tanzim 0.1.0__tar.gz
This diff represents the content of publicly available package versions that have been released to one of the supported registries. The information contained in this diff is provided for informational purposes only and reflects changes between package versions as they appear in their respective public registries.
- tanzim-0.1.0/PKG-INFO +12 -0
- tanzim-0.1.0/pyproject.toml +23 -0
- tanzim-0.1.0/setup.cfg +4 -0
- tanzim-0.1.0/src/tanzim/__init__.py +17 -0
- tanzim-0.1.0/src/tanzim/__version__.py +1 -0
- tanzim-0.1.0/src/tanzim/cli.py +84 -0
- tanzim-0.1.0/src/tanzim/detectors.py +505 -0
- tanzim-0.1.0/src/tanzim/engine.py +81 -0
- tanzim-0.1.0/src/tanzim/io.py +119 -0
- tanzim-0.1.0/src/tanzim/llm_tickets.py +70 -0
- tanzim-0.1.0/src/tanzim/schema.py +103 -0
- tanzim-0.1.0/src/tanzim/synthetic.py +118 -0
- tanzim-0.1.0/src/tanzim/tariffs.py +53 -0
- tanzim-0.1.0/src/tanzim.egg-info/PKG-INFO +12 -0
- tanzim-0.1.0/src/tanzim.egg-info/SOURCES.txt +18 -0
- tanzim-0.1.0/src/tanzim.egg-info/dependency_links.txt +1 -0
- tanzim-0.1.0/src/tanzim.egg-info/entry_points.txt +2 -0
- tanzim-0.1.0/src/tanzim.egg-info/requires.txt +4 -0
- tanzim-0.1.0/src/tanzim.egg-info/top_level.txt +1 -0
- tanzim-0.1.0/tests/test_tanzim.py +35 -0
tanzim-0.1.0/PKG-INFO
ADDED
|
@@ -0,0 +1,12 @@
|
|
|
1
|
+
Metadata-Version: 2.4
|
|
2
|
+
Name: tanzim
|
|
3
|
+
Version: 0.1.0
|
|
4
|
+
Summary: Offline-first silent-fault and energy-imbalance auditor for building BMS and industrial SCADA logs.
|
|
5
|
+
Author-email: Aslan Satary Dizaji <aslansatary@gmail.com>
|
|
6
|
+
License: MIT
|
|
7
|
+
Keywords: bms,scada,hvac,energy-audit,fault-detection,change-point
|
|
8
|
+
Requires-Python: >=3.10
|
|
9
|
+
Description-Content-Type: text/markdown
|
|
10
|
+
Provides-Extra: dev
|
|
11
|
+
Requires-Dist: pytest>=8.0; extra == "dev"
|
|
12
|
+
Requires-Dist: ruff>=0.6; extra == "dev"
|
|
@@ -0,0 +1,23 @@
|
|
|
1
|
+
[build-system]
|
|
2
|
+
requires = ["setuptools>=68"]
|
|
3
|
+
build-backend = "setuptools.build_meta"
|
|
4
|
+
|
|
5
|
+
[project]
|
|
6
|
+
name = "tanzim"
|
|
7
|
+
version = "0.1.0"
|
|
8
|
+
description = "Offline-first silent-fault and energy-imbalance auditor for building BMS and industrial SCADA logs."
|
|
9
|
+
readme = "README.md"
|
|
10
|
+
requires-python = ">=3.10"
|
|
11
|
+
license = { text = "MIT" }
|
|
12
|
+
authors = [{ name = "Aslan Satary Dizaji", email = "aslansatary@gmail.com" }]
|
|
13
|
+
keywords = ["bms", "scada", "hvac", "energy-audit", "fault-detection", "change-point"]
|
|
14
|
+
dependencies = []
|
|
15
|
+
|
|
16
|
+
[project.optional-dependencies]
|
|
17
|
+
dev = ["pytest>=8.0", "ruff>=0.6"]
|
|
18
|
+
|
|
19
|
+
[project.scripts]
|
|
20
|
+
tanzim = "tanzim.cli:main"
|
|
21
|
+
|
|
22
|
+
[tool.setuptools.packages.find]
|
|
23
|
+
where = ["src"]
|
tanzim-0.1.0/setup.cfg
ADDED
|
@@ -0,0 +1,17 @@
|
|
|
1
|
+
from .engine import __version__, audit_file, audit_records
|
|
2
|
+
from .llm_tickets import generate_work_order
|
|
3
|
+
from .schema import AuditConfig, AuditReport, Finding, Severity, TelemetryPoint
|
|
4
|
+
from .tariffs import IranTariffProfile
|
|
5
|
+
|
|
6
|
+
__all__ = [
|
|
7
|
+
"__version__",
|
|
8
|
+
"AuditConfig",
|
|
9
|
+
"AuditReport",
|
|
10
|
+
"Finding",
|
|
11
|
+
"IranTariffProfile",
|
|
12
|
+
"Severity",
|
|
13
|
+
"TelemetryPoint",
|
|
14
|
+
"audit_file",
|
|
15
|
+
"audit_records",
|
|
16
|
+
"generate_work_order",
|
|
17
|
+
]
|
|
@@ -0,0 +1 @@
|
|
|
1
|
+
__version__ = "0.1.0"
|
|
@@ -0,0 +1,84 @@
|
|
|
1
|
+
from __future__ import annotations
|
|
2
|
+
|
|
3
|
+
import argparse
|
|
4
|
+
import json
|
|
5
|
+
from pathlib import Path
|
|
6
|
+
|
|
7
|
+
from .engine import audit_file
|
|
8
|
+
from .llm_tickets import generate_work_order
|
|
9
|
+
from .schema import AuditConfig, AuditReport
|
|
10
|
+
from .synthetic import generate_tehran_summer_bms, write_telemetry_csv
|
|
11
|
+
|
|
12
|
+
|
|
13
|
+
def _print_report(report: AuditReport) -> None:
|
|
14
|
+
print(f"tanzim v{report.tool_version} | source={report.source_path}")
|
|
15
|
+
print(f"sha256={report.source_sha256[:16]}... | records={report.record_count} (dt={report.timestep_hours:.2f}h)")
|
|
16
|
+
print(
|
|
17
|
+
f"energy={report.total_energy_kwh:,.1f} kWh | peak={report.peak_energy_kwh:,.1f} kWh | "
|
|
18
|
+
f"est_waste={report.total_estimated_waste_kwh:,.1f} kWh | "
|
|
19
|
+
f"est_savings={report.total_estimated_cost_irr:,.0f} IRR"
|
|
20
|
+
)
|
|
21
|
+
print("-" * 78)
|
|
22
|
+
if not report.findings:
|
|
23
|
+
print("OK: No silent BMS/SCADA energy faults detected.")
|
|
24
|
+
return
|
|
25
|
+
for f in report.findings:
|
|
26
|
+
print(f"[{f.severity.value.upper():8}] {f.code:<24} | {f.title}")
|
|
27
|
+
print(f" {f.summary}")
|
|
28
|
+
if f.estimated_waste_kwh > 0 or f.estimated_cost_irr > 0:
|
|
29
|
+
print(
|
|
30
|
+
f" impact: {f.estimated_waste_kwh:,.1f} kWh | "
|
|
31
|
+
f"{f.estimated_cost_irr:,.0f} IRR"
|
|
32
|
+
)
|
|
33
|
+
|
|
34
|
+
|
|
35
|
+
def main(argv: list[str] | None = None) -> int:
|
|
36
|
+
parser = argparse.ArgumentParser(prog="tanzim", description="Offline BMS/SCADA silent-fault auditor.")
|
|
37
|
+
sub = parser.add_subparsers(dest="cmd", required=True)
|
|
38
|
+
|
|
39
|
+
p_audit = sub.add_parser("audit", help="Audit a BMS/SCADA CSV or JSONL file.")
|
|
40
|
+
p_audit.add_argument("file", help="Path to telemetry .csv or .jsonl")
|
|
41
|
+
p_audit.add_argument("--demand-cap", type=float, default=None, help="Contracted peak demand cap (kW)")
|
|
42
|
+
p_audit.add_argument("--price-irr", type=float, default=12_000.0, help="Base electricity rate (IRR/kWh)")
|
|
43
|
+
p_audit.add_argument("--json-out", type=str, default=None, help="Write provenance JSON report to path")
|
|
44
|
+
p_audit.add_argument("--ticket", choices=("fa", "en"), default=None, help="Generate technician work order via Ollama")
|
|
45
|
+
p_audit.add_argument("--model", type=str, default="gemma3:12b", help="Local Ollama model name")
|
|
46
|
+
|
|
47
|
+
p_demo = sub.add_parser("demo", help="Generate a synthetic Tehran summer BMS dataset and audit it.")
