13_definition.png +0 -0
  31. open_fdd/air_handling_unit/images/fc1_definition.png +0 -0
  32. open_fdd/air_handling_unit/images/fc1_report_screenshot_all.png +0 -0
  33. open_fdd/air_handling_unit/images/fc2_definition.png +0 -0
  34. open_fdd/air_handling_unit/images/fc3_definition.png +0 -0
  35. open_fdd/air_handling_unit/images/fc4_definition.png +0 -0
  36. open_fdd/air_handling_unit/images/fc5_definition.png +0 -0
  37. open_fdd/air_handling_unit/images/fc6_definition.png +0 -0
  38. open_fdd/air_handling_unit/images/fc7_definition.png +0 -0
  39. open_fdd/air_handling_unit/images/fc8_definition.png +0 -0
  40. open_fdd/air_handling_unit/images/fc9_definition.png +0 -0
  41. open_fdd/air_handling_unit/images/latex_generator.py +0 -175
  42. open_fdd/air_handling_unit/images/params.docx +0 -0
  43. open_fdd/air_handling_unit/images/params.pdf +0 -0
  44. open_fdd/air_handling_unit/images/plot_for_repo.png +0 -0
  45. open_fdd/air_handling_unit/reports/base_report.py +0 -47
  46. open_fdd/air_handling_unit/reports/report_fc1.py +0 -115
  47. open_fdd/air_handling_unit/reports/report_fc10.py +0 -126
  48. open_fdd/air_handling_unit/reports/report_fc11.py +0 -128
  49. open_fdd/air_handling_unit/reports/report_fc12.py +0 -126
  50. open_fdd/air_handling_unit/reports/report_fc13.py +0 -126
  51. open_fdd/air_handling_unit/reports/report_fc14.py +0 -124
  52. open_fdd/air_handling_unit/reports/report_fc15.py +0 -124
  53. open_fdd/air_handling_unit/reports/report_fc2.py +0 -119
  54. open_fdd/air_handling_unit/reports/report_fc3.py +0 -119
  55. open_fdd/air_handling_unit/reports/report_fc4.py +0 -148
  56. open_fdd/air_handling_unit/reports/report_fc5.py +0 -132
  57. open_fdd/air_handling_unit/reports/report_fc6.py +0 -156
  58. open_fdd/air_handling_unit/reports/report_fc7.py +0 -126
  59. open_fdd/air_handling_unit/reports/report_fc8.py +0 -118
  60. open_fdd/air_handling_unit/reports/report_fc9.py +0 -120
  61. open_fdd-0.1.4.dist-info/RECORD +0 -82
  62. {open_fdd-0.1.4.dist-info → open_fdd-0.1.6.dist-info}/LICENSE +0 -0
  63. {open_fdd-0.1.4.dist-info → open_fdd-0.1.6.dist-info}/top_level.txt +0 -0
@@ -1,127 +0,0 @@
1
- import pandas as pd
2
- import operator
3
- from open_fdd.air_handling_unit.faults.fault_condition import (
4
- FaultCondition,
5
- MissingColumnError,
6
- )
7
- import sys
8
-
9
-
10
- class FaultConditionThirteen(FaultCondition):
11
- """Class provides the definitions for Fault Condition 13.
12
- Supply air temperature too high in full cooling
13
- in economizer plus mech cooling mode
14
- """
15
-
16
- def __init__(self, dict_):
17
- super().__init__()
18
- self.supply_degf_err_thres = float
19
- self.ahu_min_oa_dpr = float
20
- self.sat_col = str
21
- self.sat_setpoint_col = str
22
- self.cooling_sig_col = str
23
- self.economizer_sig_col = str
24
- self.troubleshoot_mode = bool # default False
25
- self.rolling_window_size = int
26
-
27
- self.equation_string = (
28
- "fc13_flag = 1 if SAT > (SATSP + εSAT) in "
29
- "economizer + mech cooling mode for N consecutive values else 0 \n"
30
- )
31
- self.description_string = (
32
- "Fault Condition 13: Supply air temperature too high in full cooling "
33
- "in economizer plus mechanical cooling mode \n"
34
- )
35
- self.required_column_description = (
36
- "Required inputs are the supply air temperature, supply air temperature setpoint, "
37
- "cooling signal, and economizer signal \n"
38
- )
39
- self.error_string = f"One or more required columns are missing or None \n"
40
-
41
- self.set_attributes(dict_)
42
-
43
- # Set required columns specific to this fault condition
44
- self.required_columns = [
45
- self.sat_col,
46
- self.sat_setpoint_col,
47
- self.cooling_sig_col,
48
- self.economizer_sig_col,
49
- ]
50
-
51
- # Check if any of the required columns are None
52
- if any(col is None for col in self.required_columns):
53
- raise MissingColumnError(
54
- f"{self.error_string}"
55
- f"{self.equation_string}"
56
- f"{self.description_string}"
57
- f"{self.required_column_description}"
58
- f"{self.required_columns}"
59
- )
60
-
61
- # Ensure all required columns are strings
62
- self.required_columns = [str(col) for col in self.required_columns]
63
-
64
- self.mapped_columns = (
65
- f"Your config dictionary is mapped as: {', '.join(self.required_columns)}"
66
- )
67
-
68
- def get_required_columns(self) -> str:
69
- """Returns a string representation of the required columns."""
70
- return (
71
- f"{self.equation_string}"
72
- f"{self.description_string}"
73
- f"{self.required_column_description}"
74
- f"{self.mapped_columns}"
75
- )
76
-
77
- def apply(self, df: pd.DataFrame) -> pd.DataFrame:
78
- try:
79
- # Ensure all required columns are present
80
- self.check_required_columns(df)
81
-
82
- if self.troubleshoot_mode:
83
- self.troubleshoot_cols(df)
84
-
85
- # Check analog outputs [data with units of %] are floats only
86
- columns_to_check = [
87
- self.economizer_sig_col,
88
- self.cooling_sig_col,
89
- ]
90
- self.check_analog_pct(df, columns_to_check)
91
-
92
- # Create helper columns
93
- df["sat_greater_than_sp_calc"] = (
94
- df[self.sat_col]
95
- > df[self.sat_setpoint_col] + self.supply_degf_err_thres
96
- )
97
-
98
- df["combined_check"] = operator.or_(
99
- ((df["sat_greater_than_sp_calc"]))
100
- # OS4 AHU state clg @ min OA
101
- & (df[self.cooling_sig_col] > 0.01)
102
- & (df[self.economizer_sig_col] == self.ahu_min_oa_dpr), # OR
103
- ((df["sat_greater_than_sp_calc"]))
104
- # verify ahu is running in OS 3 clg mode in 100 OA
105
- & (df[self.cooling_sig_col] > 0.01)
106
- & (df[self.economizer_sig_col] > 0.9),
107
- )
108
-
109
- # Rolling sum to count consecutive trues
110
- rolling_sum = (
111
- df["combined_check"].rolling(window=self.rolling_window_size).sum()
112
- )
113
- # Set flag to 1 if rolling sum equals the window size
114
- df["fc13_flag"] = (rolling_sum >= self.rolling_window_size).astype(int)
115
-
116
- if self.troubleshoot_mode:
117
- print("Troubleshoot mode enabled - not removing helper columns")
118
- sys.stdout.flush()
119
- del df["sat_greater_than_sp_calc"]
120
- del df["combined_check"]
121
-
122
- return df
123
-
124
- except MissingColumnError as e:
125
- print(f"Error: {e.message}")
126
- sys.stdout.flush()
127
- raise e
@@ -1,113 +0,0 @@
1
- import pandas as pd
2
- import numpy as np
3
- from open_fdd.air_handling_unit.faults.fault_condition import (
4
- FaultCondition,
5
- MissingColumnError,
6
- )
7
- import sys
8
-
9
-
10
- class FaultConditionThree(FaultCondition):
11
- """Class provides the definitions for Fault Condition 3.
12
- Mix temperature too high; should be between outside and return air.