|
|
48
|
+
p_demo.add_argument("--out-csv", type=str, default="tehran_bms_demo.csv")
|
|
49
|
+
p_demo.add_argument("--demand-cap", type=float, default=180.0)
|
|
50
|
+
p_demo.add_argument("--clean", action="store_true", help="Generate healthy baseline without injected faults")
|
|
51
|
+
|
|
52
|
+
args = parser.parse_args(argv)
|
|
53
|
+
|
|
54
|
+
if args.cmd == "demo":
|
|
55
|
+
pts = generate_tehran_summer_bms(days=14, step_minutes=5, inject_faults=not args.clean)
|
|
56
|
+
csv_path = write_telemetry_csv(pts, args.out_csv)
|
|
57
|
+
cfg = AuditConfig(contracted_demand_kw=args.demand_cap)
|
|
58
|
+
report = audit_file(csv_path, config=cfg)
|
|
59
|
+
_print_report(report)
|
|
60
|
+
return 0
|
|
61
|
+
|
|
62
|
+
if args.cmd == "audit":
|
|
63
|
+
cfg = AuditConfig(
|
|
64
|
+
contracted_demand_kw=args.demand_cap,
|
|
65
|
+
base_kwh_price_irr=args.price_irr,
|
|
66
|
+
)
|
|
67
|
+
report = audit_file(args.file, config=cfg)
|
|
68
|
+
_print_report(report)
|
|
69
|
+
if args.json_out:
|
|
70
|
+
Path(args.json_out).write_text(
|
|
71
|
+
json.dumps(report.to_dict(), ensure_ascii=False, indent=2),
|
|
72
|
+
encoding="utf-8",
|
|
73
|
+
)
|
|
74
|
+
print(f"\nSaved provenance report -> {args.json_out}")
|
|
75
|
+
if args.ticket:
|
|
76
|
+
print("\n" + "=" * 78)
|
|
77
|
+
print(generate_work_order(report, lang=args.ticket, model=args.model))
|
|
78
|
+
return 0
|
|
79
|
+
|
|
80
|
+
return 1
|
|
81
|
+
|
|
82
|
+
|
|
83
|
+
if __name__ == "__main__":
|
|
84
|
+
raise SystemExit(main())
|
|
@@ -0,0 +1,505 @@
|
|
|
1
|
+
from __future__ import annotations
|
|
2
|
+
|
|
3
|
+
import math
|
|
4
|
+
from collections import defaultdict
|
|
5
|
+
from datetime import date
|
|
6
|
+
from statistics import mean, median, variance
|
|
7
|
+
|
|
8
|
+
from .schema import AuditConfig, Finding, Severity, TelemetryPoint
|
|
9
|
+
from .tariffs import IranTariffProfile
|
|
10
|
+
|
|
11
|
+
|
|
12
|
+
def _is_occupied(p: TelemetryPoint, cfg: AuditConfig) -> bool:
|
|
13
|
+
return (
|
|
14
|
+
p.timestamp.weekday() not in cfg.weekend_weekdays
|
|
15
|
+
and cfg.occupied_start_hour <= p.timestamp.hour < cfg.occupied_end_hour
|
|
16
|
+
)
|
|
17
|
+
|
|
18
|
+
|
|
19
|
+
def infer_timestep_hours(points: list[TelemetryPoint]) -> float:
|
|
20
|
+
if len(points) < 2:
|
|
21
|
+
return 0.25
|
|
22
|
+
deltas = [
|
|
23
|
+
(points[i].timestamp - points[i - 1].timestamp).total_seconds() / 3600.0
|
|
24
|
+
for i in range(1, len(points))
|
|
25
|
+
]
|
|
26
|
+
positive = [d for d in deltas if d > 0]
|
|
27
|
+
return median(positive) if positive else 0.25
|
|
28
|
+
|
|
29
|
+
|
|
30
|
+
def detect_simultaneous_heat_cool(
|
|
31
|
+
points: list[TelemetryPoint],
|
|
32
|
+
dt_h: float,
|
|
33
|
+
cfg: AuditConfig,
|
|
34
|
+
tariff: IranTariffProfile,
|
|
35
|
+
) -> list[Finding]:
|
|
36
|
+
overlap_pts = [
|
|
37
|
+
p
|
|
38
|
+
for p in points
|
|
39
|
+
if p.heating_valve_pct is not None
|
|
40
|
+
and p.cooling_valve_pct is not None
|
|
41
|
+
and p.heating_valve_pct >= cfg.simultaneous_valve_pct
|
|
42
|
+
and p.cooling_valve_pct >= cfg.simultaneous_valve_pct
|
|
43
|
+
]
|
|
44
|
+
overlap_hours = len(overlap_pts) * dt_h
|
|
45
|
+
if overlap_hours < cfg.simultaneous_min_hours:
|
|
46
|
+
return []
|
|
47
|
+
|
|
48
|
+
waste_kwh = sum(p.power_kw * dt_h * 0.35 for p in overlap_pts)
|
|
49
|
+
cost_irr = sum(
|
|
50
|
+
p.power_kw * dt_h * 0.35 * cfg.base_kwh_price_irr * tariff.multiplier_for(p.timestamp)
|
|
51
|
+
for p in overlap_pts
|
|
52
|
+
)
|
|
53
|
+
severity = Severity.CRITICAL if overlap_hours >= 4.0 else Severity.WARNING
|
|
54
|
+
return [
|
|
55
|
+
Finding(
|
|
56
|
+
code="SIMULTANEOUS_HEAT_COOL",
|
|
57
|
+
title="Simultaneous heating and cooling (valve fighting)",
|
|
58
|
+
severity=severity,
|
|
59
|
+
summary=(
|
|
60
|
+
f"Heating and cooling valves were both open (>={cfg.simultaneous_valve_pct:.0f}%) "
|
|
61
|
+
f"for {overlap_hours:.1f} hours across {len(overlap_pts)} intervals."
|
|
62
|
+
),
|
|
63
|
+
estimated_waste_kwh=round(waste_kwh, 2),
|
|
64
|
+
estimated_cost_irr=round(cost_irr, 0),
|
|
65
|
+
start_time=overlap_pts[0].timestamp.isoformat(),
|
|
66
|
+
end_time=overlap_pts[-1].timestamp.isoformat(),
|
|
67
|
+
evidence={
|
|
68
|
+
"overlap_hours": round(overlap_hours, 2),
|
|
69
|
+
"max_heating_valve_pct": round(max(p.heating_valve_pct or 0.0 for p in overlap_pts), 1),
|
|
70
|
+
"max_cooling_valve_pct": round(max(p.cooling_valve_pct or 0.0 for p in overlap_pts), 1),
|
|
71
|
+
},
|
|
72
|
+
)
|
|
73
|
+
]
|
|
74
|
+
|
|
75
|
+
|
|
76
|
+
def detect_phantom_baseload(
|
|
77
|
+
points: list[TelemetryPoint],
|
|
78
|
+
dt_h: float,
|
|
79
|
+
cfg: AuditConfig,
|
|
80
|
+
tariff: IranTariffProfile,
|
|
81
|
+
) -> list[Finding]:
|
|
82
|
+
occ_kw = [p.power_kw for p in points if _is_occupied(p, cfg)]
|
|
83
|
+
night_pts = [
|
|
84
|
+
p
|
|
85
|
+
for p in points
|
|
86
|
+
if cfg.night_start_hour <= p.timestamp.hour < cfg.night_end_hour
|
|
87
|
+
]
|
|
88
|
+
if len(occ_kw) < 4 or len(night_pts) < 4:
|
|
89
|
+
return []
|
|
90
|
+
|
|
91
|
+
med_occ = median(occ_kw)
|
|
92
|
+
if med_occ <= 1.0:
|
|
93
|
+
return []
|
|
94
|
+
|
|
95
|
+
by_night: dict[date, list[TelemetryPoint]] = defaultdict(list)
|
|
96
|
+
for p in night_pts:
|
|
97
|
+
by_night[p.timestamp.date()].append(p)
|
|
98
|
+
|
|
99
|
+
offending_nights: list[tuple[date, float]] = []
|
|
100
|
+
offending_pts: list[TelemetryPoint] = []
|
|
101
|
+
for d, pts in sorted(by_night.items()):
|
|
102
|
+
if len(pts) < 2:
|
|
103
|
+
continue
|
|
104
|
+
m_night = median(p.power_kw for p in pts)
|
|
105
|
+
if (m_night / med_occ) > cfg.phantom_baseload_ratio and m_night >= 5.0:
|
|
106
|
+
offending_nights.append((d, m_night))
|
|
107
|
+
offending_pts.extend(pts)
|
|
108
|
+
|
|
109
|
+
if not offending_pts or (len(offending_nights) < 2 and len(offending_nights) < len(by_night)):
|
|
110
|
+
return []
|
|
111
|
+
|
|
112
|
+
med_bad_night = median(p.power_kw for p in offending_pts)
|
|
113
|
+
ratio = med_bad_night / med_occ
|
|
114
|
+
target_night_kw = med_occ * cfg.phantom_target_ratio
|
|
115
|
+
waste_kwh = sum(max(0.0, p.power_kw - target_night_kw) * dt_h for p in offending_pts)
|
|
116
|
+
cost_irr = sum(
|
|
117
|
+
max(0.0, p.power_kw - target_night_kw)
|
|
118
|
+
* dt_h
|
|
119
|
+
* cfg.base_kwh_price_irr
|
|
120
|
+
* tariff.multiplier_for(p.timestamp)
|
|
121
|
+
for p in offending_pts
|
|
122
|
+
)
|
|
123
|
+
severity = Severity.CRITICAL if ratio >= 0.65 else Severity.WARNING
|
|
124
|
+
return [
|
|
125
|
+
Finding(
|
|
126
|
+
code="PHANTOM_BASELOAD",
|
|
127
|
+
title="Excessive unoccupied night baseload (schedule drift)",
|
|
128
|
+
severity=severity,
|
|
129
|
+
summary=(
|
|
130
|
+
f"Median night load ({med_bad_night:.1f} kW) across "
|
|
131
|
+
f"{len(offending_nights)}/{len(by_night)} nights is {ratio * 100:.0f}% of "
|
|
132
|
+
f"daytime occupied median ({med_occ:.1f} kW), exceeding the "
|
|
133
|
+
f"{cfg.phantom_baseload_ratio * 100:.0f}% threshold."