13
- """
14
-
15
- def __init__(self, dict_):
16
- super().__init__()
17
- self.mix_degf_err_thres = float
18
- self.return_degf_err_thres = float
19
- self.outdoor_degf_err_thres = float
20
- self.mat_col = str
21
- self.rat_col = str
22
- self.oat_col = str
23
- self.supply_vfd_speed_col = str
24
- self.troubleshoot_mode = bool # default to False
25
- self.rolling_window_size = int
26
-
27
- self.equation_string = (
28
- "fc3_flag = 1 if (MAT - εMAT > max(RAT + εRAT, OAT + εOAT)) and (VFDSPD > 0) "
29
- "for N consecutive values else 0 \n"
30
- )
31
- self.description_string = "Fault Condition 3: Mix temperature too high; should be between outside and return air \n"
32
- self.required_column_description = "Required inputs are the mix air temperature, return air temperature, outside air temperature, and supply fan VFD speed \n"
33
- self.error_string = f"One or more required columns are missing or None \n"
34
-
35
- self.set_attributes(dict_)
36
-
37
- # Set required columns specific to this fault condition
38
- self.required_columns = [
39
- self.mat_col,
40
- self.rat_col,
41
- self.oat_col,
42
- self.supply_vfd_speed_col,
43
- ]
44
-
45
- # Check if any of the required columns are None
46
- if any(col is None for col in self.required_columns):
47
- raise MissingColumnError(
48
- f"{self.error_string}"
49
- f"{self.equation_string}"
50
- f"{self.description_string}"
51
- f"{self.required_column_description}"
52
- f"{self.required_columns}"
53
- )
54
-
55
- # Ensure all required columns are strings
56
- self.required_columns = [str(col) for col in self.required_columns]
57
-
58
- self.mapped_columns = (
59
- f"Your config dictionary is mapped as: {', '.join(self.required_columns)}"
60
- )
61
-
62
- def get_required_columns(self) -> str:
63
- """Returns a string representation of the required columns."""
64
- return (
65
- f"{self.equation_string}"
66
- f"{self.description_string}"
67
- f"{self.required_column_description}"
68
- f"{self.mapped_columns}"
69
- )
70
-
71
- def apply(self, df: pd.DataFrame) -> pd.DataFrame:
72
- try:
73
- # Ensure all required columns are present
74
- self.check_required_columns(df)
75
-
76
- if self.troubleshoot_mode:
77
- self.troubleshoot_cols(df)
78
-
79
- # Check analog outputs [data with units of %] are floats only
80
- columns_to_check = [self.supply_vfd_speed_col]
81
- self.check_analog_pct(df, columns_to_check)
82
-
83
- # Fault condition-specific checks / flags
84
- df["mat_check"] = df[self.mat_col] - self.mix_degf_err_thres
85
- df["temp_min_check"] = np.maximum(
86
- df[self.rat_col] + self.return_degf_err_thres,
87
- df[self.oat_col] + self.outdoor_degf_err_thres,
88
- )
89
-
90
- df["combined_check"] = (df["mat_check"] > df["temp_min_check"]) & (
91
- df[self.supply_vfd_speed_col] > 0.01
92
- )
93
-
94
- # Rolling sum to count consecutive trues
95
- rolling_sum = (
96
- df["combined_check"].rolling(window=self.rolling_window_size).sum()
97
- )
98
- # Set flag to 1 if rolling sum equals the window size
99
- df["fc3_flag"] = (rolling_sum >= self.rolling_window_size).astype(int)
100
-
101
- if self.troubleshoot_mode:
102
- print("Troubleshoot mode enabled - not removing helper columns")
103
- sys.stdout.flush()
104
- del df["mat_check"]
105
- del df["temp_min_check"]
106
- del df["combined_check"]
107
-
108
- return df
109
-
110
- except MissingColumnError as e:
111
- print(f"Error: {e.message}")
112
- sys.stdout.flush()
113
- raise e
@@ -1,132 +0,0 @@
1
- import pandas as pd
2
- import numpy as np
3
- import operator
4
- from open_fdd.air_handling_unit.faults.fault_condition import (
5
- FaultCondition,
6
- MissingColumnError,
7
- )
8
- import sys
9
-
10
-
11
- class FaultConditionTwelve(FaultCondition):
12
- """Class provides the definitions for Fault Condition 12.
13
- Supply air temperature too high; should be less than
14
- mix air temperature in economizer plus mech cooling mode.