|
|
134
|
+
),
|
|
135
|
+
estimated_waste_kwh=round(waste_kwh, 2),
|
|
136
|
+
estimated_cost_irr=round(cost_irr, 0),
|
|
137
|
+
start_time=offending_pts[0].timestamp.isoformat(),
|
|
138
|
+
end_time=offending_pts[-1].timestamp.isoformat(),
|
|
139
|
+
evidence={
|
|
140
|
+
"affected_nights": len(offending_nights),
|
|
141
|
+
"total_nights": len(by_night),
|
|
142
|
+
"median_occupied_kw": round(med_occ, 2),
|
|
143
|
+
"median_night_kw": round(med_bad_night, 2),
|
|
144
|
+
"night_to_day_ratio": round(ratio, 3),
|
|
145
|
+
"target_standby_kw": round(target_night_kw, 2),
|
|
146
|
+
},
|
|
147
|
+
)
|
|
148
|
+
]
|
|
149
|
+
|
|
150
|
+
|
|
151
|
+
def detect_sensor_flatline(
|
|
152
|
+
points: list[TelemetryPoint],
|
|
153
|
+
dt_h: float,
|
|
154
|
+
cfg: AuditConfig,
|
|
155
|
+
) -> list[Finding]:
|
|
156
|
+
channels = (
|
|
157
|
+
"supply_air_temp_c",
|
|
158
|
+
"chilled_water_supply_c",
|
|
159
|
+
"chilled_water_return_c",
|
|
160
|
+
"power_kw",
|
|
161
|
+
)
|
|
162
|
+
min_samples = max(4, int(math.ceil(cfg.flatline_min_hours / max(dt_h, 1e-6))))
|
|
163
|
+
findings: list[Finding] = []
|
|
164
|
+
|
|
165
|
+
for ch in channels:
|
|
166
|
+
best_run: list[TelemetryPoint] = []
|
|
167
|
+
current_run: list[TelemetryPoint] = []
|
|
168
|
+
last_val: float | None = None
|
|
169
|
+
last_ts = None
|
|
170
|
+
|
|
171
|
+
for p in points:
|
|
172
|
+
val = getattr(p, ch)
|
|
173
|
+
active = p.power_kw >= cfg.active_plant_kw_floor
|
|
174
|
+
gap_ok = (
|
|
175
|
+
last_ts is None
|
|
176
|
+
or ((p.timestamp - last_ts).total_seconds() / 3600.0) <= dt_h * 3.0
|
|
177
|
+
)
|
|
178
|
+
if val is not None and active and gap_ok and last_val is not None and abs(val - last_val) <= 1e-6:
|
|
179
|
+
current_run.append(p)
|
|
180
|
+
else:
|
|
181
|
+
if len(current_run) > len(best_run):
|
|
182
|
+
best_run = current_run
|
|
183
|
+
current_run = [p] if (val is not None and active) else []
|
|
184
|
+
last_val = val
|
|
185
|
+
last_ts = p.timestamp
|
|
186
|
+
|
|
187
|
+
if len(current_run) > len(best_run):
|
|
188
|
+
best_run = current_run
|
|
189
|
+
|
|
190
|
+
if len(best_run) >= min_samples:
|
|
191
|
+
dur_h = len(best_run) * dt_h
|
|
192
|
+
frozen_val = getattr(best_run[0], ch)
|
|
193
|
+
findings.append(
|
|
194
|
+
Finding(
|
|
195
|
+
code="SENSOR_FLATLINE",
|
|
196
|
+
title=f"Frozen sensor / flatlined telemetry on '{ch}'",
|
|
197
|
+
severity=Severity.WARNING,
|
|
198
|
+
summary=(
|
|
199
|
+
f"Channel '{ch}' stayed locked at {frozen_val:.2f} for {dur_h:.1f} hours "
|
|
200
|
+
f"while plant load was active, risking blind PID control."
|
|
201
|
+
),
|
|
202
|
+
start_time=best_run[0].timestamp.isoformat(),
|
|
203
|
+
end_time=best_run[-1].timestamp.isoformat(),
|
|
204
|
+
evidence={
|
|
205
|
+
"channel": ch,
|
|
206
|
+
"frozen_value": round(float(frozen_val), 3),
|
|
207
|
+
"duration_hours": round(dur_h, 2),
|
|
208
|
+
"sample_count": len(best_run),
|
|
209
|
+
},
|
|
210
|
+
)
|
|
211
|
+
)
|
|
212
|
+
return findings
|
|
213
|
+
|
|
214
|
+
|
|
215
|
+
def detect_chiller_low_delta_t(
|
|
216
|
+
points: list[TelemetryPoint],
|
|
217
|
+
dt_h: float,
|
|
218
|
+
cfg: AuditConfig,
|
|
219
|
+
tariff: IranTariffProfile,
|
|
220
|
+
) -> list[Finding]:
|
|
221
|
+
has_cooling_valve = any(p.cooling_valve_pct is not None for p in points)
|
|
222
|
+
night_kw = [
|
|
223
|
+
p.power_kw
|
|
224
|
+
for p in points
|
|
225
|
+
if cfg.night_start_hour <= p.timestamp.hour < cfg.night_end_hour
|
|
226
|
+
]
|
|
227
|
+
standby_floor = (median(night_kw) + 15.0) if night_kw else cfg.active_plant_kw_floor
|
|
228
|
+
active_floor = max(cfg.active_plant_kw_floor, standby_floor)
|
|
229
|
+
|
|
230
|
+
active_chw: list[tuple[TelemetryPoint, float]] = []
|
|
231
|
+
for p in points:
|
|
232
|
+
if p.chilled_water_supply_c is None or p.chilled_water_return_c is None:
|
|
233
|
+
continue
|
|
234
|
+
plant_on = (
|
|
235
|
+
(p.cooling_valve_pct or 0.0) >= 15.0
|
|
236
|
+
if has_cooling_valve
|
|
237
|
+
else p.power_kw >= active_floor
|
|
238
|
+
)
|
|
239
|
+
if plant_on and p.power_kw >= cfg.active_plant_kw_floor:
|
|
240
|
+
active_chw.append((p, p.chilled_water_return_c - p.chilled_water_supply_c))
|
|
241
|
+
|
|
242
|
+
if len(active_chw) < 8:
|
|
243
|
+
return []
|
|
244
|
+
|
|
245
|
+
low_pts = [(p, dt) for p, dt in active_chw if dt < cfg.low_delta_t_c]
|
|
246
|
+
frac = len(low_pts) / len(active_chw)
|
|
247
|
+
if frac < cfg.low_delta_t_min_fraction or len(low_pts) < 4:
|
|
248
|
+
return []
|
|
249
|
+
|
|
250
|
+
avg_low_dt = mean(dt for _, dt in low_pts)
|
|
251
|
+
waste_kwh = sum(p.power_kw * dt_h * 0.15 for p, _ in low_pts)
|
|
252
|
+
cost_irr = sum(
|
|
253
|
+
p.power_kw * dt_h * 0.15 * cfg.base_kwh_price_irr * tariff.multiplier_for(p.timestamp)
|
|
254
|
+
for p, _ in low_pts
|
|
255
|
+
)
|
|
256
|
+
severity = Severity.CRITICAL if frac >= 0.35 else Severity.WARNING
|
|
257
|
+
return [
|
|
258
|
+
Finding(
|
|
259
|
+
code="CHILLER_LOW_DELTA_T",
|
|
260
|
+
title="Chiller Low-Delta-T syndrome (over-pumping / coil fouling)",
|
|
261
|
+
severity=severity,
|
|
262
|
+
summary=(
|
|
263
|
+
f"Chilled-water Delta-T fell below {cfg.low_delta_t_c:.1f} C during "
|
|
264
|
+
f"{frac * 100:.1f}% of active cooling hours (mean low Delta-T = {avg_low_dt:.2f} C)."
|
|
265
|
+
),
|
|
266
|
+
estimated_waste_kwh=round(waste_kwh, 2),
|
|
267
|
+
estimated_cost_irr=round(cost_irr, 0),
|
|
268
|
+
start_time=low_pts[0][0].timestamp.isoformat(),
|
|
269
|
+
end_time=low_pts[-1][0].timestamp.isoformat(),
|
|
270
|
+
evidence={
|
|
271
|
+
"affected_fraction": round(frac, 3),
|
|
272
|
+
"mean_low_delta_t_c": round(avg_low_dt, 2),
|
|
273
|
+
"design_reference_delta_t_c": 5.5,
|
|
274
|
+
"affected_hours": round(len(low_pts) * dt_h, 2),
|
|
275
|
+
},
|
|
276
|
+
)
|
|
277
|
+
]
|
|
278
|
+
|
|
279
|
+
|
|
280
|
+
def _weather_adjusted_residuals(points: list[TelemetryPoint]) -> list[float]:
|
|
281
|
+
"""Subtract linear cooling/heating degree dependence on outdoor temperature."""
|
|
282
|
+
paired = [(i, p.outdoor_temp_c, p.power_kw) for i, p in enumerate(points) if p.outdoor_temp_c is not None]
|
|
283
|
+
if len(paired) < len(points) * 0.8 or len(paired) < 10:
|
|
284
|
+
avg_p = mean(p.power_kw for p in points)
|
|
285
|
+
return [p.power_kw - avg_p for p in points]
|
|
286
|
+
|
|
287
|
+
mean_oat = mean(t for _, t, _ in paired)
|
|
288
|
+
cooling_mode = mean_oat >= 18.0
|
|
289
|
+
xs = [max(0.0, t - 18.0) if cooling_mode else max(0.0, 16.0 - t) for _, t, _ in paired]
|
|
290
|
+
ys = [kw for _, _, kw in paired]
|
|
291
|
+
|
|
292
|
+
mx, my = mean(xs), mean(ys)
|
|
293
|
+
sxx = sum((x - mx) ** 2 for x in xs)
|
|
294
|
+
if sxx < 1e-6:
|
|
295
|
+
return [p.power_kw - my for p in points]
|
|
296
|
+
|
|
297
|
+
slope = sum((x - mx) * (y - my) for x, y in zip(xs, ys)) / sxx
|
|
298
|
+
intercept = my - slope * mx
|
|
299
|
+
|
|
300
|
+
residuals: list[float] = []
|
|
301
|
+
for p in points:
|
|
302
|
+
if p.outdoor_temp_c is None:
|
|
303
|
+
residuals.append(0.0)
|
|
304
|
+
else:
|
|
305
|
+
x = max(0.0, p.outdoor_temp_c - 18.0) if cooling_mode else max(0.0, 16.0 - p.outdoor_temp_c)
|
|
306
|
+
residuals.append(p.power_kw - (intercept + slope * x))
|
|
307
|
+
return residuals
|
|
308
|
+
|
|
309
|
+
|
|
310
|
+
def detect_regime_changepoint(
|
|
311
|
+
points: list[TelemetryPoint],
|
|
312
|
+
dt_h: float,
|
|
313
|
+
cfg: AuditConfig,
|
|
314
|
+
tariff: IranTariffProfile,
|
|
315
|
+
) -> list[Finding]:
|
|
316
|
+
residuals = _weather_adjusted_residuals(points)
|
|
317
|
+
by_day: dict[date, list[float]] = defaultdict(list)
|
|
318
|
+
for p, r in zip(points, residuals):
|
|
319
|
+
by_day[p.timestamp.date()].append(r)
|
|
320
|
+
|
|
321
|
+
days = sorted(by_day.keys())
|
|
322
|
+
if len(days) < 6:
|
|
323
|
+
return []
|
|
324
|
+
|
|
325
|
+
daily_means = [mean(by_day[d]) for d in days]
|
|
326
|
+
best_k: int | None = None
|
|
327
|
+
best_score = 0.0
|
|
328
|
+
best_delta = 0.0
|
|
329
|
+
|
|
330
|
+
for k in range(2, len(days) - 1):
|
|
331
|
+
before = daily_means[:k]
|
|
332
|
+
after = daily_means[k:]
|
|
333
|
+
delta = mean(after) - mean(before)
|
|
334
|
+
if delta <= cfg.changepoint_min_delta_kw:
|
|
335
|
+
continue
|
|
336
|
+
v1 = variance(before) if len(before) > 1 else 0.0
|
|
337
|
+
v2 = variance(after) if len(after) > 1 else 0.0
|
|
338
|
+
se = math.sqrt(v1 / len(before) + v2 / len(after) + 1.0)
|
|
339
|
+
score = delta / se
|
|
340
|
+
if score > best_score:
|
|
341
|
+
best_score = score
|
|
342
|
+
best_k = k
|
|
343
|
+
best_delta = delta
|
|
344
|
+
|
|
345
|
+
if best_k is None or best_score < cfg.changepoint_min_z:
|
|
346
|
+
return []
|
|
347
|
+
|
|
348
|
+
shift_day = days[best_k]
|
|
349
|
+
post_pts = [p for p in points if p.timestamp.date() >= shift_day]
|
|
350
|
+
waste_kwh = best_delta * len(post_pts) * dt_h
|
|
351
|
+
cost_irr = sum(
|
|
352
|
+
best_delta * dt_h * cfg.base_kwh_price_irr * tariff.multiplier_for(p.timestamp)
|
|
353
|
+
for p in post_pts
|
|
354
|
+
)
|
|
355
|
+
return [
|
|
356
|
+
Finding(
|
|
357
|
+
code="REGIME_CHANGE_POINT",
|
|
358
|
+
title="Upward baseline load shift (weather-adjusted change-point)",
|
|
359
|
+
severity=Severity.CRITICAL,
|
|
360
|
+
summary=(
|
|
361
|
+
f"Detected a persistent +{best_delta:.1f} kW weather-adjusted load step-up "
|
|
362
|
+
f"starting on {shift_day.isoformat()} (z={best_score:.2f})."
|
|
363
|
+
),
|
|
364
|
+
estimated_waste_kwh=round(waste_kwh, 2),
|
|
365
|
+
estimated_cost_irr=round(cost_irr, 0),
|
|
366
|
+
start_time=post_pts[0].timestamp.isoformat(),
|
|
367
|
+
end_time=post_pts[-1].timestamp.isoformat(),
|
|
368
|
+
evidence={
|
|
369
|
+
"changepoint_date": shift_day.isoformat(),
|
|
370
|
+
"step_increase_kw": round(best_delta, 2),
|
|
371
|
+
"z_score": round(best_score, 2),
|
|
372
|
+
"post_shift_days": len(days) - best_k,
|
|
373
|
+
},
|
|
374
|
+
)
|
|
375
|
+
]
|
|
376
|
+
|
|
377
|
+
|
|
378
|
+
def detect_peak_tariff_exposure(
|
|
379
|
+
points: list[TelemetryPoint],
|
|
380
|
+
dt_h: float,
|
|
381
|
+
cfg: AuditConfig,
|
|
382
|
+
tariff: IranTariffProfile,
|
|
383
|
+
) -> list[Finding]:
|
|
384
|
+
peak_all = [p for p in points if tariff.period_for(p.timestamp) == "peak"]
|
|
385
|
+
mid_all = [p for p in points if tariff.period_for(p.timestamp) == "mid_peak"]
|
|
386
|
+
occ_peak = [p for p in peak_all if _is_occupied(p, cfg)]
|
|
387
|
+
occ_mid = [p for p in mid_all if _is_occupied(p, cfg)]
|
|
388
|
+
|
|
389
|
+
# Compare occupied peak vs occupied mid-peak when occupied schedules overlap
|
|
390
|
+
use_occ = len(occ_peak) >= 4 and len(occ_mid) >= 4
|
|
391
|
+
peak_ref = occ_peak if use_occ else peak_all
|
|
392
|
+
mid_ref = occ_mid if use_occ else mid_all
|
|
393
|
+
|
|
394
|
+
if len(peak_ref) < 4 or len(mid_ref) < 4:
|
|
395
|
+
return []
|
|
396
|
+
|
|
397
|
+
avg_peak = mean(p.power_kw for p in peak_ref)
|
|
398
|
+
avg_mid = mean(p.power_kw for p in mid_ref)
|
|
399
|
+
max_peak = max(p.power_kw for p in peak_all)
|
|
400
|
+
ratio = avg_peak / max(avg_mid, 1.0)
|
|
401
|
+
|
|
402
|
+
cap_breach_pts = (
|
|
403
|
+
[p for p in peak_all if p.power_kw > cfg.contracted_demand_kw]
|
|
404
|
+
if cfg.contracted_demand_kw is not None
|
|
405
|
+
else []
|
|
406
|
+
)
|
|
407
|
+
if not cap_breach_pts and ratio <= cfg.peak_to_mid_ratio_limit:
|
|
408
|
+
return []
|
|
409
|
+
|
|
410
|
+
shiftable_kw = max(0.0, avg_peak - avg_mid)
|
|
411
|
+
shiftable_kwh = shiftable_kw * len(peak_ref) * dt_h
|
|
412
|
+
surcharge_delta = max(0.0, tariff.peak_multiplier - tariff.off_peak_multiplier)
|
|
413
|
+
avoidable_cost_irr = shiftable_kwh * cfg.base_kwh_price_irr * surcharge_delta
|
|
414
|
+
|
|
415
|
+
reasons: list[str] = []
|
|
416
|
+
if cap_breach_pts and cfg.contracted_demand_kw is not None:
|
|
417
|
+
reasons.append(
|
|
418
|
+
f"breached contracted demand cap ({cfg.contracted_demand_kw:.0f} kW) "
|
|
419
|
+
f"in {len(cap_breach_pts)} peak intervals (max {max_peak:.1f} kW)"
|
|
420
|
+
)
|
|
421
|
+
if ratio > cfg.peak_to_mid_ratio_limit:
|
|
422
|
+
reasons.append(
|
|
423
|
+
f"peak-window average ({avg_peak:.1f} kW) is {ratio:.2f}x mid-peak average ({avg_mid:.1f} kW)"
|
|
424
|
+
)
|
|
425
|
+
|
|
426
|
+
return [
|
|
427
|
+
Finding(
|
|
428
|
+
code="PEAK_TARIFF_EXPOSURE",
|
|
429
|
+
title="Iran peak-window overload & demand-cap exposure",
|
|
430
|
+
severity=Severity.CRITICAL if cap_breach_pts else Severity.WARNING,
|
|
431
|
+
summary="Facility " + " and ".join(reasons) + ".",
|
|
432
|
+
estimated_waste_kwh=0.0,
|
|
433
|
+
estimated_cost_irr=round(avoidable_cost_irr, 0),
|
|
434
|
+
start_time=peak_all[0].timestamp.isoformat(),
|
|
435
|
+
end_time=peak_all[-1].timestamp.isoformat(),
|
|
436
|
+
evidence={
|
|
437
|
+
"avg_peak_kw": round(avg_peak, 2),
|
|
438
|
+
"max_peak_kw": round(max_peak, 2),
|
|
439
|
+
"avg_mid_peak_kw": round(avg_mid, 2),
|
|
440
|
+
"peak_to_mid_ratio": round(ratio, 3),
|
|
441
|
+
"occupied_comparison": use_occ,
|
|
442
|
+
"contracted_demand_kw": cfg.contracted_demand_kw,
|
|
443
|
+
"cap_breach_intervals": len(cap_breach_pts),
|
|
444
|
+
"shiftable_peak_kwh": round(shiftable_kwh, 2),
|
|
445
|
+
},
|
|
446
|
+
)
|
|
447
|
+
]
|
|
448
|
+
|
|
449
|
+
|
|
450
|
+
def detect_short_cycling(
|
|
451
|
+
points: list[TelemetryPoint],
|
|
452
|
+
dt_h: float,
|
|
453
|
+
cfg: AuditConfig,
|
|
454
|
+
) -> list[Finding]:
|
|
455
|
+
# Short-cycling detection requires sub-20-minute telemetry
|
|
456
|
+
if dt_h > 0.34 or len(points) < 12:
|
|
457
|
+
return []
|
|
458
|
+
|
|
459
|
+
by_hour: dict[tuple[date, int], list[float]] = defaultdict(list)
|
|
460
|
+
for p in points:
|
|
461
|
+
by_hour[(p.timestamp.date(), p.timestamp.hour)].append(p.power_kw)
|
|
462
|
+
|
|
463
|
+
bad_hours: list[tuple[tuple[date, int], int, float]] = []
|
|
464
|
+
for key, vals in sorted(by_hour.items()):
|
|
465
|
+
if len(vals) < 6:
|
|
466
|
+
continue
|
|
467
|
+
lo, hi = min(vals), max(vals)
|
|
468
|
+
span = hi - lo
|
|
469
|
+
if span < cfg.short_cycle_min_swing_kw:
|
|
470
|
+
continue
|
|
471
|
+
high_th = lo + 0.65 * span
|
|
472
|
+
low_th = lo + 0.35 * span
|
|
473
|
+
is_on = vals[0] >= high_th
|
|
474
|
+
starts = 0
|
|
475
|
+
for v in vals[1:]:
|
|
476
|
+
if not is_on and v >= high_th:
|
|
477
|
+
is_on = True
|
|
478
|
+
starts += 1
|
|
479
|
+
elif is_on and v <= low_th:
|
|
480
|
+
is_on = False
|
|
481
|
+
if starts >= cfg.short_cycle_max_per_hour:
|
|
482
|
+
bad_hours.append((key, starts, round(span, 1)))
|
|
483
|
+
|
|
484
|
+
if not bad_hours:
|
|
485
|
+
return []
|
|
486
|
+
|
|
487
|
+
worst_key, worst_count, worst_span = max(bad_hours, key=lambda x: x[1])
|
|
488
|
+
return [
|
|
489
|
+
Finding(
|
|
490
|
+
code="SHORT_CYCLING",
|
|
491
|
+
title="Rapid compressor / equipment short-cycling",
|
|
492
|
+
severity=Severity.WARNING,
|
|
493
|
+
summary=(
|
|
494
|
+
f"Detected {len(bad_hours)} hour(s) with >={cfg.short_cycle_max_per_hour} "
|
|
495
|
+
f"ON/OFF swings/hour (worst: {worst_count} starts, {worst_span:.1f} kW swing at "
|
|
496
|
+
f"{worst_key[0].isoformat()} {worst_key[1]:02d}:00)."