15
- """
16
-
17
- def __init__(self, dict_):
18
- super().__init__()
19
- self.delta_t_supply_fan = float
20
- self.mix_degf_err_thres = float
21
- self.supply_degf_err_thres = float
22
- self.ahu_min_oa_dpr = float
23
- self.sat_col = str
24
- self.mat_col = str
25
- self.cooling_sig_col = str
26
- self.economizer_sig_col = str
27
- self.troubleshoot_mode = bool # default False
28
- self.rolling_window_size = int
29
-
30
- self.equation_string = (
31
- "fc12_flag = 1 if SAT >= MAT + εMAT in "
32
- "economizer + mech cooling mode for N consecutive values else 0 \n"
33
- )
34
- self.description_string = (
35
- "Fault Condition 12: Supply air temperature too high; should be less than "
36
- "mixed air temperature in economizer plus mechanical cooling mode \n"
37
- )
38
- self.required_column_description = (
39
- "Required inputs are the supply air temperature, mixed air temperature, "
40
- "cooling signal, and economizer signal \n"
41
- )
42
- self.error_string = f"One or more required columns are missing or None \n"
43
-
44
- self.set_attributes(dict_)
45
-
46
- # Set required columns specific to this fault condition
47
- self.required_columns = [
48
- self.sat_col,
49
- self.mat_col,
50
- self.cooling_sig_col,
51
- self.economizer_sig_col,
52
- ]
53
-
54
- # Check if any of the required columns are None
55
- if any(col is None for col in self.required_columns):
56
- raise MissingColumnError(
57
- f"{self.error_string}"
58
- f"{self.equation_string}"
59
- f"{self.description_string}"
60
- f"{self.required_column_description}"
61
- f"{self.required_columns}"
62
- )
63
-
64
- # Ensure all required columns are strings
65
- self.required_columns = [str(col) for col in self.required_columns]
66
-
67
- self.mapped_columns = (
68
- f"Your config dictionary is mapped as: {', '.join(self.required_columns)}"
69
- )
70
-
71
- def get_required_columns(self) -> str:
72
- """Returns a string representation of the required columns."""
73
- return (
74
- f"{self.equation_string}"
75
- f"{self.description_string}"
76
- f"{self.required_column_description}"
77
- f"{self.mapped_columns}"
78
- )
79
-
80
- def apply(self, df: pd.DataFrame) -> pd.DataFrame:
81
- try:
82
- # Ensure all required columns are present
83
- self.check_required_columns(df)
84
-
85
- if self.troubleshoot_mode:
86
- self.troubleshoot_cols(df)
87
-
88
- # Check analog outputs [data with units of %] are floats only
89
- columns_to_check = [
90
- self.economizer_sig_col,
91
- self.cooling_sig_col,
92
- ]
93
- self.check_analog_pct(df, columns_to_check)
94
-
95
- # Create helper columns
96
- df["sat_minus_saterr_delta_supply_fan"] = (
97
- df[self.sat_col] - self.supply_degf_err_thres - self.delta_t_supply_fan
98
- )
99
- df["mat_plus_materr"] = df[self.mat_col] + self.mix_degf_err_thres
100
-
101
- df["combined_check"] = operator.or_(
102
- # OS4 AHU state clg @ min OA
103
- (df["sat_minus_saterr_delta_supply_fan"] > df["mat_plus_materr"])
104
- # verify AHU in OS4 mode
105
- & (df[self.cooling_sig_col] > 0.01)
106
- & (df[self.economizer_sig_col] == self.ahu_min_oa_dpr), # OR
107
- (df["sat_minus_saterr_delta_supply_fan"] > df["mat_plus_materr"])
108
- # verify AHU is running in OS 3 clg mode in 100 OA
109
- & (df[self.cooling_sig_col] > 0.01)
110
- & (df[self.economizer_sig_col] > 0.9),
111
- )
112
-
113
- # Rolling sum to count consecutive trues
114
- rolling_sum = (
115
- df["combined_check"].rolling(window=self.rolling_window_size).sum()
116
- )
117
- # Set flag to 1 if rolling sum equals the window size
118
- df["fc12_flag"] = (rolling_sum >= self.rolling_window_size).astype(int)
119
-
120
- if self.troubleshoot_mode:
121
- print("Troubleshoot mode enabled - not removing helper columns")
122
- sys.stdout.flush()
123
- del df["sat_minus_saterr_delta_supply_fan"]
124
- del df["mat_plus_materr"]
125
- del df["combined_check"]
126
-
127
- return df
128
-
129
- except MissingColumnError as e:
130
- print(f"Error: {e.message}")
131
- sys.stdout.flush()
132
- raise e
@@ -1,113 +0,0 @@
1
- import pandas as pd
2
- import numpy as np
3
- from open_fdd.air_handling_unit.faults.fault_condition import (
4
- FaultCondition,
5
- MissingColumnError,
6
- )
7
- import sys
8
-
9
-
10
- class FaultConditionTwo(FaultCondition):
11
- """Class provides the definitions for Fault Condition 2.