|
|
497
|
+
),
|
|
498
|
+
evidence={
|
|
499
|
+
"affected_hours": len(bad_hours),
|
|
500
|
+
"max_starts_per_hour": worst_count,
|
|
501
|
+
"worst_swing_kw": worst_span,
|
|
502
|
+
"worst_hour": f"{worst_key[0].isoformat()}T{worst_key[1]:02d}:00",
|
|
503
|
+
},
|
|
504
|
+
)
|
|
505
|
+
]
|
|
@@ -0,0 +1,81 @@
|
|
|
1
|
+
from __future__ import annotations
|
|
2
|
+
|
|
3
|
+
from datetime import datetime, timezone
|
|
4
|
+
from pathlib import Path
|
|
5
|
+
|
|
6
|
+
from .detectors import (
|
|
7
|
+
detect_chiller_low_delta_t,
|
|
8
|
+
detect_peak_tariff_exposure,
|
|
9
|
+
detect_phantom_baseload,
|
|
10
|
+
detect_regime_changepoint,
|
|
11
|
+
detect_sensor_flatline,
|
|
12
|
+
detect_short_cycling,
|
|
13
|
+
detect_simultaneous_heat_cool,
|
|
14
|
+
infer_timestep_hours,
|
|
15
|
+
)
|
|
16
|
+
from .io import load_telemetry, sha256_dict, sha256_file
|
|
17
|
+
from .schema import AuditConfig, AuditReport, Severity, TelemetryPoint
|
|
18
|
+
from .tariffs import IranTariffProfile
|
|
19
|
+
|
|
20
|
+
__version__ = "0.1.0"
|
|
21
|
+
|
|
22
|
+
_SEVERITY_ORDER = {Severity.CRITICAL: 0, Severity.WARNING: 1, Severity.INFO: 2}
|
|
23
|
+
|
|
24
|
+
|
|
25
|
+
def audit_records(
|
|
26
|
+
points: list[TelemetryPoint],
|
|
27
|
+
config: AuditConfig | None = None,
|
|
28
|
+
tariff: IranTariffProfile | None = None,
|
|
29
|
+
source_path: str = "<in-memory>",
|
|
30
|
+
source_sha256: str = "",
|
|
31
|
+
) -> AuditReport:
|
|
32
|
+
cfg = config or AuditConfig()
|
|
33
|
+
tar = tariff or IranTariffProfile()
|
|
34
|
+
dt_h = infer_timestep_hours(points)
|
|
35
|
+
|
|
36
|
+
findings = []
|
|
37
|
+
findings.extend(detect_simultaneous_heat_cool(points, dt_h, cfg, tar))
|
|
38
|
+
findings.extend(detect_phantom_baseload(points, dt_h, cfg, tar))
|
|
39
|
+
findings.extend(detect_sensor_flatline(points, dt_h, cfg))
|
|
40
|
+
findings.extend(detect_chiller_low_delta_t(points, dt_h, cfg, tar))
|
|
41
|
+
findings.extend(detect_regime_changepoint(points, dt_h, cfg, tar))
|
|
42
|
+
findings.extend(detect_peak_tariff_exposure(points, dt_h, cfg, tar))
|
|
43
|
+
findings.extend(detect_short_cycling(points, dt_h, cfg))
|
|
44
|
+
|
|
45
|
+
findings.sort(key=lambda f: (_SEVERITY_ORDER[f.severity], -f.estimated_cost_irr, f.code))
|
|
46
|
+
|
|
47
|
+
total_kwh = sum(p.power_kw * dt_h for p in points)
|
|
48
|
+
peak_kwh = sum(p.power_kw * dt_h for p in points if tar.period_for(p.timestamp) == "peak")
|
|
49
|
+
total_waste_kwh = sum(f.estimated_waste_kwh for f in findings)
|
|
50
|
+
total_cost_irr = sum(f.estimated_cost_irr for f in findings)
|
|
51
|
+
|
|
52
|
+
return AuditReport(
|
|
53
|
+
tool_version=__version__,
|
|
54
|
+
audited_at_utc=datetime.now(timezone.utc).isoformat(),
|
|
55
|
+
source_path=source_path,
|
|
56
|
+
source_sha256=source_sha256,
|
|
57
|
+
config_sha256=sha256_dict(cfg.to_dict()),
|
|
58
|
+
record_count=len(points),
|
|
59
|
+
timestep_hours=dt_h,
|
|
60
|
+
total_energy_kwh=total_kwh,
|
|
61
|
+
peak_energy_kwh=peak_kwh,
|
|
62
|
+
total_estimated_waste_kwh=total_waste_kwh,
|
|
63
|
+
total_estimated_cost_irr=total_cost_irr,
|
|
64
|
+
findings=findings,
|
|
65
|
+
)
|
|
66
|
+
|
|
67
|
+
|
|
68
|
+
def audit_file(
|
|
69
|
+
path: str | Path,
|
|
70
|
+
config: AuditConfig | None = None,
|
|
71
|
+
tariff: IranTariffProfile | None = None,
|
|
72
|
+
) -> AuditReport:
|
|
73
|
+
p = Path(path)
|
|
74
|
+
points = load_telemetry(p)
|
|
75
|
+
return audit_records(
|
|
76
|
+
points=points,
|
|
77
|
+
config=config,
|
|
78
|
+
tariff=tariff,
|
|
79
|
+
source_path=str(p),
|
|
80
|
+
source_sha256=sha256_file(p),
|
|
81
|
+
)
|
|
@@ -0,0 +1,119 @@
|
|
|
1
|
+
from __future__ import annotations
|
|
2
|
+
|
|
3
|
+
import csv
|
|
4
|
+
import hashlib
|
|
5
|
+
import json
|
|
6
|
+
from datetime import datetime
|
|
7
|
+
from pathlib import Path
|
|
8
|
+
from typing import Any
|
|
9
|
+
|
|
10
|
+
from .schema import TelemetryPoint
|
|
11
|
+
|
|
12
|
+
COLUMN_ALIASES: dict[str, tuple[str, ...]] = {
|
|
13
|
+
"timestamp": ("timestamp", "time", "datetime", "ts", "date_time"),
|
|
14
|
+
"power_kw": ("power_kw", "kw", "active_power_kw", "load_kw", "elec_kw"),
|
|
15
|
+
"outdoor_temp_c": ("outdoor_temp_c", "oat", "t_out", "ambient_temp_c"),
|
|
16
|
+
"supply_air_temp_c": ("supply_air_temp_c", "sat", "t_sa"),
|
|
17
|
+
"chilled_water_supply_c": ("chilled_water_supply_c", "chws", "chw_supply_c"),
|
|
18
|
+
"chilled_water_return_c": ("chilled_water_return_c", "chwr", "chw_return_c"),
|
|
19
|
+
"heating_valve_pct": ("heating_valve_pct", "hw_valve", "heat_valve_pct"),
|
|
20
|
+
"cooling_valve_pct": ("cooling_valve_pct", "cw_valve", "cool_valve_pct"),
|
|
21
|
+
"gas_m3_hr": ("gas_m3_hr", "gas_flow", "gas_m3h"),
|
|
22
|
+
}
|
|
23
|
+
|
|
24
|
+
|
|
25
|
+
def sha256_file(path: Path) -> str:
|
|
26
|
+
h = hashlib.sha256()
|
|
27
|
+
with path.open("rb") as f:
|
|
28
|
+
for chunk in iter(lambda: f.read(65_536), b""):
|
|
29
|
+
h.update(chunk)
|
|
30
|
+
return h.hexdigest()
|
|
31
|
+
|
|
32
|
+
|
|
33
|
+
def sha256_dict(payload: dict[str, Any]) -> str:
|
|
34
|
+
raw = json.dumps(payload, sort_keys=True, separators=(",", ":")).encode("utf-8")
|
|
35
|
+
return hashlib.sha256(raw).hexdigest()
|
|
36
|
+
|
|
37
|
+
|
|
38
|
+
def _parse_float(raw: Any) -> float | None:
|
|
39
|
+
if raw is None:
|
|
40
|
+
return None
|
|
41
|
+
text = str(raw).strip()
|
|
42
|
+
if text == "" or text.lower() in {"na", "nan", "null", "none"}:
|
|
43
|
+
return None
|
|
44
|
+
return float(text)
|
|
45
|
+
|
|
46
|
+
|
|
47
|
+
def _parse_ts(raw: str) -> datetime:
|
|
48
|
+
text = raw.strip()
|
|
49
|
+
if text.endswith("Z"):
|
|
50
|
+
text = text[:-1] + "+00:00"
|
|
51
|
+
return datetime.fromisoformat(text)
|
|
52
|
+
|
|
53
|
+
|
|
54
|
+
def _resolve_columns(fieldnames: list[str]) -> dict[str, str]:
|
|
55
|
+
lowered = {c.strip().lower(): c for c in fieldnames}
|
|
56
|
+
mapping: dict[str, str] = {}
|
|
57
|
+
for canonical, aliases in COLUMN_ALIASES.items():
|
|
58
|
+
for alias in aliases:
|
|
59
|
+
if alias in lowered:
|
|
60
|
+
mapping[canonical] = lowered[alias]
|
|
61
|
+
break
|
|
62
|
+
return mapping
|
|
63
|
+
|
|
64
|
+
|
|
65
|
+
def _row_to_point(row: dict[str, Any], col_map: dict[str, str]) -> TelemetryPoint | None:
|
|
66
|
+
ts_raw = row.get(col_map["timestamp"])
|
|
67
|
+
kw_raw = _parse_float(row.get(col_map["power_kw"]))
|
|
68
|
+
if not ts_raw or kw_raw is None:
|
|
69
|
+
return None
|
|
70
|
+
|
|
71
|
+
def opt(field_name: str) -> float | None:
|
|
72
|
+
src = col_map.get(field_name)
|
|
73
|
+
return _parse_float(row.get(src)) if src else None
|
|
74
|
+
|
|
75
|
+
return TelemetryPoint(
|
|
76
|
+
timestamp=_parse_ts(str(ts_raw)),
|
|
77
|
+
power_kw=kw_raw,
|
|
78
|
+
outdoor_temp_c=opt("outdoor_temp_c"),
|
|
79
|
+
supply_air_temp_c=opt("supply_air_temp_c"),
|
|
80
|
+
chilled_water_supply_c=opt("chilled_water_supply_c"),
|
|
81
|
+
chilled_water_return_c=opt("chilled_water_return_c"),
|
|
82
|
+
heating_valve_pct=opt("heating_valve_pct"),
|
|
83
|
+
cooling_valve_pct=opt("cooling_valve_pct"),
|
|
84
|
+
gas_m3_hr=opt("gas_m3_hr"),
|
|
85
|
+
)
|
|
86
|
+
|
|
87
|
+
|
|
88
|
+
def load_telemetry(path: str | Path) -> list[TelemetryPoint]:
|
|
89
|
+
p = Path(path)
|
|
90
|
+
suffix = p.suffix.lower()
|
|
91
|
+
rows: list[dict[str, Any]] = []
|
|
92
|
+
|
|
93
|
+
if suffix == ".csv":
|
|
94
|
+
with p.open("r", encoding="utf-8-sig", newline="") as f:
|
|
95
|
+
reader = csv.DictReader(f)
|
|
96
|
+
if not reader.fieldnames:
|
|
97
|
+
raise ValueError(f"Empty CSV header in {p}")
|
|
98
|
+
col_map = _resolve_columns(list(reader.fieldnames))
|
|
99
|
+
rows = list(reader)
|
|
100
|
+
elif suffix in {".jsonl", ".ndjson"}:
|
|
101
|
+
with p.open("r", encoding="utf-8") as f:
|
|
102
|
+
for line in f:
|
|
103
|
+
if line.strip():
|
|
104
|
+
rows.append(json.loads(line))
|
|
105
|
+
if not rows:
|
|
106
|
+
raise ValueError(f"No records found in {p}")
|
|
107
|
+
col_map = _resolve_columns(list(rows[0].keys()))
|
|
108
|
+
else:
|
|
109
|
+
raise ValueError(f"Unsupported telemetry format '{suffix}'. Use .csv or .jsonl.")
|
|
110
|
+
|
|
111
|
+
if "timestamp" not in col_map or "power_kw" not in col_map:
|
|
112
|
+
raise ValueError(
|
|
113
|
+
"Telemetry must contain timestamp and power_kw columns "
|
|
114
|
+
f"(resolved: {list(col_map.keys())})."
|
|
115
|
+
)
|
|
116
|
+
|
|
117
|
+
points = [pt for row in rows if (pt := _row_to_point(row, col_map)) is not None]
|
|
118
|
+
points.sort(key=lambda x: x.timestamp)
|
|
119
|
+
return points
|
|
@@ -0,0 +1,70 @@
|
|
|
1
|
+
from __future__ import annotations
|
|
2
|
+
|
|
3
|
+
import json
|
|
4
|
+
import urllib.error
|
|
5
|
+
import urllib.request
|
|
6
|
+
|
|
7
|
+
from .schema import AuditReport
|
|
8
|
+
|
|
9
|
+
|
|
10
|
+
def _fallback_ticket(report: AuditReport, lang: str) -> str:
|
|
11
|
+
if lang == "fa":
|
|
12
|
+
lines = [
|
|
13
|
+
f"گزارش دستور کار نگهداری و بهینهسازی انرژی (tanzim v{report.tool_version})",
|
|
14
|
+
f"کل انرژی بررسیشده: {report.total_energy_kwh:,.1f} kWh | اتلاف برآوردی: {report.total_estimated_waste_kwh:,.1f} kWh",
|
|
15
|
+
"",
|
|
16
|
+
]
|
|
17
|
+
for idx, f in enumerate(report.findings, 1):
|
|
18
|
+
lines.append(f"{idx}. [{f.severity.value.upper()}] {f.code} — {f.title}")
|
|
19
|
+
lines.append(f" شرح فنی: {f.summary}")
|
|
20
|
+
lines.append(f" برآورد هزینه قابل صرفهجویی: {f.estimated_cost_irr:,.0f} ریال")
|
|
21
|
+
return "\n".join(lines)
|
|
22
|
+
|
|
23
|
+
lines = [
|
|
24
|
+
f"Maintenance & Energy Optimization Work Order (tanzim v{report.tool_version})",
|
|
25
|
+
f"Audited energy: {report.total_energy_kwh:,.1f} kWh | Estimated waste: {report.total_estimated_waste_kwh:,.1f} kWh",
|
|
26
|
+
"",
|
|
27
|
+
]
|
|
28
|
+
for idx, f in enumerate(report.findings, 1):
|
|
29
|
+
lines.append(f"{idx}. [{f.severity.value.upper()}] {f.code} — {f.title}")
|
|
30
|
+
lines.append(f" Details: {f.summary}")
|
|
31
|
+
return "\n".join(lines)
|
|
32
|
+
|
|
33
|
+
|
|
34
|
+
def generate_work_order(
|
|
35
|
+
report: AuditReport,
|
|
36
|
+
lang: str = "fa",
|
|
37
|
+
model: str = "gemma3:12b",
|
|
38
|
+
ollama_url: str = "http://localhost:11434/api/generate",
|
|
39
|
+
timeout_sec: int = 45,
|
|
40
|
+
) -> str:
|
|
41
|
+
"""Turn deterministic audit findings into a technician work order via local Ollama."""
|
|
42
|
+
if not report.findings:
|
|
43
|
+
return "هیچ خطای پنهان انرژی شناسایی نشد." if lang == "fa" else "No silent energy faults detected."
|
|
44
|
+
|
|
45
|
+
language_directive = (
|
|
46
|
+
"Write a clear, concise maintenance work order in natural Persian (Farsi) for a Tehran building facility engineer."
|
|
47
|
+
if lang == "fa"
|
|
48
|
+
else "Write a clear, concise maintenance work order in English for a building facility engineer."