12
- Mix temperature too low; should be between outside and return air.
13
- """
14
-
15
- def __init__(self, dict_):
16
- super().__init__()
17
- self.mix_degf_err_thres = float
18
- self.return_degf_err_thres = float
19
- self.outdoor_degf_err_thres = float
20
- self.mat_col = str
21
- self.rat_col = str
22
- self.oat_col = str
23
- self.supply_vfd_speed_col = str
24
- self.troubleshoot_mode = bool # default to False
25
- self.rolling_window_size = int
26
-
27
- self.equation_string = (
28
- "fc2_flag = 1 if (MAT + εMAT < min(RAT - εRAT, OAT - εOAT)) and (VFDSPD > 0) "
29
- "for N consecutive values else 0 \n"
30
- )
31
- self.description_string = "Fault Condition 2: Mix temperature too low; should be between outside and return air \n"
32
- self.required_column_description = "Required inputs are the mix air temperature, return air temperature, outside air temperature, and supply fan VFD speed \n"
33
- self.error_string = f"One or more required columns are missing or None \n"
34
-
35
- self.set_attributes(dict_)
36
-
37
- # Set required columns specific to this fault condition
38
- self.required_columns = [
39
- self.mat_col,
40
- self.rat_col,
41
- self.oat_col,
42
- self.supply_vfd_speed_col,
43
- ]
44
-
45
- # Check if any of the required columns are None
46
- if any(col is None for col in self.required_columns):
47
- raise MissingColumnError(
48
- f"{self.error_string}"
49
- f"{self.equation_string}"
50
- f"{self.description_string}"
51
- f"{self.required_column_description}"
52
- f"{self.required_columns}"
53
- )
54
-
55
- # Ensure all required columns are strings
56
- self.required_columns = [str(col) for col in self.required_columns]
57
-
58
- self.mapped_columns = (
59
- f"Your config dictionary is mapped as: {', '.join(self.required_columns)}"
60
- )
61
-
62
- def get_required_columns(self) -> str:
63
- """Returns a string representation of the required columns."""
64
- return (
65
- f"{self.equation_string}"
66
- f"{self.description_string}"
67
- f"{self.required_column_description}"
68
- f"{self.mapped_columns}"
69
- )
70
-
71
- def apply(self, df: pd.DataFrame) -> pd.DataFrame:
72
- try:
73
- # Ensure all required columns are present
74
- self.check_required_columns(df)
75
-
76
- if self.troubleshoot_mode:
77
- self.troubleshoot_cols(df)
78
-
79
- # Check analog outputs [data with units of %] are floats only
80
- columns_to_check = [self.supply_vfd_speed_col]
81
- self.check_analog_pct(df, columns_to_check)
82
-
83
- # Fault condition-specific checks / flags
84
- df["mat_check"] = df[self.mat_col] + self.mix_degf_err_thres
85
- df["temp_min_check"] = np.minimum(
86
- df[self.rat_col] - self.return_degf_err_thres,
87
- df[self.oat_col] - self.outdoor_degf_err_thres,
88
- )
89
-
90
- df["combined_check"] = (df["mat_check"] < df["temp_min_check"]) & (
91
- df[self.supply_vfd_speed_col] > 0.01
92
- )
93
-
94
- # Rolling sum to count consecutive trues
95
- rolling_sum = (
96
- df["combined_check"].rolling(window=self.rolling_window_size).sum()
97
- )
98
- # Set flag to 1 if rolling sum equals the window size
99
- df["fc2_flag"] = (rolling_sum >= self.rolling_window_size).astype(int)
100
-
101
- if self.troubleshoot_mode:
102
- print("Troubleshoot mode enabled - not removing helper columns")
103
- sys.stdout.flush()
104
- del df["mat_check"]
105
- del df["temp_min_check"]
106
- del df["combined_check"]
107
-
108
- return df
109
-
110
- except MissingColumnError as e:
111
- print(f"Error: {e.message}")
112
- sys.stdout.flush()
113
- raise e