|
|
49
|
+
)
|
|
50
|
+
prompt = (
|
|
51
|
+
f"{language_directive}\n"
|
|
52
|
+
"For each finding, list: (1) Root cause to inspect on-site, (2) Immediate corrective step, "
|
|
53
|
+
"(3) Expected energy/tariff benefit. Do not invent numbers outside the JSON.\n\n"
|
|
54
|
+
f"AUDIT JSON:\n{json.dumps(report.to_dict(), ensure_ascii=False, indent=2)}"
|
|
55
|
+
)
|
|
56
|
+
|
|
57
|
+
payload = json.dumps({"model": model, "prompt": prompt, "stream": False}).encode("utf-8")
|
|
58
|
+
req = urllib.request.Request(
|
|
59
|
+
ollama_url,
|
|
60
|
+
data=payload,
|
|
61
|
+
headers={"Content-Type": "application/json"},
|
|
62
|
+
method="POST",
|
|
63
|
+
)
|
|
64
|
+
try:
|
|
65
|
+
with urllib.request.urlopen(req, timeout=timeout_sec) as resp:
|
|
66
|
+
body = json.loads(resp.read().decode("utf-8"))
|
|
67
|
+
text = str(body.get("response", "")).strip()
|
|
68
|
+
return text or _fallback_ticket(report, lang)
|
|
69
|
+
except (urllib.error.URLError, TimeoutError, ValueError):
|
|
70
|
+
return _fallback_ticket(report, lang)
|
|
@@ -0,0 +1,103 @@
|
|
|
1
|
+
from __future__ import annotations
|
|
2
|
+
|
|
3
|
+
from dataclasses import asdict, dataclass, field
|
|
4
|
+
from datetime import datetime
|
|
5
|
+
from enum import Enum
|
|
6
|
+
from typing import Any
|
|
7
|
+
|
|
8
|
+
|
|
9
|
+
class Severity(str, Enum):
|
|
10
|
+
INFO = "info"
|
|
11
|
+
WARNING = "warning"
|
|
12
|
+
CRITICAL = "critical"
|
|
13
|
+
|
|
14
|
+
|
|
15
|
+
@dataclass(frozen=True)
|
|
16
|
+
class TelemetryPoint:
|
|
17
|
+
timestamp: datetime
|
|
18
|
+
power_kw: float
|
|
19
|
+
outdoor_temp_c: float | None = None
|
|
20
|
+
supply_air_temp_c: float | None = None
|
|
21
|
+
chilled_water_supply_c: float | None = None
|
|
22
|
+
chilled_water_return_c: float | None = None
|
|
23
|
+
heating_valve_pct: float | None = None
|
|
24
|
+
cooling_valve_pct: float | None = None
|
|
25
|
+
gas_m3_hr: float | None = None
|
|
26
|
+
|
|
27
|
+
|
|
28
|
+
@dataclass(frozen=True)
|
|
29
|
+
class Finding:
|
|
30
|
+
code: str
|
|
31
|
+
title: str
|
|
32
|
+
severity: Severity
|
|
33
|
+
summary: str
|
|
34
|
+
estimated_waste_kwh: float = 0.0
|
|
35
|
+
estimated_cost_irr: float = 0.0
|
|
36
|
+
start_time: str | None = None
|
|
37
|
+
end_time: str | None = None
|
|
38
|
+
evidence: dict[str, Any] = field(default_factory=dict)
|
|
39
|
+
|
|
40
|
+
def to_dict(self) -> dict[str, Any]:
|
|
41
|
+
data = asdict(self)
|
|
42
|
+
data["severity"] = self.severity.value
|
|
43
|
+
return data
|
|
44
|
+
|
|
45
|
+
|
|
46
|
+
@dataclass(frozen=True)
|
|
47
|
+
class AuditConfig:
|
|
48
|
+
occupied_start_hour: int = 8
|
|
49
|
+
occupied_end_hour: int = 17
|
|
50
|
+
night_start_hour: int = 0
|
|
51
|
+
night_end_hour: int = 5
|
|
52
|
+
# Iran weekends: Friday (weekday() == 4) and optionally Thursday afternoon
|
|
53
|
+
weekend_weekdays: tuple[int, ...] = (4,)
|
|
54
|
+
simultaneous_valve_pct: float = 15.0
|
|
55
|
+
simultaneous_min_hours: float = 1.0
|
|
56
|
+
phantom_baseload_ratio: float = 0.45
|
|
57
|
+
phantom_target_ratio: float = 0.25
|
|
58
|
+
flatline_min_hours: float = 2.0
|
|
59
|
+
low_delta_t_c: float = 2.5
|
|
60
|
+
low_delta_t_min_fraction: float = 0.20
|
|
61
|
+
active_plant_kw_floor: float = 15.0
|
|
62
|
+
changepoint_min_z: float = 3.5
|
|
63
|
+
changepoint_min_delta_kw: float = 10.0
|
|
64
|
+
short_cycle_max_per_hour: int = 4
|
|
65
|
+
short_cycle_min_swing_kw: float = 25.0
|
|
66
|
+
contracted_demand_kw: float | None = None
|
|
67
|
+
peak_to_mid_ratio_limit: float = 1.30
|
|
68
|
+
base_kwh_price_irr: float = 12_000.0 # Configurable commercial/industrial IRR/kWh
|
|
69
|
+
|
|
70
|
+
def to_dict(self) -> dict[str, Any]:
|
|
71
|
+
return asdict(self)
|
|
72
|
+
|
|
73
|
+
|
|
74
|
+
@dataclass(frozen=True)
|
|
75
|
+
class AuditReport:
|
|
76
|
+
tool_version: str
|
|
77
|
+
audited_at_utc: str
|
|
78
|
+
source_path: str
|
|
79
|
+
source_sha256: str
|
|
80
|
+
config_sha256: str
|
|
81
|
+
record_count: int
|
|
82
|
+
timestep_hours: float
|
|
83
|
+
total_energy_kwh: float
|
|
84
|
+
peak_energy_kwh: float
|
|
85
|
+
total_estimated_waste_kwh: float
|
|
86
|
+
total_estimated_cost_irr: float
|
|
87
|
+
findings: list[Finding]
|
|
88
|
+
|
|
89
|
+
def to_dict(self) -> dict[str, Any]:
|
|
90
|
+
return {
|
|
91
|
+
"tool_version": self.tool_version,
|
|
92
|
+
"audited_at_utc": self.audited_at_utc,
|
|
93
|
+
"source_path": self.source_path,
|
|
94
|
+
"source_sha256": self.source_sha256,
|
|
95
|
+
"config_sha256": self.config_sha256,
|
|
96
|
+
"record_count": self.record_count,
|
|
97
|
+
"timestep_hours": round(self.timestep_hours, 4),
|
|
98
|
+
"total_energy_kwh": round(self.total_energy_kwh, 2),
|
|
99
|
+
"peak_energy_kwh": round(self.peak_energy_kwh, 2),
|
|
100
|
+
"total_estimated_waste_kwh": round(self.total_estimated_waste_kwh, 2),
|
|
101
|
+
"total_estimated_cost_irr": round(self.total_estimated_cost_irr, 0),
|
|
102
|
+
"findings": [f.to_dict() for f in self.findings],
|
|
103
|
+
}
|
|
@@ -0,0 +1,118 @@
|
|
|
1
|
+
from __future__ import annotations
|
|
2
|
+
|
|
3
|
+
import csv
|
|
4
|
+
import math
|
|
5
|
+
import random
|
|
6
|
+
from datetime import datetime, timedelta
|
|
7
|
+
from pathlib import Path
|
|
8
|
+
|
|
9
|
+
from .schema import TelemetryPoint
|
|
10
|
+
|
|
11
|
+
|
|
12
|
+
def generate_tehran_summer_bms(
|
|
13
|
+
days: int = 14,
|
|
14
|
+
step_minutes: int = 10,
|
|
15
|
+
inject_faults: bool = True,
|
|
16
|
+
seed: int = 42,
|
|
17
|
+
) -> list[TelemetryPoint]:
|
|
18
|
+
"""Generate realistic Tehran summer commercial chiller/BMS telemetry."""
|
|
19
|
+
rng = random.Random(seed)
|
|
20
|
+
start = datetime(2026, 7, 1, 0, 0, 0)
|
|
21
|
+
total_steps = int((days * 24 * 60) / step_minutes)
|
|
22
|
+
points: list[TelemetryPoint] = []
|
|
23
|
+
|
|
24
|
+
for i in range(total_steps):
|
|
25
|
+
ts = start + timedelta(minutes=i * step_minutes)
|
|
26
|
+
day_idx = (ts - start).days
|
|
27
|
+
hour_f = ts.hour + ts.minute / 60.0
|
|
28
|
+
|
|
29
|
+
# Tehran July outdoor temperature cycle (~24C at 05:00 -> ~39C at 15:30)
|
|
30
|
+
oat = 31.5 - 7.5 * math.cos(2 * math.pi * (hour_f - 4.0) / 24.0) + rng.gauss(0, 0.3)
|
|
31
|
+
|
|
32
|
+
occupied = (ts.weekday() != 4) and (8 <= ts.hour < 17)
|
|
33
|
+
base_kw = 22.0 + rng.gauss(0, 0.8)
|
|
34
|
+
cooling_kw = max(0.0, (oat - 18.0) * 4.2) if occupied else 0.0
|
|
35
|
+
occ_internal_kw = 28.0 if occupied else 0.0
|
|
36
|
+
power_kw = base_kw + cooling_kw + occ_internal_kw
|
|
37
|
+
|
|
38
|
+
sat = 13.5 + rng.gauss(0, 0.25)
|
|
39
|
+
chws = 7.2 + rng.gauss(0, 0.12)
|
|
40
|
+
chwr = chws + (5.8 if occupied else 1.2) + rng.gauss(0, 0.15)
|
|
41
|
+
heat_v = 0.0
|
|
42
|
+
cool_v = min(100.0, max(0.0, (oat - 18.0) * 4.0)) if occupied else 0.0
|
|
43
|
+
|
|
44
|
+
if inject_faults:
|
|
45
|
+
# 1. Simultaneous heat/cool on Days 3-4 (09:00-15:00)
|
|
46
|
+
if day_idx in (3, 4) and 9 <= ts.hour < 15:
|
|
47
|
+
heat_v = 45.0
|
|
48
|
+
cool_v = 82.0
|
|
49
|
+
power_kw += 24.0
|
|
50
|
+
|
|
51
|
+
# 2. Frozen supply-air temperature sensor on Day 5 (08:00-14:00)
|
|
52
|
+
if day_idx == 5 and 8 <= ts.hour < 14:
|
|
53
|
+
sat = 13.40
|
|
54
|
+
|
|
55
|
+
# 3. Persistent +38 kW regime shift + phantom night baseload from Day 7 onward
|
|
56
|
+
if day_idx >= 7:
|
|
57
|
+
power_kw += 38.0
|
|
58
|
+
if 0 <= ts.hour < 5:
|
|
59
|
+
power_kw += 36.0 # Chiller/AHU left in manual hand mode overnight
|
|
60
|
+
|
|
61
|
+
# 4. Low Delta-T syndrome on Days 9-12
|
|
62
|
+
if day_idx in (9, 10, 11, 12) and occupied:
|
|
63
|
+
chwr = chws + 1.6 + rng.gauss(0, 0.08)
|
|
64
|
+
|
|
65
|
+
# 5. Severe summer peak overload (14:00-18:00) from Day 8 onward
|
|
66
|
+
if day_idx >= 8 and 14 <= ts.hour < 18:
|
|
67
|
+
power_kw += 55.0
|
|
68
|
+
|
|
69
|
+
# 6. Rapid compressor short-cycling on Day 12 (10:00-11:00) -> 6 cycles/hr at 10-min step?
|
|
70
|
+
# Use 10-min step: alternating ON/OFF every sample gives 3 starts; let's inject on 5-min or flag >=3
|
|
71
|
+
if day_idx == 12 and 10 <= ts.hour < 12:
|
|
72
|
+
power_kw = 155.0 if (i % 2 == 0) else 25.0
|
|
73
|
+
|
|
74
|
+
points.append(
|
|
75
|
+
TelemetryPoint(
|
|
76
|
+
timestamp=ts,
|
|
77
|
+
power_kw=round(max(0.0, power_kw), 2),
|
|
78
|
+
outdoor_temp_c=round(oat, 2),
|
|
79
|
+
supply_air_temp_c=round(sat, 2),
|
|
80
|
+
chilled_water_supply_c=round(chws, 2),
|
|
81
|
+
chilled_water_return_c=round(chwr, 2),
|
|
82
|
+
heating_valve_pct=round(heat_v, 1),
|
|
83
|
+
cooling_valve_pct=round(cool_v, 1),
|
|
84
|
+
)
|
|
85
|
+
)
|
|
86
|
+
return points
|
|
87
|
+
|
|
88
|
+
|
|
89
|
+
def write_telemetry_csv(points: list[TelemetryPoint], path: str | Path) -> Path:
|
|
90
|
+
out = Path(path)
|
|
91
|
+
out.parent.mkdir(parents=True, exist_ok=True)
|
|
92
|
+
fields = [
|
|
93
|
+
"timestamp",
|
|
94
|
+
"power_kw",
|
|
95
|
+
"outdoor_temp_c",
|
|
96
|
+
"supply_air_temp_c",
|
|
97
|
+
"chilled_water_supply_c",
|
|
98
|
+
"chilled_water_return_c",
|
|
99
|
+
"heating_valve_pct",
|
|
100
|
+
"cooling_valve_pct",
|
|
101
|
+
]
|
|
102
|
+
with out.open("w", encoding="utf-8", newline="") as f:
|
|
103
|
+
writer = csv.DictWriter(f, fieldnames=fields)
|
|
104
|
+
writer.writeheader()
|
|
105
|
+
for p in points:
|
|
106
|
+
writer.writerow(
|
|
107
|
+
{
|
|
108
|
+
"timestamp": p.timestamp.isoformat(),
|
|
109
|
+
"power_kw": p.power_kw,
|
|
110
|
+
"outdoor_temp_c": p.outdoor_temp_c,
|
|
111
|
+
"supply_air_temp_c": p.supply_air_temp_c,
|
|
112
|
+
"chilled_water_supply_c": p.chilled_water_supply_c,
|
|
113
|
+
"chilled_water_return_c": p.chilled_water_return_c,
|
|
114
|
+
"heating_valve_pct": p.heating_valve_pct,
|
|
115
|
+
"cooling_valve_pct": p.cooling_valve_pct,
|
|
116
|
+
}
|
|
117
|
+
)
|
|
118
|
+
return out
|
|
@@ -0,0 +1,53 @@
|
|
|
1
|
+
from __future__ import annotations
|
|
2
|
+
|
|
3
|
+
from dataclasses import dataclass
|
|
4
|
+
from datetime import datetime
|
|
5
|
+
|
|
6
|
+
|
|
7
|
+
@dataclass(frozen=True)
|
|
8
|
+
class TariffWindow:
|
|
9
|
+
peak_hours: tuple[int, int] # [start, end)
|
|
10
|
+
off_peak_hours: tuple[int, int] # [start, end)
|
|
11
|
+
|
|
12
|
+
|
|
13
|
+
@dataclass(frozen=True)
|
|
14
|
+
class IranTariffProfile:
|
|
15
|
+
"""Configurable seasonal Time-of-Use (ToU) schedule for Iranian commercial/industrial meters."""
|
|
16
|
+
|
|
17
|
+
spring: TariffWindow = TariffWindow(peak_hours=(21, 22), off_peak_hours=(1, 9))
|
|
18
|
+
summer: TariffWindow = TariffWindow(peak_hours=(14, 18), off_peak_hours=(3, 8))
|
|
19
|
+
autumn: TariffWindow = TariffWindow(peak_hours=(18, 21), off_peak_hours=(1, 9))
|
|
20
|
+
winter: TariffWindow = TariffWindow(peak_hours=(18, 21), off_peak_hours=(1, 9))
|
|
21
|
+
|
|
22
|
+
peak_multiplier: float = 2.5
|
|
23
|
+
mid_multiplier: float = 1.0
|
|
24
|
+
off_peak_multiplier: float = 0.5
|
|
25
|
+
|
|
26
|
+
def season_for(self, ts: datetime) -> str:
|
|
27
|
+
m = ts.month
|
|
28
|
+
if m in (3, 4, 5):
|
|
29
|
+
return "spring"
|
|
30
|
+
if m in (6, 7, 8):
|
|
31
|
+
return "summer"
|
|
32
|
+
if m in (9, 10, 11):
|
|
33
|
+
return "autumn"
|
|
34
|
+
return "winter"
|
|
35
|
+
|
|
36
|
+
def period_for(self, ts: datetime) -> str:
|
|
37
|
+
window: TariffWindow = getattr(self, self.season_for(ts))
|
|
38
|
+
h = ts.hour
|
|
39
|
+
p_start, p_end = window.peak_hours
|
|
40
|
+
o_start, o_end = window.off_peak_hours
|
|
41
|
+
if p_start <= h < p_end:
|
|
42
|
+
return "peak"
|
|
43
|
+
if o_start <= h < o_end:
|
|
44
|
+
return "off_peak"
|
|
45
|
+
return "mid_peak"
|
|
46
|
+
|
|
47
|
+
def multiplier_for(self, ts: datetime) -> float:
|
|
48
|
+
period = self.period_for(ts)
|
|
49
|
+
if period == "peak":
|
|
50
|
+
return self.peak_multiplier
|
|
51
|
+
if period == "off_peak":
|
|
52
|
+
return self.off_peak_multiplier
|
|
53
|
+
return self.mid_multiplier
|
|
@@ -0,0 +1,12 @@
|
|
|
1
|
+
Metadata-Version: 2.4
|
|
2
|
+
Name: tanzim
|
|
3
|
+
Version: 0.1.0
|
|
4
|
+
Summary: Offline-first silent-fault and energy-imbalance auditor for building BMS and industrial SCADA logs.
|
|
5
|
+
Author-email: Aslan Satary Dizaji <aslansatary@gmail.com>
|
|
6
|
+
License: MIT
|
|
7
|
+
Keywords: bms,scada,hvac,energy-audit,fault-detection,change-point
|
|
8
|
+
Requires-Python: >=3.10
|
|
9
|
+
Description-Content-Type: text/markdown
|
|
10
|
+
Provides-Extra: dev
|
|
11
|
+
Requires-Dist: pytest>=8.0; extra == "dev"
|
|
12
|
+
Requires-Dist: ruff>=0.6; extra == "dev"
|
|
@@ -0,0 +1,18 @@
|
|
|
1
|
+
pyproject.toml
|
|
2
|
+
src/tanzim/__init__.py
|
|
3
|
+
src/tanzim/__version__.py
|
|
4
|
+
src/tanzim/cli.py
|
|
5
|
+
src/tanzim/detectors.py
|
|
6
|
+
src/tanzim/engine.py
|
|
7
|
+
src/tanzim/io.py
|
|
8
|
+
src/tanzim/llm_tickets.py
|
|
9
|
+
src/tanzim/schema.py
|
|
10
|
+
src/tanzim/synthetic.py
|
|
11
|
+
src/tanzim/tariffs.py
|
|
12
|
+
src/tanzim.egg-info/PKG-INFO
|
|
13
|
+
src/tanzim.egg-info/SOURCES.txt
|
|
14
|
+
src/tanzim.egg-info/dependency_links.txt
|
|
15
|
+
src/tanzim.egg-info/entry_points.txt
|
|
16
|
+
src/tanzim.egg-info/requires.txt
|
|
17
|
+
src/tanzim.egg-info/top_level.txt
|
|
18
|
+
tests/test_tanzim.py
|
|
@@ -0,0 +1 @@
|
|
|
1
|
+
|
|
@@ -0,0 +1 @@
|
|
|
1
|
+
tanzim
|
|
@@ -0,0 +1,35 @@
|
|
|
1
|
+
from __future__ import annotations
|
|
2
|
+
|
|
3
|
+
from pathlib import Path
|
|
4
|
+
|
|
5
|
+
from tanzim import AuditConfig, audit_file, audit_records
|
|
6
|
+
from tanzim.synthetic import generate_tehran_summer_bms, write_telemetry_csv
|
|
7
|
+
|
|
8
|
+
|
|
9
|
+
def test_clean_tehran_plant_has_zero_false_positives() -> None:
|
|
10
|
+
pts = generate_tehran_summer_bms(days=14, step_minutes=5, inject_faults=False, seed=7)
|
|
11
|
+
report = audit_records(pts, config=AuditConfig(contracted_demand_kw=180.0))
|
|
12
|
+
assert report.findings == []
|
|
13
|
+
assert report.total_energy_kwh > 0
|
|
14
|
+
|
|
15
|
+
|
|
16
|
+
def test_faulted_tehran_plant_catches_all_seven_faults(tmp_path: Path) -> None:
|
|
17
|
+
pts = generate_tehran_summer_bms(days=14, step_minutes=5, inject_faults=True, seed=42)
|
|
18
|
+
csv_path = write_telemetry_csv(pts, tmp_path / "faulted.csv")
|
|
19
|
+
|
|
20
|
+
report = audit_file(csv_path, config=AuditConfig(contracted_demand_kw=180.0))
|
|
21
|
+
codes = {f.code for f in report.findings}
|
|
22
|
+
|
|
23
|
+
expected = {
|
|
24
|
+
"SIMULTANEOUS_HEAT_COOL",
|
|
25
|
+
"PHANTOM_BASELOAD",
|
|
26
|
+
"SENSOR_FLATLINE",
|
|
27
|
+
"CHILLER_LOW_DELTA_T",
|
|
28
|
+
"REGIME_CHANGE_POINT",
|
|
29
|
+
"PEAK_TARIFF_EXPOSURE",
|
|
30
|
+
"SHORT_CYCLING",
|
|
31
|
+
}
|
|
32
|
+
assert expected.issubset(codes)
|
|
33
|
+
assert len(report.source_sha256) == 64
|
|
34
|
+
assert report.total_estimated_waste_kwh > 0
|
|
35
|
+
assert report.total_estimated_cost_irr > 0
|